9702-2004-00P DG1-34016FB-C21C

General specifications
Product name
Eaton DG1 variable frequency drive
Part no.
DG1-34016FB-C21C
EAN
4015081721429
Product Length/Depth
244.7 millimetre
Product height
419 millimetre
Product width
167.8 millimetre
Product weight
10.7 kilogram
Certifications
IEC/EN61800-5
UkrSEPRO
CSA-C22.2 No. 274-13
IEC/EN61800-3
CUL
CE
UL File No.: E134360
Specification for general requirements: IEC/EN 61800-2
UL
C-Tick
Certified by UL for use in Canada
UL508
UL report applies to both US and Canada
Safety requirements: IEC/EN 61800-5
EAC
RoHS, ISO 9001
UL Category Control No.: NMMS, NMMS7
IEC/EN 61800-3
Product Tradename
DG1
Product Type
Variable frequency drive
Product Sub Type
None
Catalog Notes
The brake resistors are assigned based on the maximum rated power of the variable frequency drive. Additional brake resistors and designs (e.g. different duty cycles) are available upon request.
Features & Functions
Features
Temperature-controlled fan
Tool-less swapping of fan
Parameterization: Fieldbus
Parameterization: Keypad
Parameterization: Power Xpert inControl
Functions
4-quadrant operation possible
General information
Air volume capacity
94 m³/h
Cable length
150 m, screened, maximum permissible, Motor feeder
C2 ≤ 10 m, Radio interference level, maximum motor cable length
C3 ≤ 50 m, Radio interference level, maximum motor cable length
Degree of protection
NEMA 1
IP21
Electromagnetic compatibility
1st and 2nd environments (according to EN 61800-3)
Environmental class
3C2, 3S2 (Air quality)
Fitted with:
IGBT inverter
Internal DC link
Multi-line graphic display
PC connection
Brake chopper
Additional PCB protection
Breaking resistance
DC link choke
Radio interference suppression filter
Control unit
Frame size
FS2
Mounting position
Vertical
Number of slots
2 (expansion)
Overvoltage category
III
Pollution degree
2
Product Category
Variable frequency drives
Protection
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
Radio interference class
Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments
C1: with external filter, for conducted emissions only
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
Safety function/level
STO (Safe Torque Off, SIL1, PLc Cat 1)
Shock resistance
Storage and transportation: maximum 15 g, 11 ms (inside the packaging)
UPS drop test (for weights inside the UPS frame)
Mechanical, According to EN 61800-5-1, IEC/EN 60068-2-27
Suitable for
Branch circuits, (UL/CSA)
Vibration
Resistance: 15.8 – 150 Hz, 1 g, Maximum acceleration amplitude
Resistance: 5 - 150 Hz, According to EN 61800-5-1, IEC/EN 60068-2-6
Resistance: 5 - 15.8 Hz, Amplitude 1 mm (peak)
Climatic environmental conditions
Altitude
Max. 1000 m
Above 1000 m with 1 % derating per 100 m
Max. 2000 m for Corner Grounded TN Systems
Max. 3000 m
Ambient operating temperature - min
-10 °C
Ambient operating temperature - max
50 °C
Ambient operating temperature at 150% overload - min
-30 °C
Ambient operating temperature at 150% overload - max
50 °C
Ambient storage temperature - min
-40 °C
Ambient storage temperature - max
70 °C
Climatic proofing
< 95 average relative humidity (RH), no condensation, no corrosion
Main circuit
Current limitation
0.1 - 2 x IH (CT), motor, main circuit
Efficiency
98.2 % (η)
Heat dissipation at current/speed
110 W at 25% current and 50% speed
124 W at 100% current and 50% speed
145 W at 50% current and 50% speed
161 W at 50% current and 90% speed
165 W at 100% current and 0% speed
244 W at 50% current and 0% speed
276 W at 100% current and 90% speed
97 W at 25% current and 0% speed
Input current ILN at 110% overload
21.5 A
Input current ILN at 150% overload
15 A
Leakage current at ground IPE - max
9 mA
Mains current distortion
33.8 %
Mains switch-on frequency
Maximum of one time every 60 seconds
Mains voltage - min
380 V
Mains voltage - max
500 V
Operating mode
U/f control
Speed control with slip compensation
Torque regulation
Sensorless vector control (SLV)
Output frequency - min
0 Hz
Output frequency - max
400 Hz
Output voltage (U2)
400 V AC, 3-phase
480 V AC, 3-phase
500 V AC, 3-phase
Overload current IL at 110% overload
25.3 A
Overload current IL at 150% overload
24 A
Rated conditional short-circuit current (Iq)
100 kA
Rated control supply voltage
10 V DC (Us, max. 10 mA)
Rated frequency - min
45 Hz
Rated frequency - max
66 Hz
Rated operational current (Ie) at 110% overload
23 A
Rated operational current (Ie) at 150% overload
16 A
Rated operational power at 380/400 V, 50 Hz, 3-phase
7.5 kW
Rated operational power at 380/400 V, 50 Hz, 3-phase, 110% overload
11 kW
Rated operational power at 500 V, 50 Hz, 3-phase
7.5 kW
Rated operational power at 500 V, 50 Hz, 3-phase, 110% overload
11 kW
Rated operational voltage
400 V AC, 3-phase
500 V AC, 3-phase
480 V AC, 3-phase
Resolution
0.01 Hz (Frequency resolution, setpoint value)
Short-circuit protection rating
30 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
Starting current - max
200 %, IH, max. starting current (High Overload), For 2 seconds every 20 seconds, Power section
Supply frequency
50/60 Hz
Switching frequency
4 kHz, 1 - 12 kHz adjustable, fPWM, Power section, Main circuit
System configuration type
TN-S, TN-C, TN-C-S, TT, IT
Voltage rating - max
500 V AC
Motor rating
Assigned motor current IM at 400 V, 50 Hz, 110% overload
21.7 A
Assigned motor current IM at 400 V, 50 Hz, 150% overload
15.2 A
Assigned motor current IM at 440 - 480 V, 60 Hz, 150% overload
14 A
Assigned motor current IM at 440/480 V, 60 Hz, 110% overload
21 A
Assigned motor current IM at 500 V, 50 Hz, 110% overload
17.4 A
Assigned motor current IM at 500 V, 50 Hz, 150% overload
12.1 A
Assigned motor power at 460/480 V, 60 Hz, 3-phase
10 HP
Assigned motor power at 460/480 V, 60 Hz, 3-phase, 110 % overload
15 HP
Apparent power
Apparent power at 400 V
15.9 kV·A
Apparent power at 480 V
19.9 kV·A
Braking function
Braking resistance
42 O
Braking torque
Adjustable to 150 % (I/Ie), DC - Main circuit
Adjustable to 150 %, DC - Main circuit
Max. 100 % of rated operational current Ie with external braking resistor - Main circuit
Max. 30 % MN, Standard - Main circuit
Switch-on threshold for the braking transistor
850 V DC
Control circuit
Number of inputs (analog)
2
Number of inputs (digital)
8
Number of outputs (analog)
2
Number of outputs (digital)
1
Number of relay outputs
3 (parameterizable, 2 changeover contacts and 1 N/O, 6 A (240 V AC) / 6 A (24 V DC))
Rated control voltage (Uc)
24 V DC (external, max. 250 mA options incl.)
Communication
Communication interface
BACnet MS/TP, built in
Ethernet IP, built in
Modbus RTU, built in
PROFIBUS, optional
DeviceNet, optional
Modbus TCP, built in
CANopen®, optional
SmartWire-DT, optional
Connection to SmartWire-DT
In conjunction with DXG-NET-SWD SmartWire DT module
Yes
Protocol
TCP/IP
MODBUS
DeviceNet
PROFIBUS
CAN
PROFINET IO
BACnet
Other bus systems
EtherNet/IP
Design verification
Equipment heat dissipation, current-dependent Pvid
293 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
16 A
Static heat dissipation, non-current-dependent Pvs
15.75 W
Heat dissipation details
Operation (with 150 % overload), allow for derating
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 9.0

Low-voltage industrial components (EG000017) / Frequency converter =< 1 kV (EC001857)
Electric engineering, automation, process control engineering / Electrical drive / Static frequency converter / Static frequency / Servo converter = < 1 kV (ecl@ss13-27-02-31-01 [AKE177019])
Mains voltage
380 - 500 V
Mains frequency
50/60 Hz
Number of phases input
3
Number of phases output
3
Max. output frequency
400 Hz
Max. output voltage
500 V
Nominal output current I2N
16 A
Max. output at quadratic load at rated output voltage
11 kW
Max. output at linear load at rated output voltage
7.5 kW
Power consumption
293 W
Relative symmetric net frequency tolerance
10 %
Relative symmetric net voltage tolerance
10 %
Number of analogue outputs
2
Number of analogue inputs
2
Number of digital outputs
1
Number of digital inputs
8
With control element
Yes
Application in industrial area permitted
Yes
Application in domestic- and commercial area permitted
Yes
Supporting protocol for TCP/IP
Yes
Supporting protocol for PROFIBUS
Yes
Supporting protocol for CAN
Yes
Supporting protocol for INTERBUS
No
Supporting protocol for ASI
No
Supporting protocol for KNX
No
Supporting protocol for Modbus
Yes
Supporting protocol for Data-Highway
No
Supporting protocol for DeviceNet
Yes
Supporting protocol for SUCONET
No
Supporting protocol for LON
No
Supporting protocol for PROFINET IO
Yes
Supporting protocol for PROFINET CBA
No
Supporting protocol for SERCOS
No
Supporting protocol for Foundation Fieldbus
No
Supporting protocol for EtherNet/IP
Yes
Supporting protocol for AS-Interface Safety at Work
No
Supporting protocol for DeviceNet Safety
No
Supporting protocol for INTERBUS-Safety
No
Supporting protocol for PROFIsafe
No
Supporting protocol for SafetyBUS p
No
Supporting protocol for BACnet
Yes
Supporting protocol for other bus systems
Yes
Number of HW-interfaces industrial Ethernet
1
Number of interfaces PROFINET
0
Number of HW-interfaces RS-232
0
Number of HW-interfaces RS-422
0
Number of HW-interfaces RS-485
1
Number of HW-interfaces serial TTY
0
Number of HW-interfaces USB
0
Number of HW-interfaces parallel
0
Number of HW-interfaces other
1
With optical interface
No
With PC connection
Yes
Integrated breaking resistance
Yes
4-quadrant operation possible
Yes
Type of converter
U converter
Degree of protection (IP)
IP21
Degree of protection (NEMA)
1
Height
419 mm
Width
167.8 mm
Depth
244.7 mm