9701-2101-00P DG1-32012FB-C54C

General specifications
Product name
Eaton DG1 variable frequency drive
Part no.
DG1-32012FB-C54C
EAN
4015081734191
Product Length/Depth
244.7 millimetre
Product height
419 millimetre
Product width
167.8 millimetre
Product weight
10.2 kilogram
Certifications
UL508
IEC/EN61800-3
Specification for general requirements: IEC/EN 61800-2
UL File No.: E134360
C-Tick
UkrSEPRO
IEC/EN 61800-3
UL report applies to both US and Canada
Certified by UL for use in Canada
RoHS, ISO 9001
IEC/EN61800-5
UL
CE
CSA-C22.2 No. 274-13
Safety requirements: IEC/EN 61800-5
EAC
CUL
UL Category Control No.: NMMS, NMMS7
Product Tradename
DG1
Product Type
Variable frequency drive
Product Sub Type
None
Catalog Notes
The brake resistors are assigned based on the maximum rated power of the variable frequency drive. Additional brake resistors and designs (e.g. different duty cycles) are available upon request.
Features & Functions
Features
Tool-less swapping of fan
Temperature-controlled fan
Parameterization: Fieldbus
Parameterization: Keypad
Parameterization: Power Xpert inControl
Functions
4-quadrant operation possible
General information
Air volume capacity
94 m³/h
Cable length
C2 ≤ 10 m, Radio interference level, maximum motor cable length
C3 ≤ 50 m, Radio interference level, maximum motor cable length
150 m, screened, maximum permissible, Motor feeder
Degree of protection
IP54
NEMA 12
Electromagnetic compatibility
1st and 2nd environments (according to EN 61800-3)
Environmental class
3C2, 3S2 (Air quality)
Fitted with:
Brake chopper
Multi-line graphic display
Breaking resistance
Additional PCB protection
DC link choke
Internal DC link
PC connection
Radio interference suppression filter
Control unit
IGBT inverter
Frame size
FS2
Mounting position
Vertical
Number of slots
2 (expansion)
Overvoltage category
III
Pollution degree
2
Product Category
Variable frequency drives
Protection
Finger and back-of-hand proof, Protection against direct contact (BGV A3, VBG4)
Radio interference class
C1: with external filter, for conducted emissions only
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
Optional external radio interference suppression filter for longer motor cable lengths and for use in different EMC environments
Safety function/level
STO (Safe Torque Off, SIL1, PLc Cat 1)
Shock resistance
Mechanical, According to EN 61800-5-1, IEC/EN 60068-2-27
Storage and transportation: maximum 15 g, 11 ms (inside the packaging)
UPS drop test (for weights inside the UPS frame)
Suitable for
Branch circuits, (UL/CSA)
Vibration
Resistance: 5 - 150 Hz, According to EN 61800-5-1, IEC/EN 60068-2-6
Resistance: 5 - 15.8 Hz, Amplitude 1 mm (peak)
Resistance: 15.8 – 150 Hz, 1 g, Maximum acceleration amplitude
Climatic environmental conditions
Altitude
Max. 2000 m for Corner Grounded TN Systems
Max. 3000 m
Above 1000 m with 1 % derating per 100 m
Max. 1000 m
Ambient operating temperature - min
-10 °C
Ambient operating temperature - max
50 °C
Ambient operating temperature at 150% overload - min
-30 °C
Ambient operating temperature at 150% overload - max
50 °C
Ambient storage temperature - min
-40 °C
Ambient storage temperature - max
70 °C
Climatic proofing
< 95 average relative humidity (RH), no condensation, no corrosion
Main circuit
Current limitation
0.1 - 2 x IH (CT), motor, main circuit
Efficiency
97.9 % (η)
Heat dissipation at current/speed
110 W at 50% current and 50% speed
119 W at 100% current and 0% speed
125 W at 50% current and 90% speed
154 W at 50% current and 0% speed
178 W at 100% current and 90% speed
80 W at 25% current and 0% speed
92 W at 25% current and 50% speed
95 W at 100% current and 50% speed
Input current ILN at 110% overload
16.3 A
Input current ILN at 150% overload
10.2 A
Leakage current at ground IPE - max
6 mA
Mains current distortion
33.3 %
Mains switch-on frequency
Maximum of one time every 60 seconds
Mains voltage - min
208 V
Mains voltage - max
240 V
Operating mode
Torque regulation
Sensorless vector control (SLV)
Speed control with slip compensation
U/f control
Output frequency - min
0 Hz
Output frequency - max
400 Hz
Output voltage (U2)
240 V AC, 3-phase
230 V AC, 3-phase
Overload current IL at 110% overload
19.25 A
Overload current IL at 150% overload
18.75 A
Rated conditional short-circuit current (Iq)
100 kA
Rated control supply voltage
10 V DC (Us, max. 10 mA)
Rated frequency - min
45 Hz
Rated frequency - max
66 Hz
Rated operational current (Ie) at 110% overload
17.5 A
Rated operational current (Ie) at 150% overload
12.5 A
Rated operational power at 220/230 V, 50 Hz, 1-phase
3 kW
Rated operational power at 220/230 V, 50 Hz, 3-phase, 110% overload
4 kW
Rated operational voltage
230 V AC, 3-phase
240 V AC, 3-phase
Resolution
0.01 Hz (Frequency resolution, setpoint value)
Short-circuit protection rating
20 A, UL (Class CC or J), Safety device (fuse or miniature circuit-breaker), Power Wiring
Starting current - max
200 %, IH, max. starting current (High Overload), For 2 seconds every 20 seconds, Power section
Supply frequency
50/60 Hz
Switching frequency
4 kHz, 1 - 12 kHz adjustable, fPWM, Power section, Main circuit
System configuration type
TN-S, TN-C, TN-C-S, TT, IT
Voltage rating - max
240 V AC
Motor rating
Assigned motor current IM at 220 - 240 V, 60 Hz, 150% overload
9.6 A
Assigned motor current IM at 230 V, 50 Hz, 110% overload
14.8 A
Assigned motor current IM at 230 V, 50 Hz, 150% overload
11.5 A
Assigned motor current IM at 230 V, 60 Hz, 110% overload
15.2 A
Assigned motor power at 230/240 V, 60 Hz, 1-phase
3 HP
Assigned motor power at 230/240 V, 60 Hz, 3-phase, 110 % overload
5 HP
Apparent power
Apparent power at 230 V
7 kV·A
Apparent power at 240 V
7.3 kV·A
Braking function
Braking resistance
20 O
Braking torque
Adjustable to 150 % (I/Ie), DC - Main circuit
Max. 30 % MN, Standard - Main circuit
Adjustable to 150 %, DC - Main circuit
Max. 100 % of rated operational current Ie with external braking resistor - Main circuit
Switch-on threshold for the braking transistor
425 V DC
Control circuit
Number of inputs (analog)
2
Number of inputs (digital)
8
Number of outputs (analog)
2
Number of outputs (digital)
1
Number of relay outputs
3 (parameterizable, 2 changeover contacts and 1 N/O, 6 A (240 V AC) / 6 A (24 V DC))
Rated control voltage (Uc)
24 V DC (external, max. 250 mA options incl.)
Communication
Communication interface
BACnet MS/TP, built in
Modbus RTU, built in
Ethernet IP, built in
DeviceNet, optional
PROFIBUS, optional
SmartWire-DT, optional
Modbus TCP, built in
CANopen®, optional
Connection to SmartWire-DT
In conjunction with DXG-NET-SWD SmartWire DT module
Yes
Protocol
TCP/IP
CAN
MODBUS
DeviceNet
PROFINET IO
Other bus systems
PROFIBUS
BACnet
EtherNet/IP
Design verification
Equipment heat dissipation, current-dependent Pvid
163 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
12.5 A
Static heat dissipation, non-current-dependent Pvs
18.97 W
Heat dissipation details
Operation (with 150 % overload), allow for derating
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 9.0

Low-voltage industrial components (EG000017) / Frequency converter =< 1 kV (EC001857)
Electric engineering, automation, process control engineering / Electrical drive / Static frequency converter / Static frequency / Servo converter = < 1 kV (ecl@ss13-27-02-31-01 [AKE177019])
Mains voltage
208 - 240 V
Mains frequency
50/60 Hz
Number of phases input
3
Number of phases output
3
Max. output frequency
400 Hz
Max. output voltage
240 V
Nominal output current I2N
12.5 A
Max. output at quadratic load at rated output voltage
3.7 kW
Max. output at linear load at rated output voltage
3 kW
Power consumption
163 W
Relative symmetric net frequency tolerance
10 %
Relative symmetric net voltage tolerance
10 %
Number of analogue outputs
2
Number of analogue inputs
2
Number of digital outputs
1
Number of digital inputs
8
With control element
Yes
Application in industrial area permitted
Yes
Application in domestic- and commercial area permitted
Yes
Supporting protocol for TCP/IP
Yes
Supporting protocol for PROFIBUS
Yes
Supporting protocol for CAN
Yes
Supporting protocol for INTERBUS
No
Supporting protocol for ASI
No
Supporting protocol for KNX
No
Supporting protocol for Modbus
Yes
Supporting protocol for Data-Highway
No
Supporting protocol for DeviceNet
Yes
Supporting protocol for SUCONET
No
Supporting protocol for LON
No
Supporting protocol for PROFINET IO
Yes
Supporting protocol for PROFINET CBA
No
Supporting protocol for SERCOS
No
Supporting protocol for Foundation Fieldbus
No
Supporting protocol for EtherNet/IP
Yes
Supporting protocol for AS-Interface Safety at Work
No
Supporting protocol for DeviceNet Safety
No
Supporting protocol for INTERBUS-Safety
No
Supporting protocol for PROFIsafe
No
Supporting protocol for SafetyBUS p
No
Supporting protocol for BACnet
Yes
Supporting protocol for other bus systems
Yes
Number of HW-interfaces industrial Ethernet
1
Number of interfaces PROFINET
0
Number of HW-interfaces RS-232
0
Number of HW-interfaces RS-422
0
Number of HW-interfaces RS-485
1
Number of HW-interfaces serial TTY
0
Number of HW-interfaces USB
0
Number of HW-interfaces parallel
0
Number of HW-interfaces other
1
With optical interface
No
With PC connection
Yes
Integrated breaking resistance
Yes
4-quadrant operation possible
Yes
Type of converter
U converter
Degree of protection (IP)
IP54
Degree of protection (NEMA)
12
Height
419 mm
Width
167.8 mm
Depth
244.7 mm