6093243 DMV-2500/3N/M6/2HI11/K6-PG

General specifications
Product name
Eaton DMV Switch-disconnector
Part no.
DMV-2500/3N/M6/2HI11/K6-PG
EAN
8711426640832
Product Length/Depth
630 millimetre
Product height
300 millimetre
Product width
380 millimetre
Product weight
39 kilogram
Certifications
RoHS
IEC/EN 60947
VDE 0660
IEC/EN 60204
EAC
IEC/EN 60947-3
KEMA
CE
Lloyds
Product Tradename
DMV
Product Type
Switch-disconnector
Product Sub Type
None
Catalog Notes
Rated Short-time Withstand Current (Icw) for a time of 1 second
visible contacts
Features & Functions
Features
Version as main switch
Fitted with:
Gray rotary handle and drive shaft
Functions
Interlockable
Number of poles
Three-pole + N
General information
Accessories
Connection materials included with supplied equipment.
Actuator color
Gray
Actuator type
Long turning handle
Degree of protection
NEMA Other
Degree of protection (front side)
IP20
Lifespan, mechanical
5,000 Operations
Mounting method
Surface mounting
Mounting position
As required
Overvoltage category
III
Pollution degree
3
Product Category
Main switch
Switch-disconnector
Rated impulse withstand voltage (Uimp)
12000 V
Safety parameter (EN ISO 13849-1)
B10d values as per EN ISO 13849-1, table C.1
Suitable for
Ground mounting
Intermediate mounting
Climatic environmental conditions
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
55 °C
Ambient storage temperature - min
-30 °C
Ambient storage temperature - max
80 °C
Terminal capacities
Terminal capacity
3000 mm², Flat conductor connection with busbars
Screw size
M12 x 50 (2 x), Terminal screw
Tightening torque
40 Nm, Screw terminals
Electrical rating
Rated breaking capacity at 400/415 V (cos phi to IEC 60947-3)
10000 A
Rated breaking capacity at 500 V (cos phi to IEC 60947-3)
7272 A
Rated breaking capacity at 660/690 V (cos phi to IEC 60947-3)
5040 A
Rated insulation voltage (Ui)
1000 V
Rated operational current (Ie) at AC-21, 400 V, 415 V
2500 A
Rated operational current (Ie) at AC-21, 500 V
2500 A
Rated operational current (Ie) at AC-21, 690 V
2500 A
Rated operational power at AC-23A, 400 V, 50 Hz
1400 kW
Rated operational power at AC-3, 380/400 V, 50 Hz
0 kW
Rated operational voltage (Ue) at AC - max
690 V
Rated uninterrupted current (Iu)
2500 A
Uninterrupted current
Rated uninterrupted current Iu is specified for max. cross-section.
Short-circuit rating
Rated conditional short-circuit current (Iq)
0 kA
Rated short-time withstand current (Icw)
65 kA
65 kA, Contacts, 1 second
Contacts
Number of auxiliary contacts (change-over contacts)
0
Number of auxiliary contacts (normally closed contacts)
1
Number of auxiliary contacts (normally open contacts)
1
Design verification
Equipment heat dissipation, current-dependent Pvid
68.5 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
68.5 W
Rated operational current for specified heat dissipation (In)
2500 A
Static heat dissipation, non-current-dependent Pvs
0 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 9.0

Low-voltage industrial components (EG000017) / Switch disconnector (low voltage) (EC000216)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Off-load switch, circuit breaker, control switch / Switch disconnector (ecl@ss13-27-37-14-03 [AKF060018])
Version as main switch
Yes
Version as maintenance-/service switch
No
Version as safety switch
No
Version as emergency stop installation
No
Version as reversing switch
No
Number of switches
3
Max. rated operation voltage Ue AC
690 V
Rated operating voltage
690 - 690 V
Rated permanent current Iu
2500 A
Rated permanent current at AC-23, 400 V
250 A
Rated permanent current at AC-21, 400 V
2500 A
Rated operation power at AC-3, 400 V
0 kW
Rated short-time withstand current lcw
65 kA
Rated operation power at AC-23, 400 V
1400 kW
Switching power at 400 V
0 kW
Conditioned rated short-circuit current Iq
0 kA
Number of poles
4
Number of auxiliary contacts as normally closed contact
1
Number of auxiliary contacts as normally open contact
1
Number of auxiliary contacts as change-over contact
0
Motor drive optional
No
Motor drive integrated
No
Voltage release optional
No
Device construction
Built-in device fixed built-in technique
Suitable for floor mounting
Yes
Suitable for front mounting 4-hole
No
Suitable for front mounting centre
No
Suitable for distribution board installation
No
Suitable for intermediate mounting
Yes
Colour control element
Grey
Type of control element
Long turning handle
Interlockable
Yes
Type of electrical connection of main circuit
Screw connection
With pre-assembled cabling
No
Degree of protection (IP), front side
IP20
Degree of protection (NEMA)
Other
Width
380 mm
Height
300 mm
Depth
630 mm
Width in number of modular spacings