Delivery program

Rated fault currents [ I Δn ]
0.3 A
Description
Pulse-current sensitive
Integrated auxiliary contact (1 C/O)
Ring-type transformer must also be ordered
not UL/CSA approved
Rated control voltage [Us ]
230 V AC 50/60Hz V

Technical data

Electrical
Standards
IEC/EN 60947-2, IEC 755, IEC 1008, IEC 1009
Sensitivity
Pulse current sensitive, type A
Rated control voltage [Us]
230 ±20 % (50/60 Hz) V AC
Motor rating [Pe]
3 W
Rated fault currents [ I Δn ]
0.3 A
Delay time [tv]
0.02 (non-delayed) s
Relay contacts
1 integrated changeover contact
Rated voltage of the relay contact
250/100 V AC/DC
Rated current of the relay contact
6 A
Mechanical
Standard front dimension
45 mm
Enclosure height
85 mm
Device width
45 mm
Mounting
Snap fixing, top-hat rail DIN 46277, IEC/EN 60715
Terminals top and bottom
Box terminals
Terminal protection
Finger/back-of-hand proof to BGV A2, VDE 106 part 100
Terminal capacities
2 x 0.75 - 2.5 solid, 2 x 0.75 - 1.5 flexible/with ferrules mm2
Ambient temperature
Operation
-10 - +50 °C

Design verification as per IEC/EN 61439

Technical data for design verification
Operating ambient temperature min.
-10 °C
Operating ambient temperature max.
+50 °C
IEC/EN 61439 design verification
10.2 Strength of materials and parts10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9 Insulation properties10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9 Insulation properties10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9 Insulation properties10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 7.0

Low-voltage industrial components (EG000017) / Residual current release for power circuit breaker (EC001021)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Circuit breaker (LV < 1 kV) / Fault current switch for circuit breakers (ecl@ss10.0.1-27-37-04-11 [AKF009013])
Rated control supply voltage Us at AC 50HZ
184 - 276 V
Rated control supply voltage Us at AC 60HZ
184 - 276 V
Rated control supply voltage Us at DC
0 - 0 V
Rated fault current
0.3 - 0.3 A
Max. power on-delay time
20 ms
Delay adjustable
No
Max. rated operation voltage Ue
276 V

Dimensions

123X563