Delivery program

2300DRW-12
Product range
Accessories
Accessories
Base
Function
For separate mounting
For use with
ZB32
Notes

Can be snap fitted on a top-hat rail to IEC/EN 60715 or can be screw fitted.

For ZB32-38 use additional contactor BK25/3-PKZ0.

Technical data

Main conducting paths
Rated impulse withstand voltage [Uimp]
6000 V AC
Overvoltage category/pollution degree
III/3
Rated insulation voltage [Ui ]
690 V
Rated operational voltage [Ue]
690 V AC
Safe isolation to EN 61140Between main circuits
440 V AC
Terminal capacitiesSolid
1 x (1 - 16)
2 x (1 - 16) mm2
Terminal capacitiesFlexible with ferrule
1 x (1 - 4)
2 x (1 - 4) mm2
Terminal capacitiesSolid or stranded
18 - 8 AWG
Terminal screw
M4
Tightening torque for terminal screw
1.8 Nm
Stripping length
10 mm
ToolsPozidriv screwdriver
2 Size
ToolsStandard screwdriver
1 x 6 mm

Design verification as per IEC/EN 61439

Technical data for design verification
Rated operational current for specified heat dissipation [In]
38 A
Heat dissipation per pole, current-dependent [Pvid]
0.1 W
Equipment heat dissipation, current-dependent [Pvid]
0.3 W
Static heat dissipation, non-current-dependent [Pvs]
0 W
Heat dissipation capacity [Pdiss]
0 W
Operating ambient temperature min.
-25 °C
Operating ambient temperature max.
+55 °C
IEC/EN 61439 design verification
10.2 Strength of materials and parts10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9 Insulation properties10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9 Insulation properties10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9 Insulation properties10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 7.0

Low-voltage industrial components (EG000017) / Accessories for overload protection device (EC002027)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Overload protection device / Overload protection device (accessories) (ecl@ss10.0.1-27-37-15-92 [ACO017011])
Type of accessory
Base

Approvals

Product Standards
UL 508; CSA-C22.2 No. 14; IEC/EN 60947-4-1; CE marking
UL File No.
E29184
UL Category Control No.
NKCR
CSA File No.
12528
CSA Class No.
3211-03
North America Certification
UL listed, CSA certified
Specially designed for North America
No
Max. Voltage Rating
600 V AC
Degree of Protection
IEC: IP20, UL/CSA Type: -

Dimensions

230X023
① OFF
② Reset/ON
2310DIM-8