274143 NZM4-XAHIV-230AC-MNS

General specifications
Product name
Eaton Moeller series NZM release
Part no.
NZM4-XAHIV-230AC-MNS
EAN
4015082741433
Product Length/Depth
107 millimetre
Product height
51 millimetre
Product width
64 millimetre
Product weight
0.218 kilogram
Compliances
IEC
RoHS conform
Product Tradename
NZM
Product Type
Accessories
Product Sub Type
Release
Delivery program
Type
Accessory
Shunt release
Special features
Shunt release for mesh network circuit-breakers in conjunction with NZM-XZM capacitor unit
Only for short-time operation with a maximum on-time = 1 s
Operating range 10 - 110 % Us
not UL/CSA approved
Rated control voltage 230 V AC
Cannot be installed simultaneously with NZM...-XHIV... early-make auxiliary contact or NZM...-XU... undervoltage release.
Cannot be used in conjunction with NZM...-XR... remote operator.
Intermittent operation guaranteed by series connection of an M22-(C)K10 make contact.
Early-make time of integrated auxiliary contact upon switching on (manual operation): approx. 90 ms.
Frame
NZM4
Fitted with:
Early-make auxiliary contact
Suitable for
Off-load switch
Used with
NZM4(-4), N(S)4(-4)
Technical Data - Electrical
Voltage type
AC
Voltage rating at AC (x Us) - min
0.1
Voltage rating at AC (x Us) - max
1.1
Rated control voltage (relay contacts)
230 V AC
Rated control supply voltage
230 V AC
Rated control supply voltage (Us) at AC, 50 Hz - min
230 V
Rated control supply voltage (Us) at AC, 50 Hz - max
230 V
Rated control supply voltage (Us) at AC, 60 Hz - min
230 V
Rated control supply voltage (Us) at AC, 60 Hz - max
230 V
Rated control supply voltage (Us) at DC - min
0 V
Rated control supply voltage (Us) at DC - max
0 V
Current consumption - max
0.5 A
Frequency rating
50 Hz / 60 Hz (shunt release)
Reaction time
20 ms
Time on duty - max
1000 ms
Minimum command time - min
10 ms
Minimum command time - max
15 ms
Electric connection type
Screw connection
Technical Data - Mechanical
Number of contacts (change-over contacts)
0
Number of contacts (normally closed contacts)
0
Number of contacts (normally open contacts)
1
Special features
Shunt release for mesh network circuit-breakers in conjunction with NZM-XZM capacitor unit
Only for short-time operation with a maximum on-time = 1 s
Operating range 10 - 110 % Us
not UL/CSA approved
Rated control voltage 230 V AC
Cannot be installed simultaneously with NZM...-XHIV... early-make auxiliary contact or NZM...-XU... undervoltage release.
Cannot be used in conjunction with NZM...-XR... remote operator.
Intermittent operation guaranteed by series connection of an M22-(C)K10 make contact.
Early-make time of integrated auxiliary contact upon switching on (manual operation): approx. 90 ms.
Technical Data - Mechanical - Terminals
Terminal capacity (solid/flexible conductor)
18 - 14 AWG (2x) for undervoltage releases, off-delayed
0.75 mm² - 2.5 mm² (1x) at shunt release with ferrule
18 - 14 AWG (1x) at shunt release
18 - 14 AWG (2x) at shunt release
18 - 14 AWG (1x) for undervoltage releases, off-delayed
0.75 mm² - 2.5 mm² (1x) for undervoltage releases, off-delayed with ferrule
0.75 mm² - 2.5 mm² (2x) at shunt release with ferrule
0.75 mm² - 2.5 mm² (2x) for undervoltage releases, off-delayed with ferrule
Design verification as per IEC/EN 61439
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 9.0

Low-voltage industrial components (EG000017) / Shunt release (for power circuit breaker) (EC001023)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Circuit breaker (LV < 1 kV) / Full load current trip (ecl@ss13-27-37-04-18 [AKF016018])
Rated control supply voltage AC 50 Hz
230 - 230 V
Rated control supply voltage AC 60 Hz
230 - 230 V
Rated control supply voltage DC
0 - 0 V
Voltage type for actuating
AC
Initial value of the undelayed short-circuit release - setting range
0 A
End value adjustment range undelayed short-circuit release
0 A
Power consumption
W
Type of electric connection
Screw connection
Number of contacts as normally open contact
1
Number of contacts as normally closed contact
0
Number of contacts as change-over contact
0
Suitable for power circuit breaker
No
Suitable for off-load switch
Yes
Suitable for motor safety switch
No
Suitable for overload relay
No