General specifications
Product name
Eaton Moeller series NZM auxiliary contact
Part no.
NZM4-XHIV
EAN
4015082661724
Product Length/Depth
107 millimetre
Product height
51 millimetre
Product width
64 millimetre
Product weight
0.129 kilogram
Compliances
RoHS conform
Certifications
CSA (Class No. 1437-01)
CSA (File No. 22086)
CSA certified
UL (Category Control Number DIHS)
CSA-C22.2 No. 5-09
UL489
IEC60947
UL listed
UL (File No. E140305)
CE marking
Product Tradename
NZM
Product Type
Accessories
Product Sub Type
Auxiliary contact
Delivery program
Special features
C300/R300 (auxiliary contacts, UL/CSA, pilot duty)
Used with
FAZ-B6 (max. miniature circuit breaker)
Technical Data - Electrical
Voltage rating at DC
220 V DC
Voltage rating at AC
500 V AC
Rated operational current
2.5 A at 240 V AC (UL/CSA)
1 A at 250 V DC (UL/CSA)
Rated operational current (Ie) at AC-15, 220 V, 230 V, 240 V
4 A
Conventional thermal current Ith of auxiliary contacts
4 A
Fuse short-circuit protection - max
10 A gG/gL
Technical Data - Mechanical
Mounting Method
Other
Number of contacts (change-over contacts)
0
Number of contacts (normally closed contacts)
0
Number of contacts (normally open contacts)
2
Connection type
Screw
Lamp holder
None
Special features
C300/R300 (auxiliary contacts, UL/CSA, pilot duty)
Technical Data - Mechanical - Terminals
Terminal capacity (solid/flexible conductor)
0.75 mm² - 2.5 mm² (2x) at auxiliary contacts with ferrule
0.75 mm² - 2.5 mm² (1x) at auxiliary contacts with ferrule
18 - 14 AWG (1x) at auxiliary contacts
18 - 14 AWG (2x) at auxiliary contacts
Design verification as per IEC/EN 61439
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Additional information
Model
Integrable

Technical data ETIM 8.0

Low-voltage industrial components (EG000017) / Auxiliary contact block (EC000041)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Component for low-voltage switching technology / Auxiliary switch block (ecl@ss10.0.1-27-37-13-02 [AKN342013])
Number of contacts as change-over contact
0
Number of contacts as normally open contact
2
Number of contacts as normally closed contact
0
Number of fault-signal switches
Rated operation current Ie at AC-15, 230 V
4 A
Type of electric connection
Screw connection
Model
Integrable
Mounting method
Other
Lamp holder
None