260178 NZM1-XTVDVR
Door coupling rotary handle, red-yellow for emergency switching off, size 1
EL-Nummer (Norway)
4358729
Optional accessories for circuit-breaker series NZM offers a comprehensive portfolio of application possibilities for worldwide use. Modular functional groups make mounting flexible and simple. Note: Complete including rotary drive and coupling parts. External warning plate/marking plate can be clipped on. Red/yellow for EMERGENCY SHUTDOWN. Lockable on the handle on the switch using up to 3 padlocks. Lockable in 0 position on handle, lockable on the 0 position on the switch using up to 3 padlocks. With door interlock. Can be used for: NZM1(-4), PN1(-4), N(N/O)1(-4)
Delivery program
Product range
Accessories
Accessories
Door coupling rotary handle
Standard/Approval
UL/CSA, IEC
Construction size
NZM1
Description
Door coupling rotary handle for operating the switch through a closed control panel door
Function
Red-yellow for emergency switching off
Protection class
IP66
UL/CSA Type 4X, Type 12
UL/CSA Type 4X, Type 12
Locking facility
lockable on the handle on the switch using up to 3 padlocks
With door interlock
With door interlock
Door interlock
Not defeated in the locked OFF position.
Can be modified in the unlocked ON position
Can be modified such that it can be defeated from the outside using a screwdriver
Door can be opened in OFF
Can be modified in the unlocked ON position
Can be modified such that it can be defeated from the outside using a screwdriver
Door can be opened in OFF
Project planning information
External warning plate/designation label can be clipped on.
Complete including rotary drive and coupling parts
Extension shaft additionally required.
Complete including rotary drive and coupling parts
Extension shaft additionally required.
For use with
NZM1(-4), PN1(-4), N(S)1(-4)
lockable
double
Notes
Circuit‐breaker can also be installed in a lying position 90 ° left/right, with the handle still in the same position.
Design verification as per IEC/EN 61439
IEC/EN 61439 design verification
10.2 Strength of materials and parts10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9 Insulation properties10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9 Insulation properties10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9 Insulation properties10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Technical data ETIM 8.0
Low-voltage industrial components (EG000017) / Handle for power circuit breaker (EC000229)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Circuit breaker (LV < 1 kV) / Handle for switch devices (ecl@ss10.0.1-27-37-04-14 [AKF012014])
With restart blockage
No
With key lock
No
Padlock locking
Yes
Colour
Red
Suitable for emergency stop
Yes
With extension shaft
No
Suitable for power circuit breaker
Yes
Suitable for switch disconnector
Yes
Degree of protection (NEMA)
4X, 12
-