To be discontinued 257907 XIOC-2CNT-100KHZ

General specifications
Product name
Eaton XIOC Counter module
Part no.
XIOC-2CNT-100KHZ
EAN
4015082579074
Product Length/Depth
100 millimetre
Product height
95 millimetre
Product width
30 millimetre
Product weight
0.155 kilogram
Certifications
UL508
CSA-C22.2 No. 142-M
CE
EN 50178
UL
UL Category Control No.: NRAQ
CSA Class No.: 2252-01
UL File No.: E135462
CSA-C22.2 No. 0-M
IEC/EN 61131-2
CSA File No.: 012528
CSA
Product Tradename
XIOC
Product Type
Counter module
Product Sub Type
None
Catalog Notes
4 VA/W, Voltage for Off
optocoupled, 24 V DC
Features & Functions
Functions
Single-axis positioning possible
Single-axis controller possible
General information
Admissible range
20.4 – 28.8 V (11.8 – 14.4 V), Power supply
Current consumption
200 mA (Ie), internal current consumption, Inputs
200 mA, Outputs
Degree of protection
IP20
Number of channels
4, Output
Overvoltage category
II
Pollution degree
2
Protection class
1
Rated frequency
100 (25 with four-fold resolution)
Repetition rate
1 s
Residual ripple
≤ 5 %
Suitable for
Counting
Incremental data detection
Type
Counter module
Used with
XC100/200 (expandable with up to 15 XI/OC modules)
Ambient conditions, mechanical
Impact resistance
500 g/⌀ 50 mm ±25 g
Shock resistance
15 g, Mechanical, Shock duration 11 ms
Vibration resistance
10 - 57 Hz, ± 0.075 mm
57 - 150 Hz ± 1.0 mm
Climatic environmental conditions
Ambient operating temperature - min
0 °C
Ambient operating temperature - max
55 °C
Ambient storage temperature - min
-25 °C
Ambient storage temperature - max
70 °C
Electro magnetic compatibility
Emitted interference
Class A (according to DIN/EN 55011/22)
Voltage dips
10 ms
Terminal capacities
Terminals
Optionally, screw terminals or spring-loaded terminals for digital/analog modules
Electrical rating
Leakage current
0.5 A
Power loss
1.2 W
Rated control voltage (Uc)
-5 - 8 V DC
Rated operational current (Ie)
10 A
Rated operational voltage
24 (12) V DC
Supply voltage at DC - min
2 V DC
Supply voltage at DC - max
5 V DC
Communication
Connection
30-pole plug: XIOC-TERM30-CNT4, Connection of external input (max. 30 m cable length), Inputs
Of external output: 30-pole plug XIOC-TERM30-CNT4
30 pole connector required for counter module
Screened, twisted pair cable, Output termination
Screened, twisted pair cable, Inputs
Input/Output
Counter limits
0 - 4294967295 (32 bit)
Delay time
1 ms, Outputs, Delay time from 0 to 1, Debounce OFF
1 ms, Outputs, Delay time from 1 to 0, Debounce OFF
Input
2 inputs (up to 100 kHz, 24 V DC or 5 V diff)
2 Analog inputs
Input current
4 mA (high signal)
Input B1-C: max. 35 A
Input voltage
12 - 24 V DC
± 5 V DC (differential)
Load current
Max. 20 mA (Ie)
Min. 1 mA
Output
Transistor (open collector)
4 Digital Transistor Outputs
Pulse characteristics
On ≥ 4 µs (minimum pulse width)
Voltage drop (Ud)
1.5 V
Safety
Explosion safety category for dust
None
Explosion safety category for gas
None
Potential isolation
Outputs: Opto-isolated
Opto-isolated (Inputs)
Design verification
Equipment heat dissipation, current-dependent Pvid
0 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
0 A
Static heat dissipation, non-current-dependent Pvs
1.2 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Meets the product standard's requirements.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 9.0

Programmable logic controllers PLC (EG000024) / PLC function/technology module (EC001422)
Electric engineering, automation, process control engineering / Control, Process Control System (PCS) / Programmable logic control (SPS) / SPS functional/technological module (ecl@ss13-27-24-22-05 [AKE528019])
Number of functions
2
Redundancy
No
Suitable for counting
Yes
Suitable for weighing
No
Suitable for temperature control
No
Suitable for welding control
No
Suitable for pressure control
No
Suitable for NC
No
Suitable for electronic positioning
No
Suitable for CNC
No
Suitable for SSI
No
Suitable for incremental data detection
Yes
Suitable for detection absolute value
No
Suitable for flux controller
No
Suitable for flux measurement
No
Suitable for path controller
No
Suitable for cam controller
No
Suitable for flying saw
No
Suitable for multi-axis control
No
Suitable for single-axis controller
Yes
Suitable for multi-axis positioning
No
Suitable for single-axis positioning
Yes
Suitable for safety functions
No
SIL according to IEC 61508
None
Performance level according to EN ISO 13849-1
None
Appendant operation agent (Ex ia)
No
Appendant operation agent (Ex ib)
No
Explosion safety category for gas
None
Explosion safety category for dust
None
Width
30 mm
Height
95 mm
Depth
100 mm