248398 Z-MS-10/2
Motor-Protective Circuit-Breakers, 6,3-10A, 2p
Alternate Catalog No.
Z-MS-10/2
Motor-protective circuit-breaker with thermal overload release and magnetic short-circuit release, for switching and protecting three-phase motors with outputs of up to 15 kW (380/400 V) or other loads with currents of up to 40 A, can also be used as a main switch, isolating characteristics to IEC/EN 60947, contact position display red/green
Design verification as per IEC/EN 61439
Rated operational current for specified heat dissipation [In]
10 A
Heat dissipation per pole, current-dependent [Pvid]
2.35 W
Equipment heat dissipation, current-dependent [Pvid]
4.7 W
Operating ambient temperature min.
-5 °C
Operating ambient temperature max.
+50 °C
Technical data ETIM 7.0
Low-voltage industrial components (EG000017) / Motor protection circuit-breaker (EC000074)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Circuit breaker (LV < 1 kV) / Motor protection circuit-breaker (ecl@ss10.0.1-27-37-04-01 [AGZ529016])
Overload release current setting
6.3 - 10 A
Adjustment range undelayed short-circuit release
78 - 105 A
With thermal protection
Yes
Phase failure sensitive
No
Switch off technique
Magnetic
Rated operating voltage
400 - 400 V
Rated permanent current Iu
10 A
Rated operation power at AC-3, 230 V
0 kW
Rated operation power at AC-3, 400 V
4 kW
Type of electrical connection of main circuit
Screw connection
Type of control element
Rocker lever
Device construction
Complete device in housing
With integrated auxiliary switch
No
With integrated under voltage release
No
Number of poles
2
Rated short-circuit breaking capacity lcu at 400 V, AC
10 kA
Degree of protection (IP)
IP20
Height
75 mm
Width
36 mm
Depth
80 mm
-
Eaton EMEA Download-Center - download data for this item
-
Eaton EMEA Download-Center