Delivery program

Suitable for fuses, utilisation class gG (gL), aM
Current coding through fuse set
sealable
Infeed possible from both sides
Standard, empty
Rated operational voltage
230 V AC
400 V AC
Number of poles
3 pole
Rated operational current [Ie]
63 A
Fuse cartridge
D02, D01 Size

Technical data

Electrical
Number of poles
3P
Rated operational voltage [Ue]AC: 1P, 2P, 3P [Ue]
400 V AC
Rated operational voltage [Ue]DC: 1P, 2P
1P up to 110V / 2P up to 220V V DC
Rated operational current [Ie]
63 A
Rated uninterrupted current [Iu]
63 A
Rated short-circuit making capacity [Icm]
50 kAeff
Switching category
AC 22 B, DC 21 B
Overvoltage category
IV
Rated impulse withstand voltage [Uimp]
6 kV
Current heat loss per contact at Ie
0.5 W
Power lossHeat dissipation per contact with fuse link at Ie
7.5 W
Relay section electrical
Overvoltage category/pollution degree
III/3
Mechanical
Standard front dimension
45 mm
Enclosure height
86 mm
Mounting width
27/per pole (1.5 SU) mm
Weight
1P 113
1P+N 225
2P 224
3P 450
3P+N 472 g
Mounting
Quick attachment for top-hat rail IEC/EN 60715
Degree of protectionIntegrated
IP20
Terminals
Lift terminals
Terminal capacitiesSolid
1.5 - 35 mm2
Temperature range
-25 … +60 °C
Flammability classification according to UL94
V0, glow-wire test 960°C
Terminal screw tightening torque
max. 4.5 Nm
Overvoltage category/pollution degree
III/3
Track resistance
CTI 600
Relay section mechanical
Terminals
Lift terminals

Design verification as per IEC/EN 61439

Rated operational current for specified heat dissipation [In]
63 A
Heat dissipation per pole, current-dependent [Pvid]
0 W
Equipment heat dissipation, current-dependent [Pvid]
1.5 W
Static heat dissipation, non-current-dependent [Pvs]
0 W
Heat dissipation capacity [Pdiss]
0 W
Operating ambient temperature min.
-25 °C
Operating ambient temperature max.
+55 °C
0

Technical data ETIM 8.0

Circuit breakers and fuses (EG000020) / D0-system switch disconnector (EC000277)
Electric engineering, automation, process control engineering / Electrical installation, device / Safety fuse systems / Neozed switch disconnector (ecl@ss10.0.1-27-14-21-10 [AKE282013])
Number of poles
3
Construction size
D02
Rated voltage
400 V
Rated current
63 A

Dimensions

1220DIM-15