General specifications
Product name
Eaton Moeller® series M22 Housing
Part no.
M22-I3-M2
EAN
4015082165338
Product Length/Depth
80 millimetre
Product height
70 millimetre
Product width
153 millimetre
Product weight
0.317 kilogram
Compliances
Contact Manufacturer
Certifications
UL 508
IEC/EN 60947-5
VDE 0660
UL File No.: E29184
CE
CSA File No.: 012528
CSA-C22.2 No. 14-05
CSA Class No.: 3211-03
UL
IEC/EN 60947
CSA
CSA-C22.2 No. 94-91
UL Category Control No.: NKCR
Product Tradename
M22
Product Type
Housing
Product Sub Type
None
Catalog Notes
85 - 264 V AC
Contacts with safety function, by positive opening to IEC/EN 60947-5-1
LED element
Features & Functions
Bezel color
Titanium
Color
Light gray
Design
Enclosure
Enclosure color
Gray
Enclosure material
Plastic
Inscription
Inscribed
Knockouts
2 x M20 (cable entry knockouts at the base)
2 x M25/20 (cable entry knockouts at the side)
Light color
White
Number of locations
2
RAL-number
7035
General information
Degree of protection
IP67/IP69K
NEMA 4X, 13
Lifespan
5,000,000 mechanical Operations
Operating frequency
3600 Operations/h
Product category
RMQ-Titan
Size
Front dimensions: 153 x 80 mm
Type
Indicator lights
Pushbutton actuator
Ambient conditions, mechanical
Mounting position
As required
Shock resistance
Mechanical, According to IEC/EN 60068-2-27
30 g, Mechanical, According to IEC/EN 60068-2-27, Sinusoidal shock 11 ms
Climatic environmental conditions
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
70 °C
Climatic proofing
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Electrical rating
Rated control supply voltage (Us) at AC, 50 Hz - min
85 V
Rated control supply voltage (Us) at AC, 50 Hz - max
264 V
Rated control supply voltage (Us) at AC, 60 Hz - min
85 V
Rated control supply voltage (Us) at AC, 60 Hz - max
264 V
Rated control supply voltage (Us) at DC - min
0 V
Rated control supply voltage (Us) at DC - max
0 V
Short-circuit rating
Rated conditional short-circuit current (Iq)
1 kA
Communication
Connection to SmartWire-DT
No
Connection type
Screw connection
Actuator
Actuating force
5 N
Actuator color
Red/white/green
Actuator function
Momentary
Actuator travel and actuation force (DIN EN 60947-5-1)
4.8 mm
Knob travel
5.7 mm
Contacts
Force for positive opening - min
15 N
Number of contacts (change-over contacts)
0
Number of contacts (normally closed contacts)
2
Number of contacts (normally open contacts)
2
Design verification
Equipment heat dissipation, current-dependent Pvid
0 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0.11 W
Rated operational current for specified heat dissipation (In)
6 A
Static heat dissipation, non-current-dependent Pvs
1 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Please enquire
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 9.0

Low-voltage industrial components (EG000017) / Control circuit devices combination in enclosure (EC000225)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Command and alarm device / Command and alarm device combination in housing (ecl@ss13-27-37-12-16 [AKF034019])
Number of command positions
3
Number of push buttons
2
Number of indicator lights
1
Number of key switches
0
Number of selector switches
0
Number of mushroom-shaped push-buttons
0
Suitable for emergency stop
No
Rated control supply voltage AC 50 Hz
85 - 264 V
Rated control supply voltage AC 60 Hz
85 - 264 V
Rated control supply voltage DC
0 - 0 V
Power consumption
W
Colour housing cover
Grey
Housing colour
Grey
Housing material
Plastic
Number of contacts as normally open contact
2
Number of contacts as normally closed contact
2
Number of contacts as change-over contact
0
Degree of protection (IP)
IP67/IP69K
Degree of protection (NEMA)
4X, 13