Delivery program

Basic function accessories
Contact elements
Connection technique
Screw terminals
Fixing
Base fixing
Degree of Protection
IP20
Connection to SmartWire-DT
no
Approval
000Z425
Contacts
N/O = Normally open
1 N/O
Contact sequence
116S040
Contact travel diagram, stroke in connection with front element
Contact diagram
116U021
Configuration
116Q009
Connection type
Single contact
Connection technique
Screw terminals
Notes

Up to 3 off per enclosure base

Technical data

General
Standards
IEC 60947-5-1
Lifespan, mechanical [Operations]
> 5 x 106
Operating frequency [Operations/h]
≦ 3600
Actuating force
≦ 5 n
Operating torque (screw terminals)
≦ 0.8 Nm
Degree of Protection
IP20
Climatic proofing
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperatureOpen
-25 - +70 °C
Mechanical shock resistance to IEC 60068-2-27 Shock duration 11 ms, half-sinusoidal
> 30 g
Terminal capacitiesSolid
0.75 - 2.5 mm2
Terminal capacitiesStranded
0.5 - 2.5 mm2
Terminal capacitiesFlexible with ferrule
0.5 - 1.5 mm2
Contacts
Rated impulse withstand voltage [Uimp]
6000 V AC
Rated insulation voltage [Ui ]
500 V
Overvoltage category/pollution degree
III/3
Control circuit reliabilityat 24 V DC/5 mA [HF ]
< 10-7 (i.e. 1 failure to 107 operations) Fault probability
Control circuit reliabilityat 5 V DC/1 mA [HF ]
< 5 x 10-6 (i.e. 1 failure in 5 x 106 operations) Fault probability
Max. short-circuit protective deviceFuseless
PKZM0-10/FAZ-B6/1 Type
Max. short-circuit protective deviceFuse [gG/gL]
10 A
Switching capacity
Rated operational current [Ie ]AC-15115 V [Ie ]
6 A
Rated operational current [Ie ]AC-15220 V 230 V 240 V [Ie]
6 A
Rated operational current [Ie ]AC-15380 V 400 V 415 V [Ie]
4 A
Rated operational current [Ie ]AC-15500 V [Ie]
2 A
Rated operational current [Ie ]DC-13 24 V [Ie ]
3 A
Rated operational current [Ie ]DC-13 42 V [Ie ]
1.7 A
Rated operational current [Ie ]DC-13 60 V [Ie ]
1.2 A
Rated operational current [Ie ]DC-13 110 V [Ie ]
0.6 A
Rated operational current [Ie ]DC-13 220 V [Ie ]
0.3 A
Lifespan, electricalAC-15230 V/0.5 A [Operations]
1.6 x 106
Lifespan, electricalAC-15230 V/1.0 A [Operations]
1 x 106
Lifespan, electricalAC-15230 V/3.0 A [Operations]
0.7 x 106
Lifespan, electricalDV-1312 V/2.8 A [Operations]
1.2 x 106

Design verification as per IEC/EN 61439

Technical data for design verification
Rated operational current for specified heat dissipation [In]
6 A
Heat dissipation per pole, current-dependent [Pvid]
0.11 W
Equipment heat dissipation, current-dependent [Pvid]
0 W
Static heat dissipation, non-current-dependent [Pvs]
0 W
Heat dissipation capacity [Pdiss]
0 W
Operating ambient temperature min.
-25 °C
Operating ambient temperature max.
+70 °C
IEC/EN 61439 design verification
10.2 Strength of materials and parts10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9 Insulation properties10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9 Insulation properties10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9 Insulation properties10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 7.0

Low-voltage industrial components (EG000017) / Auxiliary contact block (EC000041)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Component for low-voltage switching technology / Auxiliary switch block (ecl@ss10.0.1-27-37-13-02 [AKN342013])
Number of contacts as change-over contact
0
Number of contacts as normally open contact
1
Number of contacts as normally closed contact
0
Number of fault-signal switches
0
Rated operation current Ie at AC-15, 230 V
6 A
Type of electric connection
Screw connection
Model
Top mounting
Mounting method
Floor fastening
Lamp holder
None

Approvals

Product Standards
IEC/EN 60947-5; UL 508; CSA-C22.2 No. 14-05; CSA-C22.2 No. 94-91; CE marking
UL File No.
E29184
UL Category Control No.
NKCR
CSA File No.
012528
CSA Class No.
3211-03
North America Certification
UL listed, CSA certified
Degree of Protection
UL/CSA Type: -

Dimensions

116X102
Pushbutton with M22-(C)K…
Pushbutton with M22-(C) LED… + M22-XLED…