Delivery program

Product range
Control switches
Part group reference
T3
Basic function
Reversing switches
with black thumb grip and front plate
Contacts
5
Degree of Protection
IP65
Design
surface mounting
Switching angle
60 °
Switching performance
maintained
With 0 (Off) position
Design number
8401
front plate
1-0-2
Motor rating AC-23A, 50 - 60 Hz [P]
400 V [P]
15 kW
Rated uninterrupted current [Iu]
32 A
Note on rated uninterrupted current !u
Rated uninterrupted current Iu is specified for max. cross-section.
Number of contact units
3 contact unit(s)

Technical data

General
Standards
IEC/EN 60947, VDE 0660, IEC/EN 60204, CSA, UL
Switch-disconnector according to IEC/EN 60947-3
Climatic proofing
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperatureEnclosed
-25 - +40 °C
Overvoltage category/pollution degree
III/3
Rated impulse withstand voltage [Uimp]
6000 V AC
Mechanical shock resistance
12 g
Mounting position
As required
Contacts
Electrical characteristicsRated operational voltage [Ue]
690 V AC
Electrical characteristicsRated uninterrupted current [Iu]
32 A
Electrical characteristicsNote on rated uninterrupted current !u
Rated uninterrupted current Iu is specified for max. cross-section.
Load rating with intermittent operation, class 12AB 25 % DF
2 x Ie
Load rating with intermittent operation, class 12AB 40 % DF
1.6 x Ie
Load rating with intermittent operation, class 12AB 60 % DF
1.3 x Ie
Short-circuit ratingFuse
35 A gG/gL
Rated short-time withstand current (1 s current) [Icw ]
650 Arms
Note on rated short-time withstand current lcw
Current for a time of 1 second
Rated conditional short-circuit current [Iq]
1 kA
Switching capacity
cos ϕ rated making capacity as per IEC 60947-3
320 A
Rated breaking capacity cos ϕ to IEC 60947-3230 V
260 A
Rated breaking capacity cos ϕ to IEC 60947-3400/415 V
260 A
Rated breaking capacity cos ϕ to IEC 60947-3500 V
240 A
Rated breaking capacity cos ϕ to IEC 60947-3690 V
170 A
Safe isolation to EN 61140between the contacts
440 V AC
Safe isolation to EN 61140Current heat loss per contact at Ie
1.1 W
Safe isolation to EN 61140Current heat loss per auxiliary circuit at Ie (AC-15/230 V)
1.1 CO
Lifespan, mechanical [Operations]
> 0.5 x 106
Maximum operating frequency [Operations/h]
1200
AC AC-3Rating, motor load switch [P]220 V 230 V [P]
5.5 kW
AC AC-3Rating, motor load switch [P]230 V Star-delta [P]
7.5 kW
AC AC-3Rating, motor load switch [P]400 V 415 V [P]
11 kW
AC AC-3Rating, motor load switch [P]400 V Star-delta [P]
15 kW
AC AC-3Rating, motor load switch [P]500 V [P]
15 kW
AC AC-3Rating, motor load switch [P]500 V Star-delta [P]
18.5 kW
AC AC-3Rating, motor load switch [P]690 V [P]
11 kW
AC AC-3Rating, motor load switch [P]690 V Star-delta [P]
22 kW
AC AC-3Rated operational current motor load switch230 V [Ie]
23.7 A
AC AC-3Rated operational current motor load switch230 V star-delta [Ie]
32 A
AC AC-3Rated operational current motor load switch400V 415 V [Ie]
23.7 A
AC AC-3Rated operational current motor load switch400 V star-delta [Ie]
32 A
AC AC-3Rated operational current motor load switch500 V [Ie ]
23.7 A
AC AC-3Rated operational current motor load switch500 V star-delta [Ie ]
32 A
AC AC-3Rated operational current motor load switch690 V [Ie]
14.7 A
AC AC-3Rated operational current motor load switch690 V star-delta [Ie]
25.5 A
AC AC-23AMotor rating AC-23A, 50 - 60 Hz [P]230 V [P]
7.5 kW
AC AC-23AMotor rating AC-23A, 50 - 60 Hz [P]400 V 415 V [P]
15 kW
AC AC-23AMotor rating AC-23A, 50 - 60 Hz [P]500 V [P]
15 kW
AC AC-23AMotor rating AC-23A, 50 - 60 Hz [P]690 V [P]
15 kW
AC AC-23ARated operational current motor load switch230 V [Ie]
32 A
AC AC-23ARated operational current motor load switch400 V 415 V [Ie]
32 A
AC AC-23ARated operational current motor load switch500 V [Ie]
26.4 A
AC AC-23ARated operational current motor load switch690 V [Ie]
17 A
DCDC-1, Load-break switches L/R = 1 msRated operational current [Ie]
25 A
DCDC-1, Load-break switches L/R = 1 msVoltage per contact pair in series
60 V
DCDC-21A [Ie ]Rated operational current [Ie]
1 A
DCDC-21A [Ie ]Contacts
1 Quantity
DCDC-23A, motor load switch L/R = 15 ms24 VRated operational current [Ie]
25 A
DCDC-23A, motor load switch L/R = 15 ms24 VContacts
1 Quantity
DCDC-23A, motor load switch L/R = 15 ms48 VRated operational current [Ie]
25 A
DCDC-23A, motor load switch L/R = 15 ms48 VContacts
2 Quantity
DCDC-23A, motor load switch L/R = 15 ms60 VRated operational current [Ie]
25 A
DCDC-23A, motor load switch L/R = 15 ms60 VContacts
3 Quantity
DCDC-23A, motor load switch L/R = 15 ms120 VRated operational current [Ie]
12 A
DCDC-23A, motor load switch L/R = 15 ms120 VContacts
3 Quantity
DCDC-23A, motor load switch L/R = 15 ms240 VRated operational current [Ie]
5 A
DCDC-23A, motor load switch L/R = 15 ms240 VContacts
5 Quantity
DCDC-13, Control switches L/R = 50 msRated operational current [Ie]
20 A
DCDC-13, Control switches L/R = 50 msVoltage per contact pair in series
24 V
Control circuit reliability at 24 V DC, 10 mA [Fault probability]
< 10-5,< 1 failure in 100,000 switching operations HF
Terminal capacities
Solid or stranded
1 x (1 - 6)
2 x (1 - 6) mm2
Flexible with ferrules to DIN 46228
1 x (0.75 - 4)
2 x (0.75 - 4) mm2
Terminal screw
M4
Tightening torque for terminal screw
1.6 Nm
Technical safety parameters:
Notes
B10d values as per EN ISO 13849-1, table C1
Rating data for approved types
ContactsRated operational voltage [Ue]
600 V AC
ContactsRated uninterrupted current max.Main conducting pathsGeneral use
25 A
ContactsRated uninterrupted current max.Auxiliary contactsGeneral Use [IU]
10 A
ContactsRated uninterrupted current max.Auxiliary contactsPilot Duty
A 600
Switching capacityMaximum motor ratingSingle-phase120 V AC
1.5 HP
Switching capacityMaximum motor ratingSingle-phase200 V AC
3 HP
Switching capacityMaximum motor ratingSingle-phase240 V AC
3 HP
Switching capacityMaximum motor ratingThree-phase200 V AC
3 HP
Switching capacityMaximum motor ratingThree-phase240 V AC
3 HP
Switching capacityMaximum motor ratingThree-phase480 V AC
7.5 HP
Switching capacityMaximum motor ratingThree-phase600 V AC
10 HP
Short Circuit Current RatingBasic Rating
5 kA
Short Circuit Current Ratingmax. Fuse
40 A
Short Circuit Current RatingHigh fault rating
10 kA
Short Circuit Current Ratingmax. Fuse
40, Class J A
Terminal capacity Solid or flexible conductor with ferrule
14 - 10 AWG
Terminal capacity Terminal screw
M4
Terminal capacity Tightening torque
17.7 lb-in

Design verification as per IEC/EN 61439

Datos técnicos para la verificación del diseño
Intensidad asignada de empleo para disipación térmica específica [In]
32 A
Disipación térmica por polo, en función de la intensidad [Pvid]
1.1 W
Disipación térmica del equipo, en función de la intensidad [Pvid]
0 W
Disipación térmica estática, en función de la intensidad [Pvs]
0 W
Capacidad de disipación térmica [Pdiss]
0 W
Temperatura ambiente mínima de funcionamiento
-25 °C
Temperatura ambiente máxima de funcionamiento
+40 °C
Verificación de diseño IEC / EN 61439
10.2 Resistencia de materiales y piezas10.2.2 Resistencia a la corrosión
Cumple con los requisitos de la norma del producto.
10.2 Resistencia de materiales y piezas10.2.3.1 Verificación de la estabilidad térmica de los armarios
Cumple con los requisitos de la norma del producto.
10.2 Resistencia de materiales y piezas10.2.3.2 Verificación de la resistencia de los materiales aislantes en condiciones de calor normales
Cumple con los requisitos de la norma del producto.
10.2 Resistencia de materiales y piezas10.2.3.3. Verificación de la resistencia de los materiales aislantes al calor excesivo y al fuego debido a los efectos eléctricos internos
Cumple con los requisitos de la norma del producto.
10.2 Resistencia de materiales y piezas10.2.4 Resistencia a radiación ultravioleta (UV)
UV resistance only in connection with protective shield.
10.2 Resistencia de materiales y piezas10.2.5 Elevación
No se aplica, ya que todo el equipo de conmutación debe ser evaluado.
10.2 Resistencia de materiales y piezas10.2.6 Impacto mecánico
No se aplica, ya que todo el equipo de conmutación debe ser evaluado.
10.2 Resistencia de materiales y piezas10.2.7 Inscripciones
Cumple con los requisitos de la norma del producto.
10.3 Grado de protección de montajes
No se aplica, ya que todo el equipo de conmutación debe ser evaluado.
10.4 Distancias de separación y fuga
Cumple con los requisitos de la norma del producto.
10.5 Protección contra descargas eléctricas
No se aplica, ya que todo el equipo de conmutación debe ser evaluado.
10.6 Incorporación de dispositivos y componentes de conmutación
No se aplica, ya que todo el equipo de conmutación debe ser evaluado.
10.7 Conexiones y circuitos eléctricos internos
Es responsabilidad del cuadrista.
10.8 Conexiones de conductores externos
Es responsabilidad del cuadrista.
10.9 Propiedades de aislamiento10.9.2 Resistencia eléctrica de frecuencia de alimentación
Es responsabilidad del cuadrista.
10.9 Propiedades de aislamiento10.9.3 Tensión de impulso soportada
Es responsabilidad del cuadrista.
10.9 Propiedades de aislamiento10.9.4 Pruebas de armarios hechos de material aislante
Es responsabilidad del cuadrista.
10.10 Aumento de la temperatura
El cuadrista es responsable del cálculo del aumento de la temperatura. Eaton proporcionará datos de disipación de calor para los dispositivos.
10.11 Resistencia a los cortocircuitos
Es responsabilidad del cuadrista. Deben tenerse en cuenta las especificaciones de la aparamenta.
10.12 Compatibilidad electromagnética
Es responsabilidad del cuadrista. Deben tenerse en cuenta las especificaciones de la aparamenta.
10.13 Función mecánica
El dispositivo cumple los requisitos, siempre que se observe la información del folleto de instrucciones (IL).

Technical data ETIM 7.0

Conmutadores en baja tensión (EG000017) / Conmutador de carga (EC001105)
Tecnología electrónica, de automatización y de mando de procesos / Tecnología de conmutación de baja tensión / Conmutador de carga, seccionador de ruptura de carga, conmutador de control / Conmutador (ecl@ss10.0.1-27-37-14-05 [AKF062013])
Modelo
Conmutador inversor
Número de polos
3
Con posición 0 (desconexión)
Con retracción en la posición 0
No
Intensidad permanente nominal Iu
32 Ampere
Intensidad de funcionamiento nominal Ie a CA-3, 400 V
23.7 Ampere
Potencia de funcionamiento nominal en CA-3, 400 V
12 Kilowatt
Grado de protección (IP), lado delantero
IP65
Número de contactos auxiliares como contacto normalmente cerrado
0
Número de contactos auxiliares como contacto normalmente abierto
0
Número de contactos auxiliares como contacto de intercambio
0
Compatible para montaje en suelo
Compatible con montaje frontal de 4 orificios
No
Compatible para instalación de panel de distribución
No
Compatible para montaje intermedio
No
Dispositivo complete en alojamiento
Material de la carcasa
Plástico
Tipo de elemento de control
Agarre corto para pulgar
Tipo de conexión del circuito de corriente principal
Conexión enroscada