General specifications
Product name
Eaton Moeller® series CI-K Insulated enclosure
Part no.
CI-K4-125-M
EAN
4015082068974
Product Length/Depth
240 millimetre
Product height
125 millimetre
Product width
160 millimetre
Product weight
1.01 kilogram
Certifications
DIN EN 62208
IEC/EN 60529
UL94: VO/1.5 mm thickness
UL94: HB
IEC 60068-2-11
Product Tradename
CI-K
Product Type
Insulated enclosure
Product Sub Type
None
Catalog Notes
Lamp indicator L‐… can be mounted in base knock-out M20/M25
Features & Functions
Enclosure color
Light gray, Operator (RAL 7035)
Light gray, Cover (RAL 7035)
Black (RAL 9005)
Enclosure material
Plastic
1 Ω x 10¹³ (Surface resistance to IEC 60093)
Features
Halogen free
UV resistance beneath protective shield
Fitted with:
Control cable entry
Mounting plate
Knockouts
Hard knockout version
Metric cable entry knockouts at the top, bottom and back plate
General information
Cover material
Glass-fiber reinforced polycarbonate
Degree of protection
NEMA Other
IP65
Degree of protection (front side)
IP65
Dielectric strength
30 kV/mm, according to IEC 60243-1
Flammability characteristics
650 °C/1 mm thick (push-through membrane) to VDE 0471 Part 2)
960 °C/1 mm thickness (base, cover; glow wire to VDE 0471 Part 2)
Model
Surface mounting
Mounting depth
98 mm
Mounting weight capacity - max
0.9 kg
Product category
Empty enclosures
Suitable for
Emergency stop
Surface treatment
Resistant to corrosion
Track resistance
CTI 175 (base, to IEC 60112)
CTI 175 (cover, to IEC 60112)
Type
Basic enclosure
Water consumption
0.29 % (According to DIN EN ISO 62)
Ambient conditions, mechanical
Environmental resistance
Not resistant to Mineral oil
Resistant against benzene
Resistant against mineral oil
Partly resistant to acids (> 10%)
Resistant against acids (< 10%)
Resistant against gasoline
Partly resistant to benzene
Not resistant to alkalis
Resistant against salt solutions
Resistant against greases
Partly resistant to greases
Resistant against alkalis
Not resistant to benzene
Chemical resistant (Base, Cover)
Resistant against alcohol
Chemical resistant (Push-through membrane (CI-K1/CI-K2) and sealing material)
Partly resistant to alcohol
Impact resistance
IK06 (according to EN 50102)
Temperature resistance
-40 - 120 °C (enclosure)
-40 - 80 °C (gasket)
Climatic environmental conditions
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
70 °C
Climatic proofing
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78
Design verification
Equipment heat dissipation, current-dependent Pvid
0 W
Heat dissipation capacity Pdiss
26 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
0 A
Static heat dissipation, non-current-dependent Pvs
0 W
Radiated heat dissipation with separate mounting
26 W (at an ambient temperature of 20 °C)
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Please enquire
10.2.5 Lifting
Not applicable.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Meets the product standard's requirements.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Meets the product standard's requirements.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 9.0

Low-voltage industrial components (EG000017) / Empty enclosure for switchgear (EC000712)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Component for low-voltage switching technology / Empty housing for switch devices (ecl@ss13-27-37-13-01 [AKN343019])
Housing material
Plastic
Width
160 mm
Height
125 mm
Depth
240 mm
With transparent cover
No
Suitable for emergency stop
Yes
Model
Surface mounting
Degree of protection (IP)
IP65
Degree of protection (NEMA)
Other