Datasheet - GD4-100-BD3

German
English
French
Dutch
Italian
Polish
Czech
Russian
Norwegian Bokmål
English

 
Power supply unit, 3-phase, 400VAC/24VDC, 10A
Part no.  GD4-100-BD3
Catalog No.  200009
 
 

Delivery program
Product range
    GD4 power supply units
Description
    unregulated
smoothed
Phases
    Three-phase
Input voltage range
    380 - 420 V AC
Nominal input voltage
    3 x 400 V AC
Rated output voltage
    24 V DC
Rated output current
  A 10
For use with
    easy…
MFD…
EC4P…
XC-CPU…
XIOC…
PS4…
Technical data
General
Protection class
    1
Potential isolation
    Yes, VDE 0551, IEC/EN 60742, SELV
Supply frequency
     
Rated value
  Hz 50/60
Range
  Hz 50 - 60
Electromagnetic compatibility (EMC)
     
Emitted interference
    Class B (EN 55011, 22)
ESD
Air/contact discharge kV 6 kV contact (Level 3), 8 kV air (Level 3), IEC/EN 61000-4-2
RFI
    10 V/m, modulated, IEC/EN 61000 4-2
Burst
    2 kV (Level 3) IEC/EN 61000-4-4
Surge
    2 kV (Inst. Class 3), IEC/EN 61000-4-5
Surge voltage
    4.9 kV, IEC EN 60947
Environmental compatibility
     
Ambient temperature
    -25 - 55
Ambient temperature, storage
  °C - -25 - 85
Overvoltage category/pollution degree
    2, EN 50178
Vibration
    0.075 mm (10 - 57 Hz), 10 cycles, IEC 60068-2-6
Shock resistance Shock duration 11 ms
  g 15, IEC 60068-2-27 (3 shocks)
Altitude
  m Up to 2000 m a.s.l.; observe drating at higher altitudes
Notes
    

Derating

From +44 to +55 °C: linear derating

of power from 100 % to 93 %

Degree of Protection
    IP20
Fixing
    Screw fixing
Mounting position
    As required
Heat dissipation
  W 45
Input voltage
Rated value
  V AC 400
Range
  V AC Pick-off ± 5 % 380, 400, 420
Input currentnominal value per phase
  A 0.46
No-load losses
  W 14.2
Short-circuit losses
  W 28.6
Output voltage
Rated value
  V DC 24
Residual ripple
  % ≦ 3
Output current (nominal value)
  A 10
Output current, range at 55 °C
  A 0 - 10
Terminal capacities
Solid
  mm2 0.5 - 4
Flexible with ferrule
  mm2 0.5 - 2.5
Connections
    Screw connection
Weight
  kg 4.4
Fuse specification
Input current
I1 A 0.46
Circuit-breaker
     
PKZ
    PKZM0-0.63
Current setting
  A 0.46
Miniature circuit-breaker
     
FAZ
    FAZ-S1/1
Short-circuit protection only
   
Current/voltage characteristics
   
Notes


Range of rated voltages Ue at 230 V or 3 x 400 V AC (primary side)

and a load current of I = 0 A up to rated current 1 x Ie

Design verification as per IEC/EN 61439(Show features)(Hide features)
Technical data ETIM 7.0(Show features)(Hide features)
Dimensions
¹⁾ Maximum space requirements