199734 XV-102-A3-57TVRB-1E4

Delivery program

Product range
Visualisation solutions XV
Product range
easyE4
XV-102
Subrange

Touch HMI easy
Function
Touch display for easyE4
Function
as a visualization for the easyE4 control relay
Description
Touch display for easyE4, 24 VDC, 5.7 inches, TFT color, 640x480 px, Ethernet
Communication with the easyE4 via Modbus TCP
Common features of the model series
Ethernet interface
USB device
Slot for SD card
Display - Type
Color display, TFT
Touch-technology
Resistive-Touch
Number of colours
64 k Colours
Resolution
640 x 480
VGA Pixel
Screen diagonal
5.7 Inch
Model
Plastic enclosure and glass panel in plastic frame
Operating system
Windows CE 5.0 (licence incl.)
PLC-licence
no PLC function possible
License certificates for onboard interfaces
not expandable
built-in interfaces
1 x Ethernet 100base-TX/10base-T
1 x USB device
1 x RS232
Front type
Standard front with standard membrane (fully enclosed)
Utilization
Flush mounting
Slots
for SD card: 1
Memory card automation
Optionally with SD card -> article no. 139807
Pluggable communication cards (optional)
no
Touch sensor
Glass with film
Heat dissipation
9.5 W
For use with
easyE4
For use with
EASY-E4-...-12...

Technical data

Display
Display - Type
Color display, TFT
Screen diagonal
5.7 Inch
Resolution
640 x 480
VGA Pixel
Visible screen area
115 x 86 mm
Number of colours
64 k Colours
Contrast ratio (Normally)
Normally 300:1
Brightness
Normally 250 cd/m2
Back-lighting
LED
dimmable via software
Service life of back-lighting
Normally 40000 h
Resistive touch protective screen
Touch sensor (glass with foil)
Operation
Technology
Resistive-Touch
4 wire
Touch sensor
Glass with film
System
Processor
RISC CPU, 32 Bit, 400 MHz
Internal memory
DRAM (OS, Program and data memory): 64 MByte
NAND-Flash (can be used for data backup): approx. 128 MByte available
NVRAM (retained data): approx. 32 KByte available
External memory
SD Memory Card Slot: SDA Specification 1.00
Cooling
Fanless CPU and system cooling, natural convection-based passive cooling
Back-up of real-time clockBattery (service life)
non-replaceable, CR2032 soldered in
Back-up of real-time clockBackup (time at zero voltage)
Normally 10 years
Engineering
Visualisation software
GALILEO
PLC-licence
no PLC function possible
Operating system
Windows CE 5.0 (licence incl.)
Interfaces, communication
built-in interfaces
1 x Ethernet 100base-TX/10base-T
1 x USB device
1 x RS232
USB Host
USB 2.0 (1.5 - 12 Mbit/s), not galvanically isolated
RS-232
RS-232, not galvanically isolated (SUB-D plug 9 pole, UNC)
Slots
for SD card: 1
Ethernet
100Base-TX/10Base-T
Power supply
Nominal voltage
24 V DC SELV (safety extra low voltage)
permissible voltage
Effective: 19.2-30.0 V DC (rated operating voltage -20%/+25%)
Absolute with ripple: 18,0-31,2 V DC
Battery powered: 18,0-31,2 V DC (rated operating voltage -25%/+30%)
35 V DC for a duration of < 100 ms
Voltage dips
≤ 10 ms from rated voltage (24 V DC)
5 ms from undervoltage (19.2 V DC) ms
Power consumption [Pmax.]
10 W
Note on power consumption
Basic device
USB Slave to USB Host: 2.5
Total: 9.5
Heat dissipation
9.5 W
Note on heat dissipation
Heat dissipation with power consumption for 24 V
7 W for basic device + 2.5 W for USB module
Protection against polarity reversal
yes
Type of fuse
Yes (fuse not accessible)
Potential isolation
no potential isolation
General
Housing material
Plastic, gray
Front type
Standard front with standard membrane (fully enclosed)
Dimensions (W x H x D)
170 x 130 x 39 mm
flush mounted
Clearance: W x H x D ≥ 30 mm (1.18")
Inclination from vertical: ±45° (if using natural convection)
Material thickness at the installation cutout: min. 2 mm (0.08"), max. 5 mm (0.2")
Weight
0.6 kg
Degree of protection (IEC/EN 60529, EN50178, VBG 4)
IP65 (at front), IP20 (at rear)
ApprovalsApprovals
cUL (UL508)
EAC
ApprovalsExplosion protection (according to ATEX 94/9/EC)
II 3D Ex II T70°C IP5x: Zone 22, Category 3D
Approvalsshipping classification
DNV GL
Mechanical shock resistance
according to IEC 60068-2-27 g
Vibration
according to IEC/EN 60068-2-6
RoHS
conform
Environmental conditions
Climatic environmental conditionsAir pressure (operation)
795 - 1080 hPa
TemperatureStorage / Transport [ϑ]
-20 - +60 °C
TemperatureOperating ambient temperature min.
0 °C
TemperatureOperating ambient temperature max.
+50 °C
Relative humidityCondensation
Take appropriate measures to prevent condensation
Relative humidityRelative humidity
10 - 90%, non condensing
Supply voltage UAux
Rated operational voltage [UAux]
24 V DC (-20/+25%) V
Protection against polarity reversal
Yes
Potential isolation
No
Supply voltage UPow
Supply voltage [UPow]
24 DC -20 % + 25 % V
Input voltage ripple
≦ 5 %
Protection against polarity reversal
yes

Design verification as per IEC/EN 61439

Datos técnicos para la verificación del diseño
Disipación térmica estática, en función de la intensidad [Pvs]
9.5 W
Temperatura ambiente mínima de funcionamiento
0 °C
Temperatura ambiente máxima de funcionamiento
+50 °C
Verificación de diseño IEC / EN 61439
10.2 Resistencia de materiales y piezas10.2.2 Resistencia a la corrosión
Cumple con los requisitos de la norma del producto.
10.2 Resistencia de materiales y piezas10.2.3.1 Verificación de la estabilidad térmica de los armarios
Cumple con los requisitos de la norma del producto.
10.2 Resistencia de materiales y piezas10.2.3.2 Verificación de la resistencia de los materiales aislantes en condiciones de calor normales
Cumple con los requisitos de la norma del producto.
10.2 Resistencia de materiales y piezas10.2.3.3. Verificación de la resistencia de los materiales aislantes al calor excesivo y al fuego debido a los efectos eléctricos internos
Cumple con los requisitos de la norma del producto.
10.2 Resistencia de materiales y piezas10.2.4 Resistencia a radiación ultravioleta (UV)
Por favor, pregunte.
10.2 Resistencia de materiales y piezas10.2.5 Elevación
Does not apply to enclosures without lifting aids.
10.2 Resistencia de materiales y piezas10.2.6 Impacto mecánico
No se aplica, ya que todo el equipo de conmutación debe ser evaluado.
10.2 Resistencia de materiales y piezas10.2.7 Inscripciones
Cumple con los requisitos de la norma del producto.
10.3 Grado de protección de montajes
Cumple con los requisitos de la norma del producto.
10.4 Distancias de separación y fuga
Cumple con los requisitos de la norma del producto.
10.5 Protección contra descargas eléctricas
No se aplica, ya que todo el equipo de conmutación debe ser evaluado.
10.6 Incorporación de dispositivos y componentes de conmutación
No se aplica, ya que todo el equipo de conmutación debe ser evaluado.
10.7 Conexiones y circuitos eléctricos internos
Es responsabilidad del cuadrista.
10.8 Conexiones de conductores externos
Es responsabilidad del cuadrista.
10.9 Propiedades de aislamiento10.9.2 Resistencia eléctrica de frecuencia de alimentación
Es responsabilidad del cuadrista.
10.9 Propiedades de aislamiento10.9.3 Tensión de impulso soportada
Es responsabilidad del cuadrista.
10.9 Propiedades de aislamiento10.9.4 Pruebas de armarios hechos de material aislante
Es responsabilidad del cuadrista.
10.10 Aumento de la temperatura
El cuadrista es responsable del cálculo del aumento de la temperatura. Eaton proporcionará datos de disipación de calor para los dispositivos.
10.11 Resistencia a los cortocircuitos
Es responsabilidad del cuadrista. Deben tenerse en cuenta las especificaciones de la aparamenta.
10.12 Compatibilidad electromagnética
Es responsabilidad del cuadrista.
10.13 Función mecánica
El dispositivo cumple los requisitos, siempre que se observe la información del folleto de instrucciones (IL).

Approvals

Product Standards
UL 60950-01; CSA-C22.2 No. 60950-1; IEC/EN 61131-2; CE marking
UL File No.
E208621
UL Category Control No.
NWGQ2
CSA File No.
UL 60950-01; CSA-C22.2 No. 60950-1; IEC/EN 61131-2; CE marking
CSA Class No.
NWGQ8
North America Certification
UL recognized, certified by UL for use in Canada
Conditions of Acceptability
The investigated Pollution Degree is: 2

The following end-product enclosures are required: Fire

The unit must be supplied via a SELV source.

The provided Ethernet Connection is only allowed to connect to inhouse networks.
Specially designed for North America
No
Degree of Protection
IEC: IP65, UL/CSA Type: -

Dimensions

2726DRW-54