General specifications
Product name
Eaton Moeller® series EASY Accessory Bus module
Part no.
EASY-COM-SWD-C1
EAN
4015081978434
Product Length/Depth
58 millimetre
Product height
90 millimetre
Product width
36 millimetre
Product weight
0.1 kilogram
Certifications
IEC/EN 61000-6-2
IEC 60068-2-6
EN 50178
IEC/EN 61000-6-3
EN 61010
CE
IEC/EN 61131-2
IEC/EN 61000-4-2
IEC 60068-2-27
IEC 60068-2-30
UL Listed
UL File No.: E205091
UL hazardous location group A (acetylene)
UL hazardous location class I
UL hazardous location group C (ethylene)
UL hazardous location division 2
UL hazardous location group D (propane)
UL hazardous location group B (hydrogen)
Product Tradename
EASY
Product Type
Accessory
Product Sub Type
Bus module
Catalog Notes
Current consumption at 24 V DC
Features & Functions
Features
Expansion device
Expandable
General information
Degree of protection
IP20
Insulation resistance
According to EN 50178, EN 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-201
Mounting method
Front build in possible
Screw fixing using fixing brackets ZB4-101-GF1 (accessories)
Top-hat rail fixing (according to IEC/EN 60715, 35 mm)
Wall mounting/direct mounting
Rail mounting possible
Overvoltage category
II
Pollution degree
2
Product category
Control relays easyE4
Protocol
TCP/IP
Other bus systems
Residual ripple
≤ 5 %
≤ 5 % (input voltage)
Type
Communication module
Voltage type
DC
Ambient conditions, mechanical
Drop and topple
50 mm Drop height, Drop to IEC/EN 60068-2-31
Height of fall (IEC/EN 60068-2-32) - max
0.3 m
Mounting position
Horizontal
Vertical
Shock resistance
15 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 18 Impacts
Climatic environmental conditions
Air pressure
795 - 1080 hPa (operation)
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
55 °C
Ambient storage temperature - min
-40 °C
Ambient storage temperature - max
70 °C
Environmental conditions
Clearance in air and creepage distances according to EN 50178, EN 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-201
Condensation: prevent with appropriate measures
Relative humidity
5 - 95 % (IEC 60068-2-30, IEC 60068-2-78)
Electro magnetic compatibility
Air discharge
8 kV
Burst impulse
1 kV, SmartWire-DT cable, Signal cable, according to IEC/EN 61131-2, Level 3
Contact discharge
6 kV, Electrostatic discharge (ESD)
Electromagnetic fields
1 V/m at 2 - 2.7 GHz (according to IEC EN 61000-4-3)
10 V/m at 0.08 - 1.0 GHz (according to IEC EN 61000-4-3)
3 V/m at 1.4 - 2 GHz (according to IEC EN 61000-4-3)
Immunity to line-conducted interference
10 V (according to IEC/EN 61000-4-6)
Radio interference class
Class B (EN 61000-6-3)
Surge rating
1 kV, Supply cables, asymmetrical, power pulses (Surge), EMC
According to IEC/EN 61000-4-5, power pulses (Surge), EMC
0.5 kV, Supply cables, symmetrical, power pulses (Surge), EMC
Voltage dips
According to EN 61131-2
≤ 10 ms
Terminal capacities
Terminal capacity
0.2 - 4 mm² (AWG 22 - 12), solid
0.2 - 2.5 mm² (22 - 12 AWG), flexible with ferrule
Screwdriver size
3.5 x 0.8 mm, Terminal screw
Tightening torque
0.6 Nm, Screw terminals
Electrical rating
Heat dissipation
1 W (at 24 V DC)
Inrush current
12.5 A (for 6 ms)
Power consumption
14.5 W
Rated control supply voltage
24 V DC (UAUX, -15 %/+20 %)
20.4 - 28.8 V DC
Rated operational voltage
24 V DC (-15 %/+ 20 % - power supply)
Supply current
0.7 A, Imax, SmartWire-DT supply
2 A (UL), Imax, Supply voltage UAux
Supply voltage at AC, 50 Hz - min
0 V AC
Supply voltage at AC, 50 Hz - max
0 V AC
Supply voltage at DC - min
20.4 V DC
Supply voltage at DC - max
28.8 V DC
Voltage rating
24 Vdc
Short-circuit rating
Short-circuit protection
No, Short-circuit rating, Supply voltage UAux
Yes, SmartWire-DT supply voltage
≥ 3 A (T) (e.g. FAZ C3), Fuse, Power supply
Communication
Addressing
Address set automatically via Configuration button
Bus termination
Integrated in the device, SmartWire-DT
With SWD4-RC8-10, SmartWire-DT line end
Connection
SmartWire-DT blade terminal SWD4-8MF2
Connection type
SWD: Plug, 8-pole
Screw terminal
Data transfer rate
125 kBit/s, SmartWire-DT
250 kBit/s, SmartWire-DT
LED indicator
Status indication of SmartWire-DT master: Green and red LEDs
Station
SmartWire-DT master, SmartWire-DT network
Input/Output
Input current
500 mA (Uₑ)
Number of inputs (analog)
0
Number of inputs (digital)
0
Number of outputs (analog)
0
Number of outputs (digital)
0
Output voltage
Uₑ - 0.3 V (SWD-OUT, Supply voltage UAUX)
Safety
Explosion safety category for gas
None
Potential isolation
Between SmartWire-DT supply voltage and Power supply POW: no
Between SmartWire-DT supply voltage and AUX: yes
Between Supply voltage UAUX and SmartWire-DT: yes
Between supply voltage UAUX and Power supply POW: yes
Between SmartWire-DT supply voltage and COM Interface: yes
Protection against polarity reversal
Yes
Explosion safety category for dust
None
Design verification
Equipment heat dissipation, current-dependent Pvid
10.5 W
Static heat dissipation, non-current-dependent Pvs
4 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Meets the product standard's requirements.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 9.0

Programmable logic controllers PLC (EG000024) / Logic module (EC001417)
Electric engineering, automation, process control engineering / Control, Process Control System (PCS) / Programmable logic control (SPS) / Logic module (ecl@ss13-27-24-22-16 [AKE539019])
Supply voltage AC 50 Hz
0 - 0 V
Supply voltage AC 60 Hz
0 - 0 V
Supply voltage DC
20.4 - 28.8 V
Voltage type (supply voltage)
DC
Switching current
0 A
Power consumption
14.5 W
Number of analogue inputs
0
Number of analogue outputs
0
Number of digital inputs
0
Number of digital outputs
0
With relay output
No
Number of HW-interfaces industrial Ethernet
0
Number of interfaces PROFINET
0
Number of HW-interfaces RS-232
0
Number of HW-interfaces RS-422
0
Number of HW-interfaces RS-485
0
Number of HW-interfaces serial TTY
0
Number of HW-interfaces USB
0
Number of HW-interfaces parallel
0
Number of HW-interfaces wireless
0
Number of HW-interfaces other
1
With optical interface
No
Supporting protocol for EtherCAT
No
Supporting protocol for TCP/IP
Yes
Supporting protocol for PROFIBUS
No
Supporting protocol for CAN
No
Supporting protocol for INTERBUS
No
Supporting protocol for ASI
No
Supporting protocol for KNX
No
Supporting protocol for Modbus
No
Supporting protocol for Data-Highway
No
Supporting protocol for DeviceNet
No
Supporting protocol for SUCONET
No
Supporting protocol for LON
No
Supporting protocol for PROFINET IO
No
Supporting protocol for PROFINET CBA
No
Supporting protocol for SERCOS
No
Supporting protocol for Foundation Fieldbus
No
Supporting protocol for EtherNet/IP
No
Supporting protocol for AS-Interface Safety at Work
No
Supporting protocol for DeviceNet Safety
No
Supporting protocol for INTERBUS-Safety
No
Supporting protocol for PROFIsafe
No
Supporting protocol for SafetyBUS p
No
Supporting protocol for other bus systems
Yes
Radio standard Bluetooth
No
Radio standard WLAN 802.11
No
Radio standard GPRS
No
Radio standard GSM
No
Radio standard UMTS
No
IO link master
No
Redundancy
No
With display
No
Degree of protection (IP)
IP20
Basic device
No
Expandable
Yes
Expansion device
Yes
With time switch clock
No
Rail mounting possible
Yes
Wall mounting/direct mounting
Yes
Front built-in possible
Yes
Rack-assembly possible
No
Suitable for safety functions
No
SIL according to IEC 61508
None
Performance level according to EN ISO 13849-1
None
Appendant operation agent (Ex ia)
No
Appendant operation agent (Ex ib)
No
Explosion safety category for gas
None
Explosion safety category for dust
None
Certified for UL hazardous location class I
Yes
Certified for UL hazardous location class II
No
Certified for UL hazardous location class III
No
Certified for UL hazardous location division 1
No
Certified for UL hazardous location division 2
Yes
Certified for UL hazardous location group A (acetylene)
Yes
Certified for UL hazardous location group B (hydrogen)
No
Certified for UL hazardous location group C (ethylene)
Yes
Certified for UL hazardous location group D (propane)
Yes
Certified for UL hazardous location group E (metal dusts)
No
Certified for UL hazardous location group F (carbonaceous dusts)
No
Certified for UL hazardous location group G (non-conductive dusts)
No
Width
36 mm
Height
90 mm
Depth
58 mm