Delivery program

Product range
Control relays easyE4
Subrange
easy communication module
Accessories
Connect up to 99 SmartWire-DT modules with a total of up to 244 digital and/or 88 analog inputs/outputs, can be switched on using a SmartWire-DT phase element
Basic function
easy communication module
For use with
EASY-E4-...-12...
from generation 05
Description
combines the functionality of an easyE4 with direct connection to the SmartWire-DT communication system
up to 99 SmartWire-DT modules with a total of up to 224 digital and/or up to 88 analog inputs/outputs via SmartWire-DT phase element
Screw terminals
Supply voltage
24 V DC
For use with
EASY-E4-

Technical data

General
Standards
IEC/EN 61131-2
IEC/EN IEC 61010-2-201
ApprovalsApprovals
cULus
Approvalscertificate
CE
Dimensions (W x H x D)
35.5 x 90 x 58 mm
Weight
0.087 kg
Mounting
Top-hat rail IEC/EN 60715, 35 mm or screw fixing using fixing brackets ZB4-101-GF1 (accessories)
Connection type
screw terminal
Terminal capacities
Screw terminalsSolid
0,2 - 4 mm2
Screw terminalsflexible
0,2 - 2,5 mm2
Screw terminalsSolid or flexible conductor, with ferrule
0,2 - 2,5 mm2
Screw terminalsSolid or stranded
22 - 12 AWG
Screw terminalsStandard screwdriver
0.8 x 3.5 mm
Screw terminalsTightening torque
0.5 - 0.7 Nm
Screw terminalsStripping length
6.5 mm
Climatic environmental conditions
Operating ambient temperature
-25 to 55, cold as per IEC 60068-2-1, heat as per IEC 60068-2-2 °C
Condensation
Take appropriate measures to prevent condensation
Storage [ϑ]
-40 - +70 °C
relative humidity
in accordance with IEC 60068-2-30, IEC 60068-2-78
5 - 95 %
Air pressure (operation)
795 - 1080 hPa
Ambient conditions, mechanical
Protection type (IEC/EN 60529, EN50178, VBG 4)
IP20
Mounting position
Vertical or horizontal
Vibrations (IEC/EN 61131-2:2008)Constant amplitude 3,5 mm
5 - 8.4 Hz
Vibrations (IEC/EN 61131-2:2008)Constant acceleration 1 g
8.4 - 150 Hz
Mechanical shock resistance (IEC/EN 60068-2-27) semi-sinusoidal 15 g/11 ms
18 Impacts
Drop to IEC/EN 60068-2-31 [Drop height]
50 mm
Free fall, packaged (IEC/EN 60068-2-32)
0.3 m
Electromagnetic compatibility (EMC)
Overvoltage category/pollution degree
II/2
Electrostatic discharge (ESD)applied standard
nach IEC/EN 61000-4-2
Electrostatic discharge (ESD)Air discharge
8 kV
Electrostatic discharge (ESD)Contact discharge
6 kV
Electrostatic discharge (ESD)Environment (EMC)
This product has been designed for use in the industrial sector (Environment A).
Electromagnetic fields (RFI) to IEC EN 61000-4-3
0.08 - 1.0 GHz: 10
1.4 - 6 GHz: 3 V/m
Environment (EMC)
This product has been designed for use in the industrial sector (Environment A).
Radio interference suppression
IEC/EN 61000-6-4
Class A
Burst
according to IEC/EN 61000-4-4
Supply cables: 2
SmartWire-DT Leitungen: 1 kV
power pulses (Surge)
according to IEC/EN 61000-4-5
0.5 kV (supply cables, symmetrical)
1 kV (supply cables, asymmetrical)
Immunity to line-conducted interference to (IEC/EN 61000-4-6)
10 V
Insulation resistance
Clearance in air and creepage distances
IEC 61010-2-201, EN IEC 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-201
Insulation resistance
IEC 61010-2-201, EN IEC 61010-2-201, UL61010-2-201, CSA-C22.2 NO. 61010-2-201
Power supply
Rated operational voltage [Ue]
24 DC (-15/+20%) V
Supply voltage UPowSupply voltage
24 V DC
Input voltage ripple
≦ 5 %
Protection against polarity reversal
yes
Rated current [I]
0.7 A
Overload proof
yes
Inrush current and length
12.5 for 6 ms A
Voltage dips
≤ In accordance with IEC 61131-2
≤ 10 ms
Fuse
≧ 3 A (T) (e.g FAZ C3) A
Potential isolation
from power supply AUX: yes
to the base unit: yes
to SmartWire-DT: no
Static heat dissipation, non-current-dependent [Pvs]
2.5 W
Heat dissipation at 24 V DC
2,5 W
Supply voltage UAux
Rated operational voltage [UAux]
24 V DC (-15/+20%) SELV V
Permissible range
20.4 - 28.8 V DC
Output voltage SWD-OUT
typ. Ue - 0.4 V
Protection against polarity reversal
yes
Residual ripple on the input voltage
≦ 5 %
Max. current [Imax]
3 (IEC)
2 (UL) A
Short-circuit rating
nein, externe Absicherung FAZ-Z3
Heat dissipation
type. 1 W at 24 V DC
Potential isolation
from power supply POW: yes
to the base device: yes
to SmartWire-DT: yes
SmartWire-DT supply voltage
Rated operating voltage [Ue]
14.5 ± 3 % V
max. current [Imax]
0.7 A
Short-circuit rating
Yes
Potential isolation
from power supply POW: no
to the base device: yes
to AUX: yes
SmartWire-DT network
Station type
Client for SmartWire-DT Master
Number of SmartWire-DT slaves
Max. 99
Baud Rates
125/250 kBd
Address allocation
Automatically (via Configuration button)
Status indication
SWD-LED: orange/green/red
Config. LED: green/red
Connections
Plug, 8-pole
Plug connector
Blade terminal SWD4-8MF2
Bus termination
Integrated in the device
SmartWire-DT line end with SWD4-RC8-10

Design verification as per IEC/EN 61439

Technical data for design verification
Static heat dissipation, non-current-dependent [Pvs]
2.5 W
Operating ambient temperature min.
-25 °C
Operating ambient temperature max.
+55 °C
IEC/EN 61439 design verification
10.2 Strength of materials and parts10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
Meets the product standard's requirements.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9 Insulation properties10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9 Insulation properties10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9 Insulation properties10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 8.0

Programmable logic controllers PLC (EG000024) / Logic module (EC001417)
Electric engineering, automation, process control engineering / Control / Programmable logic control (SPS) / Logic module (ecl@ss10.0.1-27-24-22-16 [AKE539014])
Supply voltage AC 50 Hz
0 - 0 V
Supply voltage AC 60 Hz
0 - 0 V
Supply voltage DC
20.4 - 28.8 V
Voltage type of supply voltage
DC
Switching current
5 A
Number of analogue inputs
0
Number of analogue outputs
0
Number of digital inputs
0
Number of digital outputs
0
With relay output
No
Number of HW-interfaces industrial Ethernet
0
Number of interfaces PROFINET
0
Number of HW-interfaces RS-232
0
Number of HW-interfaces RS-422
0
Number of HW-interfaces RS-485
0
Number of HW-interfaces serial TTY
0
Number of HW-interfaces USB
0
Number of HW-interfaces parallel
0
Number of HW-interfaces Wireless
0
Number of HW-interfaces other
1
With optical interface
No
Supporting protocol for TCP/IP
Yes
Supporting protocol for PROFIBUS
No
Supporting protocol for CAN
No
Supporting protocol for INTERBUS
No
Supporting protocol for ASI
No
Supporting protocol for KNX
No
Supporting protocol for Modbus
No
Supporting protocol for Data-Highway
No
Supporting protocol for DeviceNet
No
Supporting protocol for SUCONET
No
Supporting protocol for LON
No
Supporting protocol for PROFINET IO
No
Supporting protocol for PROFINET CBA
No
Supporting protocol for SERCOS
No
Supporting protocol for Foundation Fieldbus
No
Supporting protocol for EtherNet/IP
No
Supporting protocol for AS-Interface Safety at Work
No
Supporting protocol for DeviceNet Safety
No
Supporting protocol for INTERBUS-Safety
No
Supporting protocol for PROFIsafe
No
Supporting protocol for SafetyBUS p
No
Supporting protocol for other bus systems
Yes
Radio standard Bluetooth
No
Radio standard Wi-Fi 802.11
No
Radio standard GPRS
No
Radio standard GSM
No
Radio standard UMTS
No
IO link master
No
Redundancy
No
With display
No
Degree of protection (IP)
IP20
Basic device
No
Expandable
Yes
Expansion device
Yes
With time switch clock
No
Rail mounting possible
Yes
Wall mounting/direct mounting
Yes
Front built-in possible
Yes
Rack-assembly possible
No
Suitable for safety functions
No
SIL according to IEC 61508
None
Performance level according to EN ISO 13849-1
None
Appendant operation agent (Ex ia)
No
Appendant operation agent (Ex ib)
No
Explosion safety category for gas
None
Explosion safety category for dust
None
Width
36 mm
Height
90 mm
Depth
58 mm

Approvals

UL File No.
E205091
North America Certification
UL listed
Degree of Protection
IEC: IP20, UL/CSA Type: -

Dimensions

2528DIM-16