197375 P3-100/SE3/SVB-SW/N

Delivery program

Product range
Main switch
maintenance switch
Part group reference
P3
Stop Function
STOP function
With black rotary handle and locking ring
Information about equipment supplied
auxiliary contact fitted by user.
Notes
in steel enclosure
Number of poles
3 pole + N
Auxiliary contacts
0 N/O
0 N/C
Locking facility
Lockable in the 0 (Off) position
Degree of Protection
IP65
000Z083
Design
surface mounting
000Z428
Contact sequence
115S010-2
Switching angle
90 °
Function
1150SPC-194
Motor rating AC-23A, 50 - 60 Hz [P]
400 V [P]
55 kW
Rated uninterrupted current [Iu]
100 A
Note on rated uninterrupted current !u
Rated uninterrupted current Iu is specified for max. cross-section.

Technical data

General
Standards
IEC/EN 60947, VDE 0660, IEC/EN 60204
Switch disconnector in accordance with IEC/EN 60947-3
Ambient temperatureEnclosed
-25 - +40 °C
Overvoltage category/pollution degree
III/3
Rated impulse withstand voltage [Uimp]
6000 V AC
Mechanical shock resistance
15 g
Mounting position
As required
Contacts
Mechanical variablesNumber of poles
3 pole + N
Mechanical variablesAuxiliary contacts
0 N/O
Mechanical variablesAuxiliary contacts
0 N/C
Electrical characteristicsRated operational voltage [Ue]
690 V AC
Electrical characteristicsRated uninterrupted current [Iu]
100 A
Electrical characteristicsNote on rated uninterrupted current !u
Rated uninterrupted current Iu is specified for max. cross-section.
Load rating with intermittent operation, class 12AB 25 % DF
2 x Ie
Load rating with intermittent operation, class 12AB 40 % DF
1.6 x Ie
Load rating with intermittent operation, class 12AB 60 % DF
1.3 x Ie
Short-circuit ratingFuse
100 A gG/gL
Rated short-time withstand current (1 s current) [Icw ]
2000 Arms
Note on rated short-time withstand current lcw
Current for a time of 1 second
Rated conditional short-circuit current [Iq]
4 (Load side)
80 (Supply side) kA
Switching capacity
cos ϕ rated making capacity as per IEC 60947-3
950 A
Rated breaking capacity cos ϕ to IEC 60947-3230 V
760 A
Rated breaking capacity cos ϕ to IEC 60947-3400/415 V
740 A
Rated breaking capacity cos ϕ to IEC 60947-3500 V
880 A
Rated breaking capacity cos ϕ to IEC 60947-3690 V
520 A
Safe isolation to EN 61140between the contacts
440 V AC
Safe isolation to EN 61140Current heat loss per contact at Ie
7.5 W
Lifespan, mechanical [Operations]
> 0.1 x 106
Maximum operating frequency [Operations/h]
1200
AC AC-3Rating, motor load switch [P]220 V 230 V [P]
22 kW
AC AC-3Rating, motor load switch [P]400 V 415 V [P]
37 kW
AC AC-3Rating, motor load switch [P]500 V [P]
45 kW
AC AC-3Rating, motor load switch [P]690 V [P]
37 kW
AC AC-3Rated operational current motor load switch230 V [Ie]
71 A
AC AC-3Rated operational current motor load switch400V 415 V [Ie]
71 A
AC AC-3Rated operational current motor load switch500 V [Ie ]
65 A
AC AC-3Rated operational current motor load switch690 V [Ie]
23.8 A
AC AC-23AMotor rating AC-23A, 50 - 60 Hz [P]230 V [P]
30 kW
AC AC-23AMotor rating AC-23A, 50 - 60 Hz [P]400 V 415 V [P]
55 kW
AC AC-23AMotor rating AC-23A, 50 - 60 Hz [P]500 V [P]
55 kW
AC AC-23AMotor rating AC-23A, 50 - 60 Hz [P]690 V [P]
55 kW
AC AC-23ARated operational current motor load switch230 V [Ie]
100 A
AC AC-23ARated operational current motor load switch400 V 415 V [Ie]
100 A
AC AC-23ARated operational current motor load switch500 V [Ie]
96 A
AC AC-23ARated operational current motor load switch690 V [Ie]
68 A
DCDC-1, Load-break switches L/R = 1 msRated operational current [Ie]
100 A
DCDC-1, Load-break switches L/R = 1 msVoltage per contact pair in series
60 V
DCDC-23A, motor load switch L/R = 15 ms24 VRated operational current [Ie]
50 A
DCDC-23A, motor load switch L/R = 15 ms24 VContacts
1 Quantity
DCDC-23A, motor load switch L/R = 15 ms48 VRated operational current [Ie]
50 A
DCDC-23A, motor load switch L/R = 15 ms48 VContacts
2 Quantity
DCDC-23A, motor load switch L/R = 15 ms60 VRated operational current [Ie]
50 A
DCDC-23A, motor load switch L/R = 15 ms60 VContacts
2 Quantity
DCDC-23A, motor load switch L/R = 15 ms120 VRated operational current [Ie]
25 A
DCDC-23A, motor load switch L/R = 15 ms120 VContacts
3 Quantity
Control circuit reliability at 24 V DC, 10 mA [Fault probability]
< 10-5,< 1 failure in 100,000 switching operations HF
Terminal capacities
Solid or stranded
1 x (2,5 - 35)
2 x (2,5 - 10) mm2
Flexible with ferrules to DIN 46228
1 x (1.5 - 25)
2 x (1.5 - 6) mm2
Tightening torque for terminal screw
3 Nm
Technical safety parameters:
Notes
B10d values as per EN ISO 13849-1, table C1

Technical data ETIM 7.0

Conmutadores en baja tensión (EG000017) / Disyuntor (EC000216)
Tecnología electrónica, de automatización y de mando de procesos / Tecnología de conmutación de baja tensión / Conmutador de carga, seccionador de ruptura de carga, conmutador de control / Seccionador de ruptura de carga compacto (ecl@ss10.0.1-27-37-14-03 [AKF060013])
Versión de interruptor principal
No
Versión de interruptor de mantenimiento/servicio
Versión de interruptor de seguridad
No
Versión de instalación de parada de emergencia
No
Número de conmutadores
1
Tensión de funcionamiento nominal máxima Ue CA
690 Volt
Tensión de funcionamiento nominal
690 - 690 Volt
Intensidad permanente nominal Iu
100 Ampere
Potencia de funcionamiento nominal en CA-3, 400 V
37 Kilowatt
Corriente no disruptiva de corta duración nominal lcw
2 kiloampere
Potencia de funcionamiento nominal a CA-23, 400 V
55 Kilowatt
Intensidad nominal condicionado de cortocircuito Iq
4 kiloampere
Número de polos
4
Número de contactos auxiliares como contacto normalmente cerrado
0
Número de contactos auxiliares como contacto normalmente abierto
0
Número de contactos auxiliares como contacto de intercambio
0
Accionamiento por motor opcional
No
Accionamiento por motor integrado
No
Liberación de tensión opcional
No
Construcción de dispositivo
Dispositivo completo en carcasa
Compatible para montaje en suelo
Compatible para montaje frontal
No
Compatible para centro de montaje frontal
No
Compatible para instalación de panel de distribución
No
Compatible para montaje intermedio
No
Elemento de control de color
Negro
Tipo de elemento de control
Dispositivo giratorio de acoplamiento a la puerta
Con capacidad de interbloqueo
Tipo de conexión del circuito de corriente principal
Conexión enroscada
Grado de protección (IP), lado delantero
IP65

Dimensions

1150DIM-191