Delivery program

Product range
Electronic motor starter
Product range
SmartWire-DT slave
Subrange
SmartWire-DT electronic motor starters
Basic function
DOL starters (complete devices)
Function
For connecting to SmartWire-DT for expanded diagnostics
Description
DOL starting
Motor protection
Circuit design: safety output stage with bypass, three-phase disconnect.
Motor current additionally adjustable via SmartWire-DT.
Messages
Operational readiness
Operating direction feedback
Motor current in %
Motor current in A
Thermal motor image in %
Overload prewarning
Trip indications (overload, phase failure, etc.)
Set short-circuit release value
Device Type
Commands
Operating the motor starter
Manual reset
Automatic reset
Motor ratings
Max. rating for three-phase motors, 50 - 60 HzAC-53a380 V 400 V 415 V [P]
0.06 - 1.1 kW
Setting range of overload releases [Ir]
0,18 - 3 A_x
Actuating voltage
24 V DC
Connection technique
Push in terminals
Connection to SmartWire-DT
yes

Technical data

General
Standards
IEC/EN 60947-4-2
UL508
Ambient temperatureStorageMin. ambient temperature, storage
- 40 °C
Ambient temperatureStorageAmbient temperature, storage max.
+ 80 °C
Ambient temperatureOpenOperating ambient temperature min.
-5 °C
Ambient temperatureOpenOperating ambient temperature max.
+55 °C
Weight
0.22 kg
Mounting
Top-hat rail IEC/EN 60715, 35 mm
Protection type (IEC/EN 60529, EN50178, VBG 4)
IP20
Mounting position
Vertical
Motor feeder at bottom
Terminal capacity Push-in terminals
0.2 - 2.5 mm2
Terminal capacity Push-in terminals
24 - 14 AWG
Main conducting paths
Rated operational voltage [Ue]
500 V AC
Operational voltage rangeOperating voltage range min.
42 V
Operational voltage rangeOperating voltage range max.
550 V
Rated operational currentAC-51 [Ie]
3 A
Rated operational currentAC-53a [Ie]
3 A
Rated operational current
AC-53a: Please note possible derating.
Rated operational currentSetting range of overload releases [Ir]
0,18 - 3 A_x
Release class
10 CLASS
Heat dissipation [PV]
0.1 - 2.5 W
Control section
Rated control voltage [Us ]
24 V DC
Control voltage range
19,2 - 30 V DC V
Residual ripple on the input voltage
≦ 5 %
Rated control current [Is]
60 mA
Current draw inrush
120 mA
Actuating circuit (ON, L, R)Rated actuation voltage [Uc ]
24 V
Actuating circuit (ON, L, R)Switching level "Low"
-3 - +9.6 V DC V
Actuating circuit (ON, L, R)Switching level "confirm Off"
< 5 V DC V
Actuating circuit (ON, L, R)Switching level "High"
19.2 - 30 V DC V
Actuating circuit (ON, L, R)Rated actuating current [Ic]
7 mA
Electromagnetic compatibility (EMC)
Radio interference suppression
EN 55011
EN 61000-6-3, Class A (emitted interference, radiated)

Design verification as per IEC/EN 61439

Technical data for design verification
Rated operational current for specified heat dissipation [In]
3 A
Heat dissipation per pole, current-dependent [Pvid]
0 W
Equipment heat dissipation, current-dependent [Pvid]
2.5 W
Static heat dissipation, non-current-dependent [Pvs]
2 W
Heat dissipation capacity [Pdiss]
0 W
Operating ambient temperature min.
-5 °C
Operating ambient temperature max.
+55 °C
If necessary, Allow for derating
IEC/EN 61439 design verification
10.2 Strength of materials and parts10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9 Insulation properties10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9 Insulation properties10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9 Insulation properties10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 8.0

Low-voltage industrial components (EG000017) / Motor starter/Motor starter combination (EC001037)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Load breakout, motor breakout / Motor starter combination (ecl@ss10.0.1-27-37-09-05 [AJZ718013])
Type of motor starter
Direct online starter (DOL)
With short-circuit release
No
Rated control supply voltage Us at AC 50HZ
0 - 0 V
Rated control supply voltage Us at AC 60HZ
0 - 0 V
Rated control supply voltage Us at DC
24 - 24 V
Voltage type for actuating
DC
Rated operation power at AC-3, 230 V, 3-phase
0.55 kW
Rated operation power at AC-3, 400 V
1.1 kW
Rated power, 460 V, 60 Hz, 3-phase
0 kW
Rated power, 575 V, 60 Hz, 3-phase
0 kW
Rated operation current Ie
3 A
Rated operation current at AC-3, 400 V
3 A
Overload release current setting
0.18 - 3 A
Rated conditional short-circuit current, type 1, 480 Y/277 V
0 A
Rated conditional short-circuit current, type 1, 600 Y/347 V
0 A
Rated conditional short-circuit current, type 2, 230 V
0 A
Rated conditional short-circuit current, type 2, 400 V
0 A
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
Ambient temperature, upper operating limit
55 °C
Temperature compensated overload protection
Yes
Release class
CLASS 10
Type of electrical connection of main circuit
Spring clamp connection
Type of electrical connection for auxiliary- and control current circuit
Spring clamp connection
Rail mounting possible
Yes
With transformer
No
Number of command positions
0
Suitable for emergency stop
No
Coordination class according to IEC 60947-4-3
Class 1
Number of indicator lights
0
External reset possible
No
With fuse
No
Degree of protection (IP)
IP20
Degree of protection (NEMA)
Other
Supporting protocol for TCP/IP
No
Supporting protocol for PROFIBUS
No
Supporting protocol for CAN
No
Supporting protocol for INTERBUS
No
Supporting protocol for ASI
No
Supporting protocol for Modbus
No
Supporting protocol for Data-Highway
No
Supporting protocol for DeviceNet
No
Supporting protocol for SUCONET
No
Supporting protocol for LON
No
Supporting protocol for PROFINET IO
No
Supporting protocol for PROFINET CBA
No
Supporting protocol for SERCOS
No
Supporting protocol for Foundation Fieldbus
No
Supporting protocol for EtherNet/IP
No
Supporting protocol for AS-Interface Safety at Work
No
Supporting protocol for DeviceNet Safety
No
Supporting protocol for INTERBUS-Safety
No
Supporting protocol for PROFIsafe
No
Supporting protocol for SafetyBUS p
No
Supporting protocol for other bus systems
Yes
Width
22.5 mm
Height
99 mm
Depth
114.5 mm