Delivery program

Approvals
CE, cULus
EAC
certificate
CE
Connection design in TOP direction
Push-in spring-cage terminal

Technical data

General
Standards
EN 61131
ApprovalsApprovals
CE, cULus
EAC
Approvalscertificate
CE
Electromagnetic compatibility (EMC)ESD [Air/contact discharge]
8 / 4 kV
Electromagnetic compatibility (EMC)Electromagnetic fields [(0.08…1) / (1,4…2) / (2…2,7) GHz ]
10 / 3 / 1 V/m
Electromagnetic compatibility (EMC)BurstSupply cable
2 kV
Electromagnetic compatibility (EMC)BurstSignal cable
1 kV
Electromagnetic compatibility (EMC)SurgeSupply cable (balanced / unbalanced)
0,5 / 0,5 kV
Electromagnetic compatibility (EMC)SurgeSignal cable (unbalanced)
1 kV
Electromagnetic compatibility (EMC)Radiated RFI
10 V
Electromagnetic compatibility (EMC)Emitted interference (radiated, high frequency) [(30...230 MHz) / (230...1000 MHz)]
40 / 47 class A dB
Electromagnetic compatibility (EMC)Voltage fluctuations/voltage dips
Yes / 20 ms
Ambient conditionsClimatic conditionsClimatic proofing
Dry heat to IEC 60068-2-2
Damp heat as per EN 60068-2-3
Ambient conditionsClimatic conditionsAir pressure (operation)
795 - 1080 hPa
Ambient conditionsClimatic conditionsRelative humidity
< 95%, non-condensing
Ambient conditionsClimatic conditionsCondensation
prevent with suitable measures
Ambient conditionsTemperatureOperation
-25 - +55 °C
Ambient conditionsTemperatureStorage, transport [ϑ]
-25 - +80 °C
Degree of Protection
IP20
Mounting position
Vertical (on horizontal top-hat rail)
Free fall, packaged (IEC/EN 60068-2-32)
1 m
Vibrations [3,5 mm / 1 g]
5 - 8.4 / 8.4 -150 Hz
Mechanical shock resistance [Semisinusoidal 15 g/11 ms]
9 Impacts
Terminations
Rated operational dataInsulating material group
I
Rated operational dataOvervoltage category / pollution degree
II / 2
Rated operational dataRated operating voltage
160 V
Rated operational dataMaximum load current/cross-sectional area
6/1.5 A / mm²
Connection design in TOP direction
Push-in spring-cage terminal
Stripping length
10 mm
Gauge pin IEC/EN 60947-1
A1
Connection specifications"e" solid H07V-U
0.2 - 1.5 mm2
Connection specifications"f" flexible H 07V-K
0.2 - 1.5 mm2
Connection specifications"f" with ferrules without plastic collar according to DIN 46228-1 (ferrules crimped gas-tight)
0.25-1.5 mm2
Connection specifications"f" with ferrules with plastic collar according to DIN 46228-1 (ferrules crimped gas-tight)
0.25-1.5 mm2
Connection specificationsCable size
24 - 16 AWG
Supply
Power supply - InputPower supplyRated operating voltage [Ue]
24 V
Power supply - InputPower supplyRated operational current [Ie]
2.8 A
Power supply - InputPower supplyPotential isolation [PE (polyethylene)]
No
Heat dissipationMax. heat dissipation
8 W
Heat dissipationNotes on heat dissipation
The max. heat dissipation is specified as the maximum power produced inside the device's housing.
Digital inputs
Channels
4 (interruptfähig) Number
Input voltageNominal input voltage [Ue]
24 V DC
Input voltageLow level [UeL]
0 < UeL < +5 V
Input voltageHigh level [UeH]
+15 < UeH < +30 V
Input currentInput current, nominal value [Ie]
2 mA
Input currentLow level⁄active level [IeL]
≤1.1 mA
Input currentHigh level⁄active level [IeH]
≥2.3 mA
Input delaytRising edge
< 300 µs
Input delaytFalling edge
< 300 µs
Potential isolation
No Input to input
Heat dissipation (per active channel)
0.05 inputs as per EN61131-2 Type 1; inputs can also be operated as outputs W
Digital outputs
Channels
4 Quantity
Output currentOutput current, nominal value [IaL]
0.5 A
Short-circuit rating
Yes
Potential isolation
No Output against output
Heat dissipation (internal, per active channel)
0.1 W
Utilization factor [%]
100% (Ʃ IAmax = 2A) g
Delay on signal change and resistive loadfrom Low to High level
200 µs
Delay on signal change and resistive loadFrom High to Low signal
200 µs
Notes on digital outputs
Protective devices must be installed directly at the inductive load in order to prevent interference.

Design verification as per IEC/EN 61439

Technical data for design verification
Static heat dissipation, non-current-dependent [Pvs]
8 W
Operating ambient temperature min.
-25 °C
Operating ambient temperature max.
+55 °C
Degree of Protection
IP20
IEC/EN 61439 design verification
10.2 Strength of materials and parts10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
Meets the product standard's requirements.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9 Insulation properties10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9 Insulation properties10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9 Insulation properties10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 7.0

PLC's (EG000024) / PLC CPU-module (EC000236)
Electric engineering, automation, process control engineering / Control / Programmable logic control (SPS) / SPS - basic device (ecl@ss10.0.1-27-24-22-07 [AKE530014])
Supply voltage AC 50 Hz
0 - 0 V
Supply voltage AC 60 Hz
0 - 0 V
Supply voltage DC
18 - 30 V
Voltage type of supply voltage
DC
Voltage type of supply voltage
DC
Number of relay outputs
0
Max. number of time switches
1000
Model
Modular
Processing time (1K, binary operation)
0.0011 ms
Number of HW-interfaces industrial Ethernet
0
Number of interfaces PROFINET
0
Number of HW-interfaces RS-232
0
Number of HW-interfaces RS-422
0
Number of HW-interfaces RS-485
0
Number of HW-interfaces USB
0
Number of HW-interfaces parallel
0
Number of HW-interfaces Wireless
0
Number of HW-interfaces other
1
Number of analogue outputs
0
Number of analogue inputs
0
Number of digital inputs
0
Number of digital outputs
0
With optical interface
No
Supporting protocol for TCP/IP
Yes
Supporting protocol for PROFIBUS
No
Supporting protocol for CAN
Yes
Supporting protocol for INTERBUS
No
Supporting protocol for ASI
No
Supporting protocol for KNX
No
Supporting protocol for MODBUS
Yes
Supporting protocol for Data-Highway
No
Supporting protocol for DeviceNet
No
Supporting protocol for SUCONET
No
Supporting protocol for LON
No
Supporting protocol for PROFINET IO
No
Supporting protocol for PROFINET CBA
No
Supporting protocol for SERCOS
No
Supporting protocol for Foundation Fieldbus
No
Supporting protocol for EtherNet/IP
Yes
Supporting protocol for AS-Interface Safety at Work
No
Supporting protocol for DeviceNet Safety
No
Supporting protocol for INTERBUS-Safety
No
Supporting protocol for PROFIsafe
No
Supporting protocol for SafetyBUS p
No
Supporting protocol for other bus systems
Yes
Radio standard Bluetooth
No
Radio standard WLAN 802.11
No
Radio standard GPRS
No
Radio standard GSM
No
Radio standard UMTS
No
IO link master
No
System accessory
Yes
Redundancy
Yes
With display
No
Type of memory
RAM
Memory size
512000 kByte
Additional program memory possible
Yes
Rail mounting possible
Yes
Wall mounting/direct mounting
No
Front build in possible
No
Rack-assembly possible
No
Suitable for safety functions
No
Category according to EN 954-1
SIL according to IEC 61508
None
Performance level acc. EN ISO 13849-1
None
Appendant operation agent (Ex ia)
No
Appendant operation agent (Ex ib)
No
Explosion safety category for gas
None
Explosion safety category for dust
None
Width
51 mm
Height
110 mm
Depth
81 mm

Approvals

North America Certification
Request filed for cULus
Specially designed for North America
No
Current Limiting Circuit-Breaker
No

Dimensions

2723DIM-87
2723DRW-321
108.7 mm (4.28") x 54.3 mm (2.13") x 80.3 mm (3.16")