189896 PKZM0-0,4-EA
Motor-protective circuit-breaker, 3p, Ir=0.25-0.4A, screw connection
Motor-protective circuit-breaker conforming to IEC/EN 60947, 3-pole PKZM0 frame size, with adjustable overload release and non-delayed short-circuit release, phase failure-sensitive, screw and snap fitting, with screw terminals, cap installation dimension of 45 mm, rated operating voltage Ue of 690 V, IP20 degree of protection, finger-safe as per VDE 0106 Part 100, available accessories: auxiliary contact module, voltage release, contact module, clip plate
General specifications
Product name
Eaton Moeller® series PKZM0 Motor-protective circuit-breaker
Part no.
PKZM0-0,4-EA
EAN
4015081878925
Product Length/Depth
76 millimetre
Product height
93 millimetre
Product width
45 millimetre
Product weight
0.243 kilogram
Compliances
CE Marked
RoHS conform
RoHS conform
Product Tradename
PKZM0
Product Type
Motor-protective circuit-breaker
Product Sub Type
None
Features & Functions
Actuator type
Turn button
Features
Phase-failure sensitivity (according to IEC/EN 60947-4-1, VDE 0660 Part 102)
Functions
Motor protection
Phase failure sensitive
Phase failure sensitive
Number of poles
Three-pole
General information
Connection
Screw terminals
Degree of protection
IP20
Lifespan, electrical
100,000 operations
Lifespan, mechanical
100,000 Operations
Mounting position
Can be snapped on to IEC/EN 60715 top-hat rail with 7.5 or 15 mm height.
Operating frequency
40 Operations/h
Overvoltage category
III
Pollution degree
3
Product category
Motor protective circuit breaker
Protection
Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
Rated impulse withstand voltage (Uimp)
6000 V AC
Shock resistance
25 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
Suitable for
Also motors with efficiency class IE3
Branch circuit: Suitable for group installations, (UL/CSA)
Branch circuit: Suitable for group installations, (UL/CSA)
Temperature compensation
≤ 0.25 %/K, residual error for T > 40°
-25 - 55 °C, Operating range
-5 - 40 °C to IEC/EN 60947, VDE 0660
-25 - 55 °C, Operating range
-5 - 40 °C to IEC/EN 60947, VDE 0660
Climatic environmental conditions
Altitude
Max. 2000 m
Ambient operating temperature (enclosed) - min
-25 °C
Ambient storage temperature - min
-40 °C
Ambient storage temperature - max
80 °C
Climatic proofing
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, cyclic, to IEC 60068-2-30
Terminal capacities
Terminal capacity (flexible with ferrule)
1 x (1 - 6) mm², ferrule to DIN 46228
2 x (1 - 6) mm², ferrule to DIN 46228
2 x (1 - 6) mm², ferrule to DIN 46228
Terminal capacity (solid)
2 x (1 - 6) mm²
1 x (1 - 6) mm²
1 x (1 - 6) mm²
Terminal capacity (solid/stranded AWG)
18 - 10
Stripping length (main cable)
10 mm
Tightening torque
1.7 Nm, Screw terminals, Main cable
Electrical rating
Rated frequency - min
50 Hz
Rated frequency - max
60 Hz
Rated operational current (Ie)
0.4 A
Rated operational power at AC-3, 220/230 V, 50 Hz
0.06 kW
Rated operational power at AC-3, 380/400 V, 50 Hz
0.09 kW
Rated operational power at AC-3, 440 V, 50 Hz
0.12 kW
Rated operational power at AC-3, 500 V, 50 Hz
0.12 kW
Rated operational power at AC-3, 690 V, 50 Hz
0.18 kW
Rated operational voltage (Ue) - min
690 V
Rated operational voltage (Ue) - max
690 V
Rated uninterrupted current (Iu)
0.4 A
Short-circuit rating
Rated short-circuit breaking capacity Icu at 400 V AC
150 kA
Rated short-circuit breaking capacity Ics at 400 V AC
150 kA
Rated short-circuit breaking capacity Icu at 440 V AC
150 kA
Rated short-circuit breaking capacity Ics at 440 V AC
150 kA
Rated short-circuit breaking capacity Icu at 500 V AC
150 kA
Rated short-circuit breaking capacity Ics at 500 V AC
150 kA
Rated short-circuit breaking capacity Icu at 690 V AC
150 kA
Rated short-circuit breaking capacity Ics at 690 V AC
150 kA
Short-circuit current rating (group protection)
50 kA, 600 V High Fault, CB, SCCR (UL/CSA) with 600 A, 600 V High Fault, CB, SCCR (UL/CSA)
50 kA, 600 V High Fault, Fuse, SCCR (UL/CSA) with 600 A, 600 V High Fault, Fuse, SCCR (UL/CSA)
50 kA, 600 V High Fault, Fuse, SCCR (UL/CSA) with 600 A, 600 V High Fault, Fuse, SCCR (UL/CSA)
Short-circuit release
Basic device fixed 15.5 x Iu, Trip Blocks
6.2 A, Irm, Setting range max.
± 20% tolerance, Trip blocks
6.2 A, Irm, Setting range max.
± 20% tolerance, Trip blocks
Switching capacity
Switching capacity
0.4 A, AC-3 up to 690 V
Trip blocks
Overload release current setting - min
0.25 A
Overload release current setting - max
0.4 A
Design verification
Equipment heat dissipation, current-dependent Pvid
5.22 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
1.7 W
Rated operational current for specified heat dissipation (In)
0.4 A
Static heat dissipation, non-current-dependent Pvs
0 W
Technical data ETIM 9.0
Low-voltage industrial components (EG000017) / Motor protection circuit-breaker (EC000074)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Circuit breaker (LV < 1 kV) / Motor protection circuit-breaker (ecl@ss13-27-37-04-01 [AGZ529021])
Overload release current setting
0.25 - 0.4 A
Adjustment range undelayed short-circuit release
6.2 - 6.2 A
With thermal overload protection
No
Phase failure sensitive
Yes
Switch off technique
Thermomagnetic
Rated operating voltage
690 - 690 V
Rated permanent current Iu
0.4 A
Rated operation power at AC-3, 230 V
0.06 kW
Rated operation power at AC-3, 400 V
0.09 kW
Power loss
5.22 W
Type of electrical connection of main circuit
Screw connection
Type of control element
Turn button
Device construction
Built-in device fixed built-in technique
With integrated auxiliary switch
No
With integrated under voltage release
No
Number of poles
3
Rated short-circuit breaking capacity lcu at 400 V, AC
150 kA
Degree of protection (IP)
IP20
Height
93 mm
Width
45 mm
Depth
76 mm
-