General specifications
Product name
Eaton Moeller® series EMR6 Phase sequence relay
Part no.
EMR6-F500-G-1
EAN
4015081788255
Product Length/Depth
103.7 millimetre
Product height
85.6 millimetre
Product width
22.5 millimetre
Product weight
0.16 kilogram
Certifications
IEC/EN 60255-6
Product Tradename
EMR6
Product Type
Phase sequence relay
Product Sub Type
None
Features & Functions
Electric connection type
Screw connection
Features
Fixed response delay
Functions
Monitoring of three-phase networks
Phase failure detection
Monitoring function
Phase sequence
Phase sequence monitoring
Phase failure
Voltage measurement - min
200 V
Voltage measurement - max
500 V
General information
Degree of protection
Terminals: IP20
Enclosure: IP50
Lifespan, mechanical
30,000,000 Operations
Mounting position
As required
Overvoltage category
III
Pollution degree
3
Product category
EMR Measuring and monitoring relays
Rated impulse withstand voltage (Uimp)
4000 V AC
Shock resistance
Class 2
LED indicator
Status indication of Phase sequence fault: Red, flashing light
Status indication of Phase failure: Red, solid light
Status indication of energized output relay: Yellow LED
Type
Phase sequence relay
Voltage type
AC
Climatic environmental conditions
Ambient operating temperature - min
-20 °C
Ambient operating temperature - max
60 °C
Ambient storage temperature - min
-40 °C
Ambient storage temperature - max
85 °C
Climatic proofing
Damp heat, cyclic, to IEC 60068-2-30
Electro magnetic compatibility
Air discharge
Air/contact discharge, according to IEC/EN 61000-4-2, level 3
Burst impulse
According to IEC/EN 61000-4-4, level 3
Electromagnetic compatibility
According to IEC/EN 60947-6-2
Immunity to line-conducted interference
Level 3 (according to IEC/EN 61000-4-6)
Immunity to radiation
Level 3 (according to IEC/EN 61000-4-3)
Surge rating
According to IEC/EN 61000-4-5 Level 4
Terminal capacities
Connection type
Snap fixing, top-hat rail IEC/EN 60715
Terminal capacity
2 x 2.5 mm², (2 x 14 AWG), flexible with ferrule
2 x 2.5 mm², solid
Screwdriver size
5.5 x 0.8 mm, Terminal screw
Tightening torque
0.8 Nm, Screw terminals
Min. 0.5 Nm, Screw terminals
Timing cycle
Timing cycle
0.5 % Error within supply voltage (Measuring circuits)
Power supply
Duty factor
100 %, Power supply
Power consumption
11 VA
Rated control supply voltage (Us) at AC, 50 Hz - min
200 V
Rated control supply voltage (Us) at AC, 50 Hz - max
500 V
Rated control supply voltage (Us) at AC, 60 Hz - min
200 V
Rated control supply voltage (Us) at AC, 60 Hz - max
500 V
Rated control supply voltage (Us) at DC - min
0 V
Rated control supply voltage (Us) at DC - max
0 V
Rated frequency - min
50 Hz
Rated frequency - max
60 Hz
Supply voltage
200 - 500 V AC, 50/60 Hz
Voltage tolerance
1.1 x Uc
0.85 x Uc
Measuring circuits
Measuring cycle
500 ms
Monitoring voltage
200 - 500 V AC
200 - 500 V AC, 50/60 Hz (per phase)
Temperature error
0.06 %/°C, Measuring circuits
Relay output contacts
Number of contacts (change-over contacts)
2
Number of contacts (normally closed contacts)
0
Number of contacts (normally open contacts)
0
Lifespan, electrical
300,000 Operation (at 230 V, AC-12, 4 A)
Rated operational current (Ie)
3 A at AC-15, 230 V
4 A at DC-12, 24 V
4 A at AC-12, 230 V
2 A at DC-13, 24 V
Rated operational voltage (Ue) at AC - max
250 V
Short-circuit protection rating
Max. 10 A Fast/gL, Fuse, Relay output contacts

Technical data ETIM 9.0

Relays (EG000019) / Phase monitoring relay (EC001441)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Monitoring equipment (low-voltage switch technology) / Asymmetry monitoring equipment (ecl@ss13-27-37-18-03 [AKF097019])
Type of electric connection
Screw connection
With detachable clamps
No
External power supply required
No
Voltage type (supply voltage)
AC
Supply voltage AC 50 Hz
200 - 500 V
Supply voltage AC 60 Hz
200 - 500 V
Supply voltage DC
V
Phase sequence monitoring
Yes
Phase failure detection
Yes
Function under voltage detection
No
Function over voltage detection
No
Phase imbalance monitoring
No
Voltage measuring range
200 - 500 V
Min. adjustable delay-on energization time
0 s
Max. permitted delay-on energization time
0 s
Min. adjustable off-delay time
0 s
Max. permitted off-delay time
0 s
Number of contacts as normally closed contact
0
Number of contacts as normally open contact
0
Number of contacts as change-over contact
2
Voltage type (operating voltage)
AC
Operating voltage AC 50 Hz
200 - 500 V
Operating voltage AC 60 Hz
200 - 500 V
Operating voltage DC
V
Rated switch current
4 A
Width
22.5 mm
Height
85.6 mm
Depth
103.7 mm