179647 XV-303-70-B00-A00-1B

General specifications
Product name
Eaton XV-303 Touch panel
Part no.
XV-303-70-B00-A00-1B
EAN
7640130098589
Product Length/Depth
196 millimetre
Product height
51 millimetre
Product width
135 millimetre
Product weight
0.78 kilogram
Certifications
CE
DNV GL
Certified by UL for use in Canada
EMC according to 2014/30/EU
UL 61010-2-201
CUL
IEC/EN 61131-2
EN 50178
UL
UL File No.: E205091
Product Tradename
XV-303
Product Type
Touch panel
Product Sub Type
None
Features & Functions
Enclosure material
Insulated material
Features
RS232
USB device
Integrated Runtime visualization software license
Fanless CPU and system cooling, natural convection-based passive cooling
RS485
CAN
Target and web visualization
Portrait format
Slot for SD card
Operating System Windows Embedded Compact 7 pro
USB Host
Ethernet interface
Fitted with:
Printer output
1 x RS485 (built-in interface)
1 x RS232 (built-in interface)
Message indication
SW interfaces
1 x USB host 2.0 (built-in interface)
Recipes
Message system (incl. buffer and confirmation)
1 x CANopen®/easyNet (built-in interfaces)
1 x Ethernet 10/100 Mbps (built-in interfaces)
1 x USB device (built-in interface)
Color display
Functions
Process default value (input) possible
Process value representation (output) possible
Additional software components, loadable
General information
Battery runtime
Back-up of real-time clock: BR 2330, non-replaceable (soldered)
Degree of protection
NEMA 4X
NEMA 12
IP20, rear (according to EN 60529-1)
Degree of protection (front side)
NEMA 12
IP65
Fuse type
Built-in fuse (not accessible)
Lifespan
50,000 h (Service life of back-lighting)
Model
Plastic enclosure and glass panel in plastic frame
Mounting method
Flush mounting - Clearance: Width x Height x Depth ≥ 30 mm (1.18")
Flush mounting
Flush mounting - Inclination from vertical: ±45° (if using natural convection)
Potential isolation
Power supply: no
Protection against polarity reversal
Yes, for supply voltage (Siemens MPI optional)
Product category
HMI-PLC (SPS function, retrofittable)
RoHs conformity
Yes
Software
XSOFT-CODESYS, Visualization software, Engineering
GALILEO, Visualization software, Engineering
XSOFT-CODESYS-2, PLC-Programming software, Engineering
XSOFT-CODESYS-3, PLC-Programming software, Engineering
Type
Control panel
Voltage type
DC
Ambient conditions, mechanical
Shock resistance
15 g, 11 ms, Mechanical
Vibration resistance
According to IEC/EN 60068-2-6
9 - 60 Hz, ± 0.15 mm
60 - 150 Hz, ± 2 g
5 - 9 Hz, ± 3.5 mm
Climatic environmental conditions
Air pressure
795 - 1080 hPa (operation)
Ambient operating temperature - min
0 °C
Ambient operating temperature - max
50 °C
Ambient storage temperature - min
-20 °C
Ambient storage temperature - max
60 °C
Climatic proofing
Cold to EN 60068-2-1
Damp heat, constant, to IEC 60068-2-3
Dry heat to IEC 60068-2-2
Environmental conditions
Condensation: Non-condensing
Operating temperature - min
0 °C
Operating temperature - max
50 °C
Relative humidity
10 - 95 % (non-condensing)
Electro magnetic compatibility
Emitted interference
According to IEC/EN 61000-6-4
Interference immunity
According to EN 61000-6-2
Voltage dips
5 ms from undervoltage (19.2 V DC)
≤ 10 ms from rated voltage (24 V DC)
Electrical rating
Permissible voltage
35 V DC (for a duration of < 100 ms)
19.2 - 30 V DC, effective (rated operating voltage -20 %/+25 %)
18.0 - 31.2 V DC, absolute with ripple
18 - 31.2 V DC, battery powered (rated operating voltage -25 %/+30 %)
Power consumption
11.9 W
14 W typ.
Max. 14.4 W
Rated operational voltage
24 V DC (power-supply - safety extra low voltage)
Supply voltage at AC, 50 Hz - min
0 V AC
Supply voltage at AC, 50 Hz - max
0 V AC
Supply voltage at DC - min
19.2 V DC
Supply voltage at DC - max
30 V DC
Communication
Interfaces
10/100 Mbps Ethernet connection
CAN (not galvanically isolated, 9-pin SUB-D plug, UNC)
RS232 (not galvanically isolated, 9-pin SUB-D plug, UNC)
USB 2.0 host (not galvanically isolated)
RS485 (not galvanically isolated, 9-pin SUB-D plug, UNC)
USB 2.0 device (not galvanically isolated)
Number of slots
1 (for SD-Card)
Protocol
EtherCAT
CAN
MODBUS
EtherNet/IP
TCP/IP
Display
Display contrast ratio
850:1
Display lighting
LED
Dimmable via software
Display size
153.6 x 90.0 mm
16:9
Display type
TFT
Anti-glare tempered glass in plastic bezel
Color display, TFT, anti-glare
Luminance intensity
400 cd/m²
Number of colors of the display
16777216
Resolution
WSVGA
1024 x 600 px
Screen size (diagonal)
7 in
Touch technology
Projected Capacitive Touch (PCT)
Multi-touch touch panel touch sensor
Capacitive multitouch
System
Backup time
10 years, typ. (time at zero voltage)
Memory
SD card, Type: SDSC, SDHC (external memory)
DRAM: 512 MByte RAM
NVRAM: 128kByte Retain
Flash: 1 GByte SLC
Memory capacity
512,000 kByte
Operating system
Windows Embedded Compact 7 Pro
Processor
ARM Cortex-A9 800 MHz
Design verification
Equipment heat dissipation, current-dependent Pvid
14.4 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
0 A
Static heat dissipation, non-current-dependent Pvs
14.4 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Please enquire
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Meets the product standard's requirements.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 9.0

Programmable logic controllers PLC (EG000024) / Graphic panel (EC001412)
Electric engineering, automation, process control engineering / Display and control component / Panel (HMI) / Graphic panel (HMI) (ecl@ss13-27-33-02-01 [AFX016008])
Supply voltage AC 50 Hz
0 - 0 V
Supply voltage AC 60 Hz
0 - 0 V
Supply voltage DC
19.2 - 30 V
Voltage type (supply voltage)
DC
Power consumption
14.4 W
Number of HW-interfaces industrial Ethernet
1
Number of interfaces PROFINET
0
Number of HW-interfaces RS-232
1
Number of HW-interfaces RS-422
0
Number of HW-interfaces RS-485
1
Number of HW-interfaces serial TTY
0
Number of HW-interfaces USB
2
Number of HW-interfaces parallel
0
Number of HW-interfaces wireless
0
Number of HW-interfaces other
1
With SW interfaces
Yes
Supporting protocol for EtherCAT
Yes
Supporting protocol for TCP/IP
Yes
Supporting protocol for PROFIBUS
No
Supporting protocol for CAN
Yes
Supporting protocol for INTERBUS
No
Supporting protocol for ASI
No
Supporting protocol for KNX
No
Supporting protocol for Modbus
Yes
Supporting protocol for Data-Highway
No
Supporting protocol for DeviceNet
No
Supporting protocol for SUCONET
No
Supporting protocol for LON
No
Supporting protocol for PROFINET IO
No
Supporting protocol for PROFINET CBA
No
Supporting protocol for SERCOS
No
Supporting protocol for Foundation Fieldbus
No
Supporting protocol for EtherNet/IP
Yes
Supporting protocol for AS-Interface Safety at Work
No
Supporting protocol for DeviceNet Safety
No
Supporting protocol for INTERBUS-Safety
No
Supporting protocol for PROFIsafe
No
Supporting protocol for SafetyBUS p
No
Supporting protocol for other bus systems
No
Radio standard Bluetooth
No
Radio standard WLAN 802.11
No
Radio standard GPRS
No
Radio standard GSM
No
Radio standard UMTS
No
IO link master
No
Type of display
TFT
Colour display
Yes
Number of colours of the display
16777216
Number of grey-scales/blue-scales of display
0
Screen diagonal
7 inch
Number of pixels, horizontal
1024
Number of pixels, vertical
600
Useful project memory/user memory
512000 kByte
With numeric keyboard
No
With alpha numeric keyboard
No
Number of function buttons, programmable
0
Number of buttons with LED
0
Number of system buttons
1
Touch technology
Capacitive multitouch
With message indication
Yes
With message system (incl. buffer and confirmation)
Yes
Process value representation (output) possible
Yes
Process default value (input) possible
Yes
With recipes
Yes
Number of password levels
200
With printer output
Yes
Number of online languages
100
Additional software components, loadable
Yes
Degree of protection (IP), front side
IP65
Degree of protection (NEMA), front side
12
Certified for UL hazardous location class I
No
Certified for UL hazardous location class II
No
Certified for UL hazardous location class III
No
Certified for UL hazardous location division 1
No
Certified for UL hazardous location division 2
No
Certified for UL hazardous location group A (acetylene)
No
Certified for UL hazardous location group B (hydrogen)
No
Certified for UL hazardous location group C (ethylene)
No
Certified for UL hazardous location group D (propane)
No
Certified for UL hazardous location group E (metal dusts)
No
Certified for UL hazardous location group F (carbonaceous dusts)
No
Certified for UL hazardous location group G (non-conductive dusts)
No
Operating temperature
0 - 50 °C
Rail mounting possible
No
Wall mounting/direct mounting
No
Suitable for safety functions
No
Width of the front
196 mm
Height of the front
135 mm
Built-in depth
43.1 mm