Datasheet - DE1-34016FN-N20N

German
English
French
Dutch
Italian
Polish
Czech
Russian
Norwegian Bokmål
English

 
Variable speed starter, Rated operational voltage 400 V AC, 3-phase, Ie 16 A, 7.5 kW, 10 HP, Radio interference suppression filter
Part no.  DE1-34016FN-N20N
Catalog No.  174340
Eaton Catalog No.  DE1-34016FN-N20N
EL-Nummer (Norway)  4110104

Delivery program
Product range
    Variable speed starter
Part group reference (e.g. DIL)
    DE1
Rated operational voltage
Ue   400 V AC, 3-phase
480 V AC, 3-phase
Output voltage with Ve
U2   400 V AC, 3-phase
480 V AC, 3-phase
Mains voltage (50/60Hz)
ULN V 380 (-10%) - 480 (+10%)
Rated operational current
     
At 150% overload
Ie A 16
Note
    Rated operational current at an operating frequency of 16 kHz and an ambient air temperature of +50 °C
Note
    Overload cycle for 60 s every 600 s
Assigned motor rating
     
Note
    for normal internally and externally ventilated 4 pole, three-phase asynchronous motors with 1500 rpm-1 at 50 Hz or 1800 min-1 at 60 Hz
Note
    Overload cycle for 60 s every 600 s
Note
    at 400 V, 50 Hz
150 % Overload
P kW 7.5
150 % Overload
IM A 15.2
Note
    at 440 - 480 V, 60 Hz
150 % Overload
P HP 10
150 % Overload
IM A 14
Degree of Protection
    IP20/NEMA 0
Interface/field bus (built-in)
    OP-Bus (RS485)/Modbus RTU
Fitted with
    Radio interference suppression filter
Frame size
    FS2
Connection to SmartWire-DT
    yes
in conjunction with DX-NET-SWD3 SmartWire DT module
Technical data
General
Standards
    Specification for general requirements: IEC/EN 61800-2
EMC requirements: IEC/EN 61800-3
Safety requirements: IEC/EN 61800-5-1
Certifications
    CE, UL, cUL, RCM
Production quality
    RoHS, ISO 9001
Climatic proofing
ρw % < 95%, average relative humidity (RH), non-condensing, non-corrosive
Ambient temperature
     
operation (150 % overload)
ϑ °C -10 - +50
 
    Derating between 50 °C and 60 °C:
None if fPWM ≦ 14 kHz up to a max. of 50 °C
None if fPWM ≦ 16 kHz up to a max. of 46 °C
None if Ie ≦ 14.9 A and fPWM ≦ 10 kHz
None if Ie ≦ 10.6 A and fPWM ≦ 20 kHz
Storage
ϑ °C -40 - +70
Radio interference level
     
Radio interference class (EMC)
    C2, C3, depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
Environment (EMC)
    1st and 2nd environments as per EN 61800-3
maximum motor cable length
I m C2 ≤ 10 m
C3 ≤ 25 m
Mechanical shock resistance
  g 15 (11 m/s, EN 60068-2-27)
Vibration
    EN 61800-5-1
Altitude
  m 0 - 1000 m above sea level
Above 1000 m: 1% derating for every 100 m
max. 2000 m
Degree of Protection
    IP20/NEMA 0
Protection against direct contact
    BGV A3 (VBG4, finger- and back-of-hand proof)
Main circuit
Supply
     
Rated operational voltage
Ue   400 V AC, 3-phase
480 V AC, 3-phase
Mains voltage (50/60Hz)
ULN V 380 (-10%) - 480 (+10%)
Input current (150% overload)
ILN A 16.5
Supply frequency
fLN Hz 50/60
Frequency range
fLN Hz 45 - 66
Mains switch-on frequency
    Maximum of one time every 30 seconds
Power section
     
Overload current (150% overload)
IL A 24
max. starting current (High Overload)
IH % 200
Note about max. starting current
    for 1.875 seconds every 600 seconds
Output voltage with Ve
U2   400 V AC, 3-phase
480 V AC, 3-phase
Output Frequency
f2 Hz 0 - 50/60 (max. 300)
Switching frequency
fPWM kHz 16
adjustable 4 - 32 (audible)
Operation Mode
    U/f control
Speed control with slip compensation
Frequency resolution (setpoint value)
Δf Hz 0.025
Rated operational current
     
At 150% overload
Ie A 16
Note
    Rated operational current at an operating frequency of 16 kHz and an ambient air temperature of +50 °C
Maximum leakage current to ground (PE) without motor
IPE mA < 3.5 AC, < 10 DC
Fitted with
    Radio interference suppression filter
Frame size
    FS2
Motor feeder
     
Note
    for normal internally and externally ventilated 4 pole, three-phase asynchronous motors with 1500 rpm-1 at 50 Hz or 1800 min-1 at 60 Hz
Note
    Overload cycle for 60 s every 600 s
Note
    at 400 V, 50 Hz
150 % Overload
P kW 7.5
Note
    at 440 - 480 V, 60 Hz
150 % Overload
P HP 10
Apparent power
     
Apparent power at rated operation 400 V
S kVA 11.09
Apparent power at rated operation 480 V
S kVA 13.3
Braking function
     
Standard braking torque
    max. 30 % MN
DC braking torque
    adjustable to 100 %
Control section
Reference voltage
Us V 10 V DC (max. 0.2 mA)
Analog inputs
    1, parameterizable, 0 - 10 V DC, 0/4 - 20 mA
Digital inputs
    4, parameterizable, 10 - 30 V DC
Relay outputs
    1, parameterizable, N/O, 6 A (250 V, AC-1) / 5 A (30 V, DC-1)
Interface/field bus (built-in)
    OP-Bus (RS485)/Modbus RTU
Assigned switching and protective elements
Power Wiring
     
Safety device (fuse or miniature circuit-breaker)
     
IEC (Type B, gG), 150 %
    FAZ-B25/3
UL (Class CC or J)
  A 25
Mains contactor
     
150 % overload (CT/IH, at 50 °C)
    DILEM-…
110 % overload (VT/IL, at 40 °C)
    DILM7-…
Main choke
     
150 % overload (CT/IH, at 50 °C)
    DX-LN3-024
Motor feeder
     
motor choke
     
150 % overload (CT/IH, at 50 °C)
    DX-LM3-016
Design verification as per IEC/EN 61439(Show features)(Hide features)
Technical data ETIM 6.0(Show features)(Hide features)
Approvals
Product Standards     UL 508C; CSA-C22.2 No. 14; IEC/EN61800-3; IEC/EN61800-5; CE marking
UL File No.     E172143
UL Category Control No.     NMMS, NMMS7
CSA File No.     UL report applies to both US and Canada
North America Certification     UL listed, certified by UL for use in Canada
Specially designed for North America     No
Suitable for     Branch circuits
Max. Voltage Rating     3~ 480 V AC IEC: TN-S UL/CSA: "Y" (Solidly Grounded Wey)
Degree of Protection     IEC: IP20
Dimensions