Datasheet - DS7-34DSX007N0-D

German
English
French
Dutch
Italian
Polish
Czech
Russian
Norwegian Bokmål
English

 
Soft starter, 7 A, 200 - 480 V AC, 24 V DC, Frame size: FS1, Communication Interfaces: SmartWire-DT
Part no.  DS7-34DSX007N0-D
Catalog No.  134945
Eaton Catalog No.  DS7-34DSX007N0-D
EL-Nummer (Norway)  0004137333

Delivery program
Product range
    SmartWire-DT slave
Subrange
    SmartWire-DT Soft starters
Description
    With internal bypass contacts
Function
    Soft starters for three-phase loads
Mains supply voltage (50/60 Hz)
ULN V AC 200 - 480
Supply voltage
Us   24 V DC
Control voltage
UC   24 V DC
Assigned motor rating (Standard connection, In-Line)
     
at 400 V, 50 Hz
P kW 3
at 460 V, 60 Hz
P HP 5
Rated operational current
     
AC-53
Ie A 7
Rated operational voltage
Ue   200 V
230 V
400 V
480 V
Connection to SmartWire-DT
    yes
Frame size
    FS1
Technical data
General
Standards
    IEC/EN 60947-4-2
UL 508
CSA22.2-14
Approvals
    CE
Approvals
    UL
CSA
C-Tick
UkrSEPRO
Climatic proofing
    Damp heat, constant, to IEC 60068-2-3
Damp heat, cyclic, to IEC 60068-2-10
Ambient temperature
     
Operation
ϑ °C -5 - +40
up to 60 at 2% derating per Kelvin temperature rise
Storage
ϑ °C -25 - +60
Altitude
  m 0 - 1000 m, above that 1 % derating per 100 m , up to 2000 m
Mounting position
    Vertical
Degree of protection
     
Degree of Protection
    IP20
Protection against direct contact
    Finger- and back-of-hand proof
Overvoltage category/pollution degree
    II/2
Shock resistance
    8 g/11 ms
Vibration resistance to EN 60721-3-2
    2M2
Radio interference level (IEC/EN 55011)
    B
Static heat dissipation, non-current-dependent
Pvs W 0.35
Weight
  kg 0.41
Main conducting paths
Rated operating voltage
Ue V AC 200 - 480
Supply frequency
fLN Hz 50/60
Rated operational current
Ie A  
AC-53
Ie A 7
Assigned motor rating (Standard connection, In-Line)
     
at 230 V, 50 Hz
P kW 1.5
at 400 V, 50 Hz
P kW 3
at 200 V, 60 Hz
P HP 2
at 230 V, 60 Hz
P HP 2
at 460 V, 60 Hz
P HP 5
Overload cycle to IEC/EN 60947-4-2
     
AC-53a
    7 A: AC-53a: 3 - 5: 75 - 10
Internal bypass contacts
   
Short-circuit rating
     
Type “1” coordination
    PKM0-10 (+ CL-PKZ0)
Type „2“ coordination (additional with the fuses for coordination type „1“)
    3 x 170M1361
 
     
Fuse base (number x part no.)
    3 x 170H1007
Terminal capacities
Cable lengths
     
Solid
  mm2 1 x (0.75 - 4)
2 x (0.75 - 2.5)
Flexible with ferrule
  mm2 1 x (0.75 - 2.5)
2 x (0.75 - 2.5)
Solid or stranded
  AWG 18 - 10
Tightening torque
  Nm 1.2
Screwdriver (PZ: Pozidriv)
  mm PZ2; 1 x 6 mm
Control cables
     
Solid
  mm2 1 x (0.75 - 4)
2 x (0.75 - 2.5)
Flexible with ferrule
  mm2 1 x (0.75 - 2.5)
2 x (0.75 - 2.5)
Solid or stranded
  AWG 18 - 10
Tightening torque
  Nm 1.2
Screwdriver
  mm 0,8 x 5,5

1 x 6
Control circuit
Digital inputs
     
Control voltage
     
DC-operated
  V DC 24 V DC +10 %/- 15 % oder über SWD
Current consumption 24 V
  mA  
External 24 V
  mA 1.6
Pick-up voltage
  x Us  
DC-operated
  V DC 17.3 - 27
Drop-out voltage
x Us    
DC operated
  V DC 0 - 3
Pick-up time
     
DC operated
  ms 250
Drop-out time
     
DC operated
  ms 350
Regulator supply
     
Voltage
Us V 24 V DC +10 %/- 15 %
Current consumption
Ie mA 50
Notes
    External supply voltage
Relay outputs
     
Number
    1 (TOR)
Voltage range
  V AC = Us
AC-11 current range
  A 1 A, AC-11
Soft start function
Ramp times
     
Acceleration
  s 1 - 30
Deceleration
  s 0 - 30
Start voltage (= turn-off voltage)
  % 30   100
Start pedestal
  % 30 - 100
Current limitation
    (0 - 8) x Ie
Fields of application
     
Fields of application
    Soft starting of three-phase asynchronous motors
1-phase motors
   
3-phase motors
   
Functions
Fast switching (semiconductor contactor)
    - (minimum ramp time 1s)
Soft start function
   
Reversing starter
    External solution required
Suppression of closing transients
   
Current limitation
    ●, with PKE
Fault memory
  Faults 8
Suppression of DC components for motors
   
Potential isolation between power and control sections
   
 
     
Communication Interfaces
    SmartWire-DT
Notes


Rated impulse withstand voltage:

  • 1.2 µs/50 µs (rise time/fall time of the pulse to IEC/EN 60947‐2 or ‐3)
  • Applies for control circuit/power section/enclosure
Design verification as per IEC/EN 61439(Show features)(Hide features)
Technical data ETIM 7.0(Show features)(Hide features)
Approvals
Product Standards     IEC/EN 60947-4-2; GB 14048.6; UL 508; CSA-C22.2 No 0-M91; CSA-C22.2 No 14-05 CE marking
Specially designed for North America     No
Suitable for     Branch circuits
Current Limiting Circuit-Breaker     No
Max. Voltage Rating     480 V
Degree of Protection     IP20; UL/CSA Type 1
Dimensions