Datasheet - DS7-340SX100N0-N

German
English
French
Dutch
Italian
Polish
Czech
Russian
Norwegian Bokmål
English

 
Soft starter, 100 A, 200 - 480 V AC, Us= 24 V AC/DC, Frame size FS3
Part no.  DS7-340SX100N0-N
Catalog No.  134920
Eaton Catalog No.  DS7-340SX100N0-N
EL-Nummer (Norway)  0004134205

Delivery program
Description
    With internal bypass contacts
Function
    Soft starters for three-phase loads
Mains supply voltage (50/60 Hz)
ULN V AC 200 - 480
Supply voltage
Us   24 V AC/DC
Control voltage
UC   24 V AC
24 V DC
Assigned motor rating (Standard connection, In-Line)
     
at 400 V, 50 Hz
P kW 55
at 460 V, 60 Hz
P HP 75
Rated operational current
     
AC-53
Ie A 100
Rated operational voltage
Ue   200 V
230 V
400 V
480 V
Connection to SmartWire-DT
    no
Frame size
    FS3
Technical data
General
Standards
    IEC/EN 60947-4-2
UL 508
CSA22.2-14
Approvals
    CE
Approvals
    UL
CSA
C-Tick
UkrSEPRO
Climatic proofing
    Damp heat, constant, to IEC 60068-2-3
Damp heat, cyclic, to IEC 60068-2-10
Ambient temperature
     
Operation
ϑ °C -5 - +40
up to 60 at 2% derating per Kelvin temperature rise
Storage
ϑ °C -25 - +60
Altitude
  m 0 - 1000 m, above that 1 % derating per 100 m , up to 2000 m
Mounting position
    Vertical
Degree of protection
     
Degree of Protection
    IP20 (terminals IP00)
Integrated
    Protection type IP40 can be achieved on all sides with covers from the NZM range.
Protection against direct contact
    Finger- and back-of-hand proof
Overvoltage category/pollution degree
    II/2
Shock resistance
    8 g/11 ms
Vibration resistance to EN 60721-3-2
    2M2
Radio interference level (IEC/EN 55011)
    B
Static heat dissipation, non-current-dependent
Pvs W 25
Weight
  kg 1.8
Main conducting paths
Rated operating voltage
Ue V AC 200 - 480
Supply frequency
fLN Hz 50/60
Rated operational current
Ie A  
AC-53
Ie A 100
Assigned motor rating (Standard connection, In-Line)
     
at 230 V, 50 Hz
P kW 30
at 400 V, 50 Hz
P kW 55
at 200 V, 60 Hz
P HP 30
at 230 V, 60 Hz
P HP 30
at 460 V, 60 Hz
P HP 75
Overload cycle to IEC/EN 60947-4-2
     
AC-53a
    100 A: AC-53a: 3 - 5: 75 - 10
Internal bypass contacts
   
Short-circuit rating
     
Type “1” coordination
    NZMN1-M100
Type „2“ coordination (additional with the fuses for coordination type „1“)
    3 x 170M4008
 
     
Fuse base (number x part no.)
    3 x 170H3004
Terminal capacities
Cable lengths
     
Solid
  mm2 1 x (25 - 70)
2 x (6 - 25)
Stranded
  mm2 1 x (25 - 70)
2 x (6 - 25)
Solid or stranded
  AWG 1 x (12 - 2/0)
Copper band
  MM 2 x 9 x 0.8   9 x 9 x 0.8
Tightening torque
  Nm 6 (≤ 10 mm²); 9 (> 10 mm²)
Screwdriver (PZ: Pozidriv)
  mm PZ2; 1 x 6 mm
Control cables
     
Solid
  mm2 1 x (0.5 - 2.5)
2 x (0.5 - 1.0)
Flexible with ferrule
  mm2 1 x (0.5 - 1.5)
2 x (0.5 - 0.75)
Stranded
  mm2 1 x (0.5 - 1.5)
2 x (0.5 - 1.0)
Solid or stranded
  AWG 1 x (21 - 14)
2 x (21 - 18)
Tightening torque
  Nm 0.4
Screwdriver
  mm 0,6 x 3,5
Control circuit
Digital inputs
     
Control voltage
     
DC-operated
  V DC 24 V DC +10 %/- 15 %
AC operated
  V AC 24 V AC +10 %/- 15 %
Current consumption 24 V
  mA  
External 24 V
  mA 1.6
Pick-up voltage
  x Us  
DC-operated
  V DC 17.3 - 27
AC operated
  V AC 17.3 - 27
Drop-out voltage
x Us    
DC operated
  V DC 0 - 3
AC operated
  V AC 0 - 3
Pick-up time
     
DC operated
  ms 250
AC operated
  ms 250
Drop-out time
     
DC operated
  ms 350
Regulator supply
     
Voltage
Us V 24 V AC/DC +10 %/- 15 %
Current consumption
Ie mA 50
Current consumption at peak performance (close bypass) at 24 V DC
IPeak A/ms 0,6/50
Notes
    External supply voltage
Relay outputs
     
Number
    2 (TOR, Ready)
Voltage range
  V AC 250
AC-11 current range
  A 1 A, AC-11
Soft start function
Ramp times
     
Acceleration
  s 1 - 30
Deceleration
  s 0 - 30
Start voltage (= turn-off voltage)
  % 30   100
Start pedestal
  % 30 - 100
Fields of application
     
Fields of application
    Soft starting of three-phase asynchronous motors
1-phase motors
   
3-phase motors
   
Functions
Fast switching (semiconductor contactor)
    - (minimum ramp time 1s)
Soft start function
   
Reversing starter
    External solution required
Suppression of closing transients
   
Suppression of DC components for motors
   
Potential isolation between power and control sections
   
Notes


Rated impulse withstand voltage:

  • 1.2 µs/50 µs (rise time/fall time of the pulse to IEC/EN 60947‐2 or ‐3)
  • Applies for control circuit/power section/enclosure
Design verification as per IEC/EN 61439(Show features)(Hide features)
Technical data ETIM 7.0(Show features)(Hide features)
Approvals
Product Standards     IEC/EN 60947-4-2; GB 14048.6; UL 508; CSA-C22.2 No 0-M91; CSA-C22.2 No 14-05 CE marking
UL File No.     E251034
CSA File No.     2511305
CSA Class No.     321106
Specially designed for North America     No
Suitable for     Branch circuits
Current Limiting Circuit-Breaker     No
Max. Voltage Rating     480 V
Degree of Protection     IP20; UL/CSA Type 1
Dimensions