Delivery program

Product range
Accessories
Accessories
Remote switching
Accessories
Undervoltage release
Cannot be combined with a second shunt release.
Retrofitting kit
Slot on the right on the adapter plate.
Maximum operating frequency [Actuations/minute]
3
Limited to 3/min due to the high pick-up current for 35 ms.
Please note - the circuit-breaker's switching frequency = 60/h
Rated control voltage [Us]
48 V DC V
Operating range [x US]
0,85 - 1,1 Factor
max. holding current [In]
0.089 A
max. pick-up current (35ms) [In]
16 A
max. continuous power [AC/DC]
5 VA/W
max. pull-in power (35ms) [AC/DC]
850 VA/W
Circuit-breaker total switching time [@ US=100%]
37 ms
For use with
IZMX16..., IZMX40...
INX16..., INX40...
Instructions
An additional control circuit terminal block is required for retrofitting.
For fixed mounting circuit-breakers→#156593 and withdrawable unit circuit-breakers →#156590
Notes

Can be continuously ON (100% DF)

Design verification as per IEC/EN 61439

Operating ambient temperature min.
-25 °C
Operating ambient temperature max.
+70 °C

Technical data ETIM 7.0

Low-voltage industrial components (EG000017) / Under voltage coil (EC001022)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Circuit breaker (LV < 1 kV) / Undervoltage trip (ecl@ss10.0.1-27-37-04-17 [AKF015013])
Rated control supply voltage Us at AC 50HZ
0 - 0 V
Rated control supply voltage Us at AC 60HZ
0 - 0 V
Rated control supply voltage Us at DC
48 - 48 V
Voltage type for actuating
DC
Type of electric connection
Flat plug-in connection
Number of contacts as normally open contact
0
Number of contacts as normally closed contact
0
Number of contacts as change-over contact
0
Delayed
No
Suitable for power circuit breaker
Yes
Suitable for off-load switch
Yes
Suitable for motor safety switch
No
Suitable for overload relay
No