121474 M22-K02SMC10
Self-monitoring contact elements, Screw terminals, Front fixing, 1 N/O, 2 NC, 24 V 3 A
Alternate Catalog No.
M22-K02SMC10Q
EL-Nummer (Norway)
4315253
Contact element, Connection technique: Screw terminals, Fixing: Front fixing, Description: The N/O is actuated when mounted on the pushbutton., Contacts N/O = Normally open: 1 N/O, Contacts N/C = Normally closed: 2 NC, Contacts Notes: = safety function, by positive opening to IEC/EN 60947-5-1, Actuator travel and actuation force as per DIN EN 60947-5-1, K.5.4.1: mm 4.8, Maximum travel: mm 5.7, Minimum force for positive opening: N 30, Degree of Protection: IP20, Connection to SmartWire-DT: no, Standards: IEC 60947-5-1
Delivery program
Basic function accessories
Self-monitoring contact elements
Description
The N/O is actuated when mounted on the pushbutton.
Connection technique
Screw terminals
Fixing
Front fixing
Degree of Protection
IP20
Connection to SmartWire-DT
no
Contacts
N/O = Normally open
1 N/O
N/C = Normally closed
2 NC 

Notes

Actuator travel and actuation force as per DIN EN 60947-5-1, K.5.4.1
[mm]
4.8
Maximum travel [mm]
5.7
Minimum force for positive opening [ N]
30
Contact travel diagram, stroke in connection with front element
Connection technique
Screw terminals
Technical data
General
Standards
IEC 60947-5-1
Actuating force
≦ 10 n
Operating torque (screw terminals)
≦ 0.8 Nm
Degree of Protection
IP20
Climatic proofing
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperatureOpen
-25 - +70 °C
Terminal capacitiesSolid
0.75 - 2.5 mm2
Terminal capacitiesStranded
0.5 - 2.5 mm2
Terminal capacitiesFlexible with ferrule
0.5 - 1.5 mm2
Contacts
Rated impulse withstand voltage [Uimp]
6000 V AC
Rated insulation voltage [Ui
]
500 V
Overvoltage category/pollution degree
III/3
Max. short-circuit protective deviceFuseless
PKZM0-10/FAZ-B6/1 Type
Max. short-circuit protective deviceFuse [gG/gL]
10 A
Switching capacity
Rated operational current [Ie
]AC-15115 V [Ie
]
6 A
Rated operational current [Ie
]AC-15220 V 230 V 240 V [Ie]
6 A
Rated operational current [Ie
]AC-15380 V 400 V 415 V [Ie]
4 A
Rated operational current [Ie
]AC-15500 V [Ie]
2 A
Rated operational current [Ie
]DC-13 24 V [Ie
]
3 A
Rated operational current [Ie
]DC-13 42 V [Ie
]
1.7 A
Rated operational current [Ie
]DC-13 60 V [Ie
]
1.2 A
Rated operational current [Ie
]DC-13 110 V [Ie
]
0.6 A
Rated operational current [Ie
]DC-13 220 V [Ie
]
0.3 A
Auxiliary contacts
Rated conditional short-circuit current [Iq]
1 kA
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation [In]
6 A
Heat dissipation per pole, current-dependent [Pvid]
0.11 W
Equipment heat dissipation, current-dependent [Pvid]
0 W
Static heat dissipation, non-current-dependent [Pvs]
0 W
Heat dissipation capacity [Pdiss]
0 W
Operating ambient temperature min.
-25 °C
Operating ambient temperature max.
+70 °C
IEC/EN 61439 design verification
10.2 Strength of materials and parts10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9 Insulation properties10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9 Insulation properties10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9 Insulation properties10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Technical data ETIM 7.0
Low-voltage industrial components (EG000017) / Auxiliary contact block (EC000041)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Component for low-voltage switching technology / Auxiliary switch block (ecl@ss10.0.1-27-37-13-02 [AKN342013])
Number of contacts as change-over contact
0
Number of contacts as normally open contact
0
Number of contacts as normally closed contact
2
Number of fault-signal switches
0
Rated operation current Ie at AC-15, 230 V
6 A
Type of electric connection
Screw connection
Model
Top mounting
Mounting method
Front fastening
Lamp holder
None
Approvals
Product Standards
IEC/EN 60947-5; UL 508; CSA-C22.2 No. 14-05; CSA-C22.2 No. 94-91; CE marking
UL File No.
E340491
UL Category Control No.
NISD
CSA File No.
012528_C_000
CSA Class No.
3211-03
North America Certification
UL listed, CSA certified
Degree of Protection
UL/CSA Type: -
-
(Web)
-
Instruction LeafletAssetformer AWA1160-1745, IL04716001E(PDF, 09/2020, bgcsdadeelenesetfifrhrhuitltlvnlplptroruskslsvzh)
-
Instruction LeafletAssetIL04716005Z RMQ-Titan: Emergency-Stop buttons, Emergency-Switching-Off buttons(PDF, 01/2020, bgcsdadeelenesetfifrhrhuitltlvnlplptroruskslsvzh)
-
Eaton EMEA Download-Center - download data for this item
-