116307 EU5C-SWD-CAN
Gateway, SmartWire-DT, 99 SWD modules at CANopen
EL Number (Norway)
4519724
SmartWire-DT gateway for connection to the field bus and for supply of the SmartWire-DT card and switchgears. The connection to CANopen is carried out via the 9 pole SUB-D plug as slave. Automatic baud rate detection from 10 kBit/s to 1 Mbit/s.The address range can be set from 1-32. Up to 99 SmartWire-DT cards can be connected.
General specifications
Product name
Eaton EU5C Communication module
Part no.
EU5C-SWD-CAN
EAN
4015081160471
Product Length/Depth
127 millimetre
Product height
90 millimetre
Product width
35 millimetre
Product weight
0.159 kilogram
Certifications
UL File No.: E29184
UL
CSA File No.: 2324643
CSA
IEC/EN 61131-2
CSA Class No.: 3211-07
UL Category Control No.: NKCR
EN 50178
UL
CSA File No.: 2324643
CSA
IEC/EN 61131-2
CSA Class No.: 3211-07
UL Category Control No.: NKCR
EN 50178
Product Tradename
EU5C
Product Type
Communication module
Product Sub Type
None
Globally Marketable
Yes
Features & Functions
Features
Potential isolation (Fieldbus Interface)
Overload proof
Overload proof
Functions
For connection to CANopen® field bus
Operating mode
Address allocation via DIP switch
General information
Degree of protection
IP20
Overvoltage category
II
Pollution degree
2
Product category
SmartWire-DT coordinators
Repetition rate
1 s
Residual ripple
≤ 5 % (input voltage)
Suitable for
Safety functions
Terminal capacity
0.25 - 1.5 mm², flexible with ferrule
0.2 - 1.5 mm², solid
24 - 16 AWG, solid or stranded
0.2 - 1.5 mm², solid
24 - 16 AWG, solid or stranded
Voltage type
DC
Ambient conditions, mechanical
Constant acceleration
1 g, 8.4 - 150 Hz, according to IEC/EN 61131-2, Vibrations
Constant amplitude
3,5 mm, 5 - 8.4 Hz, according to IEC/EN 61131-2, Vibrations
Drop and topple
50 mm Drop height, Drop to IEC/EN 60068-2-31
Height of fall (IEC/EN 60068-2-32) - max
0.3 m
Mounting position
As required
Shock resistance
15 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 9 Impacts
Climatic environmental conditions
Air pressure
795 - 1080 hPa (operation)
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
55 °C
Ambient storage temperature - min
-40 °C
Ambient storage temperature - max
70 °C
Climatic proofing
In accordance with IEC 60068-2
Operating temperature - min
-25 °C
Operating temperature - max
55 °C
Relative humidity
5 - 95 % (non-condensing, IEC/EN 60068-2-30)
Electro magnetic compatibility
Air discharge
8 kV, according to IEC 61131-2, level 3, ESD
Burst impulse
1 kV, SmartWire-DT cable, according to IEC/EN 61131-2, Level 3
2 kV, Supply cable, according to IEC/EN 61131-2, Level 3
1 kV
2 kV, Supply cable, according to IEC/EN 61131-2, Level 3
1 kV
Contact discharge
4 kV, according to IEC/EN 61131-2, Level 2, ESD
Electromagnetic fields
1 V/m at 2.0 - 2.7 GHz (according to IEC/EN 61131-2:2008)
10 V/m at 80 - 1000 MHz (according to IEC/EN 61131-2:2008)
3 V/m at 1.4 - 2 GHz (according to IEC/EN 61131-2:2008)
10 V/m at 80 - 1000 MHz (according to IEC/EN 61131-2:2008)
3 V/m at 1.4 - 2 GHz (according to IEC/EN 61131-2:2008)
Radiated RFI
10 V (IEC/EN 61131-2:2008, Level 3)
Radio interference class
Class A (EN 55011)
Surge rating
0.5 kV, Supply cable, Surge (IEC/EN 61131-2:2008, Level 1), EMC
Voltage dips
≤ 10 ms, Bridging voltage dips
Electrical rating
Inrush current
12.5 A (for 6 ms)
Power loss
Normally 1 W
Rated control supply voltage
24 V DC (UAUX, -15 %/+20 %)
24 V DC (UPOW, -15 %/+20 %)
24 V DC (UPOW, -15 %/+20 %)
Rated operational current (Ie)
0.6 A
Rated operational voltage
Typically UAUX -0.2 V (for 24 V DC slaves)
14.5 V (± 3 % - SmartWire-DT)
14.5 V (± 3 % - SmartWire-DT)
Short-circuit protection
Yes, Short-circuit rating, SmartWire-DT supply voltage
No, external fuse FAZ Z3, Supply voltage UAux
No, external fuse FAZ Z3, Supply voltage UAux
Supply current - max
0.7 mA
Supply voltage at AC, 50 Hz - min
0 V
Supply voltage at AC, 50 Hz - max
0 V
Supply voltage at DC - min
20.4 V
Supply voltage at DC - max
28.8 V
Communication
Addressing
Address set automatically
Address range: 1 - 32
Address range: 1 - 32
Connection
SmartWire-DT blade terminal SWD4-8MF2
The connection to CANopen® is carried out via the 9 pole SUB-D plug as slave.
Used to connect the SmartWire-DT communication system to industrial field bus systems. Powers SmartWire-DT modules and switchgear
SmartWire-DT gateway for connecting up to 99 SmartWire-DT modules to the field bus and for powering the SmartWire-DT modules and switchgear.
The connection to CANopen® is carried out via the 9 pole SUB-D plug as slave.
Used to connect the SmartWire-DT communication system to industrial field bus systems. Powers SmartWire-DT modules and switchgear
SmartWire-DT gateway for connecting up to 99 SmartWire-DT modules to the field bus and for powering the SmartWire-DT modules and switchgear.
Connection type
1 x SUB-D plug, 9-pole, Field bus interface
Push in terminals, Supply voltage
SWD: Plug, 8-pole
Push in terminals, Supply voltage
SWD: Plug, 8-pole
Data transfer rate
125 kBit/s, SmartWire-DT
250 kBit/s, SmartWire-DT
Up to 1 MBit/s, Fieldbus interface
128 Byte, Fieldbus interface, Output data, max.
128 Byte, Fieldbus interface, Input data, max.
Automatic baud rate detection for rates ranging from 10 kBit/s to 1 Mbit/s.
250 kBit/s, SmartWire-DT
Up to 1 MBit/s, Fieldbus interface
128 Byte, Fieldbus interface, Output data, max.
128 Byte, Fieldbus interface, Input data, max.
Automatic baud rate detection for rates ranging from 10 kBit/s to 1 Mbit/s.
Interfaces
Module type: CANopen® slave
Status display fieldbus interface for CAN with Multi color LED
Terminating resistor switchable via DIP switches
Status display fieldbus interface for CAN with Multi color LED
Terminating resistor switchable via DIP switches
LED indicator
Status indication of SmartWire-DT network: Configurable green or red LED
Status indication of SmartWire-DT master: Green and red LEDs
Status indication of Supply voltage: LED
Status indication of SmartWire-DT master: Green and red LEDs
Status indication of Supply voltage: LED
Number of modules
99 (SmartWire-DT)
Protocol
CAN
CANopen®
CANopen®
Station
2 - 32, Station address, Fieldbus interface
SmartWire-DT master, SmartWire-DT network
SmartWire-DT master, SmartWire-DT network
Safety
Explosion safety category for dust
None
Explosion safety category for gas
None
Potential isolation
Between UPow and 15 V SmartWire-DT supply voltage: no
Supply voltage UAUX: no
Supply voltage UAUX: no
Protection against polarity reversal
Yes
Yes, for supply voltage (Siemens MPI optional)
Yes, for supply voltage (Siemens MPI optional)
Design verification
Equipment heat dissipation, current-dependent Pvid
3.8 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
0 A
Static heat dissipation, non-current-dependent Pvs
1 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Meets the product standard's requirements.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Technical data ETIM 8.0
Programmable logic controllers PLC (EG000024) / Fieldbus, decentr. periphery - communication module (EC001604)
Electric engineering, automation, process control engineering / Control / Field bus, decentralized peripheral / Field bus, decentralized peripheral - communications module (ecl@ss10.0.1-27-24-26-08 [BAA073013])
Supply voltage AC 50 Hz
0 - 0 V
Supply voltage AC 60 Hz
0 - 0 V
Supply voltage DC
20.4 - 28.8 V
Voltage type of supply voltage
DC
Supporting protocol for TCP/IP
No
Supporting protocol for PROFIBUS
No
Supporting protocol for CAN
Yes
Supporting protocol for INTERBUS
No
Supporting protocol for ASI
No
Supporting protocol for KNX
No
Supporting protocol for Modbus
No
Supporting protocol for Data-Highway
No
Supporting protocol for DeviceNet
No
Supporting protocol for SUCONET
No
Supporting protocol for LON
No
Supporting protocol for SERCOS
No
Supporting protocol for PROFINET IO
No
Supporting protocol for PROFINET CBA
No
Supporting protocol for Foundation Fieldbus
No
Supporting protocol for EtherNet/IP
No
Supporting protocol for AS-Interface Safety at Work
No
Supporting protocol for DeviceNet Safety
No
Supporting protocol for INTERBUS-Safety
No
Supporting protocol for PROFIsafe
No
Supporting protocol for SafetyBUS p
No
Supporting protocol for other bus systems
No
Radio standard Bluetooth
No
Radio standard Wi-Fi 802.11
No
Radio standard GPRS
No
Radio standard eGPRS
No
Radio standard GSM
No
Radio standard LTE
No
Radio standard UMTS
No
IO link master
No
System accessory
Yes
Degree of protection (IP)
IP20
With potential separation
No
Fieldbus connection over separate bus coupler possible
No
Rail mounting possible
Yes
Wall mounting/direct mounting
Yes
Front built-in possible
No
Rack-assembly possible
No
Suitable for safety functions
Yes
SIL according to IEC 61508
None
Performance level according to EN ISO 13849-1
None
Appendant operation agent (Ex ia)
No
Appendant operation agent (Ex ib)
No
Explosion safety category for gas
None
Explosion safety category for dust
None
Width
35 mm
Height
90 mm
Depth
127 mm
-
(Web)
-
Asset
-
Asset
-
Asset
-
Asset
-
Asset
-
Asset
-
Asset
-
Eaton EMEA Download-Center - download data for this item
-
Eaton EMEA Download-Center