112922 PF6-25/2/01-A
Residual current circuit breaker (RCCB), 25A, 2p, 100mA, type A
Residual current circuit-breaker PF6, 2 pole, Rated current In: 25 A, Rated short-circuit strength Icn: 6 kA, Rated fault current IΔN: 0.1 A, Type A, Pulse-current sensitive, Partly surge-proof 250 A, Switchgear for residential and commercial applications
General specifications
Product name
Eaton Moeller series xPole - PF6/7 RCCB
Part no.
PF6-25/2/01-A
EAN
4015081124602
Product Length/Depth
80 millimetre
Product height
71 millimetre
Product width
35 millimetre
Product weight
0.22 kilogram
Compliances
RoHS conform
Certifications
IEC/EN 61008
Product Tradename
xPole - PF6/7
Product Type
RCCB
Product Sub Type
None
Delivery program
Application
xPole - Switchgear for residential and commercial applications
Residual current circuit breaker for residential and commercial applications
Residual current circuit breaker for residential and commercial applications
Number of poles
Two-pole
Tripping time
Non-delayed
Amperage Rating
25 A
Rated short-circuit strength
6 kA
Fault current rating
100 mA
Sensitivity type
Pulse-current sensitive
Impulse withstand current
Partly surge-proof 250 A
Type
Tripping signal contact for subsequent installation Z-NHK 248434
Maximum operating temperature is 55 °C: Starting at 40 °C, the max. permissible continuous current decreases by 3% for every 1 °C
Maximum operating temperature is 55 °C: Starting at 40 °C, the max. permissible continuous current decreases by 3% for every 1 °C
Technical Data - Electrical
Voltage rating
230 V AC
Rated operational voltage (Ue) - max
230 V
Rated insulation voltage (Ui)
440 V
Rated impulse withstand voltage (Uimp)
4 kV
Rated fault current - min
0.1 A
Rated fault current - max
0.1 A
Frequency rating
50 Hz
Short-circuit rating
63 A (max. admissible back-up fuse)
Leakage current type
A
Rated residual making and breaking capacity
500 A
Admissible back-up fuse overload - max
25 A gG/gL
Rated short-time withstand current (Icw)
6 kA
Surge current capacity
0.25 kA
Test circuit range
184 V AC - 250 V AC
Pollution degree
2
Lifespan, electrical
4000 operations
Technical Data - Mechanical
Frame
45 mm
Width in number of modular spacings
2
Built-in width (number of units)
35 mm (2 SU)
Built-in depth
69.5 mm
Mounting Method
DIN rail
Quick attachment with 2 latch positions for DIN-rail IEC/EN 60715
Quick attachment with 2 latch positions for DIN-rail IEC/EN 60715
Degree of protection
IP20
IP20, IP40 with suitable enclosure
IP20, IP40 with suitable enclosure
Terminals (top and bottom)
Open mouthed/lift terminals
Terminal capacity (solid wire)
1.5 mm² - 35 mm²
Connectable conductor cross section (solid-core) - min
1.5 mm²
Connectable conductor cross section (solid-core) - max
35 mm²
Terminal capacity (stranded cable)
16 mm² (2x)
Connectable conductor cross section (multi-wired) - min
1.5 mm²
Connectable conductor cross section (multi-wired) - max
16 mm²
Terminal protection
Finger and hand touch safe, DGUV VS3, EN 50274
Busbar material thickness
0.8 mm - 2 mm
Lifespan, mechanical
20000 operations
Permitted storage and transport temperature - min
-35 °C
Permitted storage and transport temperature - max
60 °C
Climatic proofing
25-55 °C / 90-95% relative humidity according to IEC 60068-2
Design verification as per IEC/EN 61439 - technical data
Rated operational current for specified heat dissipation (In)
25 A
Heat dissipation per pole, current-dependent
0 W
Equipment heat dissipation, current-dependent
1.3 W
Static heat dissipation, non-current-dependent
0 W
Heat dissipation capacity
0 W
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
55 °C
Design verification as per IEC/EN 61439
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Additional information
Accessories required
Z-HK 248432
Features
Residual current circuit breaker
Additional equipment possible
Additional equipment possible
Fitted with:
Interlocking device
IS/SPE-1TE 101911
IS/SPE-1TE 101911
Special features
Type A
Residual current circuit breakers
PF6
Residual current circuit breakers
PF6
Used with
Z-RC/AK-2TE 285385 (sealing cover set)
Z-FW/LP 248296 (Remote control and automatic switching device)
KLV-TC-2 276240 (Compact enclosure)
Z-FW/LP 248296 (Remote control and automatic switching device)
KLV-TC-2 276240 (Compact enclosure)
Technical data ETIM 9.0
Circuit breakers and fuses (EG000020) / Residual current circuit breaker (RCCB) (EC000003)
Electric engineering, automation, process control engineering / Electrical installation, device / Residual current protection system / Residual current circuit breaker (RCCB) (ecl@ss13-27-14-22-01 [AAB906019])
Number of poles
2
Rated voltage
230 V
Rated current
25 A
Rated fault current
0.1 A
Rated insulation voltage Ui
440 V
Rated impulse withstand voltage Uimp
4 kV
Power loss
W
Mounting method
DIN rail
Leakage current type
A
Selective protection
No
Short-time delayed tripping
No
Short-circuit breaking capacity (Icw)
6 kA
Surge current capacity
0.25 kA
Voltage type
AC
With interlocking device
Yes
Frequency
50 Hz
Additional equipment possible
Yes
Degree of protection (IP)
IP20
Width in number of modular spacings
2
Built-in depth
69.5 mm
Ambient temperature during operating
-25 - 55 °C
Pollution degree
2
Connectable conductor cross section multi-wired
1.5 - 16 mm²
Connectable conductor cross section solid-core
1.5 - 35 mm²
RAL-number (similar)
7035
Explosion-proof
No
-
Eaton EMEA Download-Center - download data for this item
-
Eaton EMEA Download-Center