111761 PDIM-100/4
Residual current circuit-breaker, 100A, 4p, 0mA, AC-Char
Alternate Catalog No.
PDIM-100-4
EL-Nummer (Norway)
1609349
Leakage current meter PDIM, 4 pole, Rated current In: 100 A, Rated short-circuit strength Icn: 10 kA, Rated fault current IΔN: adjustable: 0.03/0.1/0.3/0.5/1 A, Switchgear for industrial and advanced commercial applications
Delivery program
Basic function
Leakage current monitor
Number of poles
4 pole
Application
Switchgear for industrial and advanced commercial applications
Rated current [In]
100 A
Rated short-circuit strength [Icn]
10 kA
Rated fault current [IΔN]
adjustable: 0.03/0.1/0.3/0.5/1 A
Tripping
Short time-delayed, adjustable
selective switch off, adjustable
non-delayed, adjustable s…
selective switch off, adjustable
non-delayed, adjustable s…
Product range
PDIM
Sensitivity
AC and pulsating DC current sensitive
Technical data
Electrical
Types based on
DIN/EN 62020
Current test marks
As per inscription
Rated current [In]
100 A
Response value
unverzögert
Type G
10 ms verzögert
Type S
40 ms verzögert - selektiv
Rated voltage according to IEC/EN 60947-2 [Un]
230/400, 50/60 Hz
240/415, 50/60 Hz V AC
240/415, 50/60 Hz V AC
Sensitivity
AC and pulsating DC current sensitive
Rated insulation voltage [Ui
]
440 V
Rated short-circuit strength [Icn]
10 kA
Max. admissible back-up fuseShort-circuit [gG/gL]
100 A
Max. admissible back-up fuseOverload [gG/gL]
63 A
Switch contacts
10 A / 240 V~
Response behaviour of contacts
1: 30 - 50 % IΔn
2: > 50 % IΔn
2: > 50 % IΔn
lifespanElectrical [Operations]
≧ 4000
lifespanMechanical [Operations]
≧ 20000
Mechanical
Standard front dimension
45 mm
Device height
80 mm
Built-in width
70 (4TE) mm
Mounting
Quick attachment with 2 latch positions on top-hat rail IEC/EN 60715
Degree of Protection
IP20, IP40 with suitable enclosure
Terminals top and bottom
Twin-purpose terminals
Terminal protection
finger and hand touch safe, DGUV VS3, EN 50274
Terminal capacity (1, 2, 3, 4, 5, 6, N, N)Solid
1.5 - 35 mm2
Terminal capacity (1, 2, 3, 4, 5, 6, N, N)Stranded
2 x 16 mm2
Terminal cross-section of switching contacts
0.25 - 1.5 mm2
Thickness of busbar material
0.8 - 2 mm
Admissible ambient temperature range
-25 - +60 °C
Permissible storage and transport temperatures
-35 - +60 °C
Climatic proofing
25-55°C/90-95% relative humidity according to IEC 60068-2
Operating ambient temperature min.
-25 °C
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation [In]
100 A
Heat dissipation per pole, current-dependent [Pvid]
0 W
Equipment heat dissipation, current-dependent [Pvid]
18.8 W
Static heat dissipation, non-current-dependent [Pvs]
0 W
Heat dissipation capacity [Pdiss]
0 W
Operating ambient temperature min.
-25 °C
Operating ambient temperature max.
+60 °C
Starting at 40 °C, the max. permissible continuous current decreases by 1.2% for every 1 °C
IEC/EN 61439 design verification
10.2 Strength of materials and parts10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9 Insulation properties10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9 Insulation properties10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9 Insulation properties10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Technical data ETIM 8.0
Circuit breakers and fuses (EG000020) / Residual current circuit breaker (RCCB) (EC000003)
Electric engineering, automation, process control engineering / Electrical installation, device / Residual current protection system / Residual current circuit breaker (RCCB) (ecl@ss10.0.1-27-14-22-01 [AAB906014])
Number of poles
4
Rated voltage
415 V
Rated current
100 A
Rated fault current
1 A
Rated insulation voltage Ui
440 V
Rated impulse withstand voltage Uimp
4 kV
Mounting method
DIN rail
Leakage current type
AC
Selective protection
Yes
Short-time delayed tripping
Yes
Short-circuit breaking capacity (Icw)
10 kA
Surge current capacity
0.25 kA
Voltage type
AC
With interlocking device
Yes
Frequency
60 Hz
Additional equipment possible
Yes
Degree of protection (IP)
IP20
Width in number of modular spacings
4
Built-in depth
60 mm
Ambient temperature during operating
-25 - 60 °C
Pollution degree
2
Connectable conductor cross section multi-wired
1.5 - 16 mm²
Connectable conductor cross section solid-core
1.5 - 35 mm²
Explosion-proof
No
-
Asset
-
Eaton EMEA Download-Center - download data for this item
-
Eaton EMEA Download-Center