111705 CS-84/250
Wall enclosure with mounting plate, HxWxD=800x400x250mm
EL-Nummer (Norway)
2466129
Wall-mounting enclosure CS, door with continuous foamed-in polyurethane gasket, shock resistance category IK09 to EN 62262, single door, door hinges right, opening angle 120°, door hinge pins with quick change technology, door profile molding with perforation at 25 mm intervals for fixing DIN mounting rails or for fixing cable conduits and leads, standardized locking system with sash fastener, made completely of metal, with mounting plate sheet steel, equipment supplied: lock, 3mm double ward key. Optional accessory equipment e.g. rotary comfort grip PHZ-A-ADD-ON with cylinder lock PHZ-E10/30-GS. Designed according IEC/EN 62208.
Delivery program
Product range
Wall-mounting housing CS
Product function
Wall-mounting housing with mounting plate
Degree of Protection
IP66
IP23 (with ventilating plates)
IP23 (with ventilating plates)
Description
Foamed polyurethane sealing throughout.
Impact resistance category IK09 to EN 62262.
Sheet steel mounting plate
Bottom plate with foamed gasket.
Single door, door stop on the right, door opening angle 120°
Door hinge pins with quick change technology.
Standardized locking system with sash fastener.
Powder coating RAL 7035 inside and outside
Impact resistance category IK09 to EN 62262.
Sheet steel mounting plate
Bottom plate with foamed gasket.
Single door, door stop on the right, door opening angle 120°
Door hinge pins with quick change technology.
Standardized locking system with sash fastener.
Powder coating RAL 7035 inside and outside
Material
Steel plate
Dimensions
Width
400 mm
Height
800 mm
Depth
250 mm
Locks [Number]
2
Hinges [Number]
3
Door profile molding [Number]
2
Flange plates [Width x Depth]
172 x 332 mm
Max. F3A flanges [Number]
1
Mounting plates [Width x Depth]
Height
770 mm
Width
350 mm
Weight
23.2 kg
Information about equipment supplied
Lock, 3 mm double ward key
Including M6 threaded welded studs for earth conductor connections in the door
Including M6 threaded welded studs for earth conductor connections in the door
Technical data
General
Standards
IEC/EN 62208
RoHS
in accordance with Directive 2015/863/EU of the European Parliament and Council
RoHS (in accordance with Directive 2002/95/EC of the European Parliament and Council)
yes
Climatic proofing
Damp heat, constant, to IEC 60068-2-78; Damp heat, cyclical, to IEC 60068-2-30
Ambient temperature
-25 - +40 °C
Degree of Protection
IP66
IP23 (with ventilating plates)
IP23 (with ventilating plates)
Installation conditions
Indoor installation
Power loss
Power loss Pv [W] for fully enclosed sheet steel enclosure CS without internal partitions for wall mounting.
Example: max. ambient temperature 35°C; Overtemperature ΔT = 20 K; Relative humidity = 75%.
Example: max. ambient temperature 35°C; Overtemperature ΔT = 20 K; Relative humidity = 75%.
Power lossMax. heat dissipationIndividual enclosure for wall mounting [PV]
57 W
Power lossMax. heat dissipationStarting enclosure for wall mounting [PV]
53 W
Power lossMax. heat dissipationMiddle enclosure for wall mounting [PV]
48 W
Material characteristics
Material
Steel plate
Surface treatment
Structured powder spray polyester based paint finish
Surface finish
Semi-textured
Colour
light gray (RAL 7035)
Finish
Gloss
Material thicknessBody
1.5 mm
Material thicknessMounting plate
3 mm
Material thicknessDoor
1.5 mm
Material thicknessBottom plate
2 mm
Material properties
MechanicalImpact resistance
IK09 according to EN 62262
Mechanicalmax. assembly weightsTotal of Weight of fitted components
325 kg
Mechanicalmax. assembly weightsMounting plate
300 kg
Mechanicalmax. assembly weightsDoor
25 kg
Mechanicalmax. assembly weights
500 kg payload, when brackets fitted in all four enclosure corners (vertically or horizontally) and the weights are symmetrically distributed within the enclosure.
Description/standard features
Construction
Canted and seam welded, including two M6 threaded bolts for earth conductor connections inside the enclosure.
Back plate
9 mm drilling dimensions for wall mounting
Side plates
Without apertures
Top plate
Without apertures
Bottom plate
Enclosed, foamed gasket, can be unscrewed for F3A-… flanges or for assembly by user
Mounting plate, material
Sheet steel, hot-galvanized
Door, Engineering
Including M6 threaded welded studs for earth conductor connections in the door:
Information about equipment supplied
Lock, 3 mm double ward key
Including M6 threaded welded studs for earth conductor connections in the door
Including M6 threaded welded studs for earth conductor connections in the door
If electrical apparatus is to be installed in the door, a continuous, permanent protective ground contactor connection must be established with a protective ground cable. The threaded welded studs on the door and on the cabinet side wall must be used as connecting points for the ground leads.
Door hinges
On the right, can be converted by user
Type Door
closed
door opening angle
120°
Door interlock
Standard closure 3 mm double-ward key
Locks [Number]
2
Design verification as per IEC/EN 61439
Technical data for design verification
Heat dissipation, at an ambient temperature of 35°C, delta T: 20 degrees in top of the enclosure, calculated as per IEC 60890Individual enclosure for wall mounting [PV]
57 W
Heat dissipation, at an ambient temperature of 35°C, delta T: 20 degrees in top of the enclosure, calculated as per IEC 60890Starting enclosure for wall mounting [PV]
53 W
Heat dissipation, at an ambient temperature of 35°C, delta T: 20 degrees in top of the enclosure, calculated as per IEC 60890Middle enclosure for wall mounting [PV]
48 W
Heat dissipation, at an ambient temperature of 35°C, delta T: 35 degrees in top of the enclosure, calculated as per IEC 60890Individual enclosure for wall mounting [PV]
109 W
Heat dissipation, at an ambient temperature of 35°C, delta T: 35 degrees in top of the enclosure, calculated as per IEC 60890Starting enclosure for wall mounting [PV]
101 W
Heat dissipation, at an ambient temperature of 35°C, delta T: 35 degrees in top of the enclosure, calculated as per IEC 60890Middle enclosure for wall mounting [PV]
92 W
IEC/EN 61439 design verification
10.2 Strength of materials and parts10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.5 Lifting
Does not apply to enclosures without lifting aids.
10.2 Strength of materials and parts10.2.6 Mechanical impact
IK09
10.2 Strength of materials and parts10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
IP66
10.4 Clearances and creepage distances
Is the panel builder's responsibility.
10.5 Protection against electric shock
< 0.1 Ω; meets the product standard's requirements.
10.6 Incorporation of switching devices and components
Is the panel builder's responsibility.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9 Insulation properties10.9.2 Power-frequency electric strength
Ui = 1000 V AC
10.9 Insulation properties10.9.3 Impulse withstand voltage
Does not apply to basic enclosures as defined in EN 62208.
10.9 Insulation properties10.9.4 Testing of enclosures made of insulating material
Does not apply to metal enclosures.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
Meets the product standard's requirements.
Technical data ETIM 8.0
Cabinet enclosures (EG000011) / Enclosure/cabinet (empty) (EC000261)
Electric engineering, automation, process control engineering / Electrical cabinet, housing, rack / Electrical cabinet (empty) / Electrical cabinet (ecl@ss10.0.1-27-18-01-01 [AGZ056016])
Width
400 mm
Height
800 mm
Depth
250 mm
Material
Steel
Material quality
Other
Surface finishing
Powder coating
Colour
Grey
RAL-number
7035
Detached
No
Floor standing wall model
Yes
Suitable for wall mounting
Yes
Corner model
No
Intermediate mounting
Yes
Connectable
No
With mounting plate
Yes
Mounting plate depth-adjustable
No
Suitable for wall built-in
Yes
Pole fastening
Yes
Number of doors
1
Number of locks
2
Suitable for metrical mounting
Yes
Suitable for outdoor set-up
No
Pitched roof
No
EMC-version
No
With glazed door
No
With ventilation door
No
With backside door
No
Impact strength
IK09
Degree of protection (IP)
IP66
Degree of protection (NEMA)
12
Thermal dissipation (Delta T = 20 K) according to IEC/TR 60890
57 W
Max. permissible load of the enclosure according to IEC 62208
3250 N
Max. permissible load of the door(s) according to IEC 62208
250 N
Max. permissible load of the mounting plate according to IEC 62208
3000 N
-