Delivery program

Product range
Switch-disconnectors
Protective function
Disconnectors/main switches
Standard/Approval
IEC, UL
Installation type
Fixed
Construction size
N1
Description
IEC/EN 60947-2: Circuit-breakers without overcurrent (CBI-X) with main switch characteristics and isolating characteristics to IEC/EN 60204.
Number of poles
3 pole
Standard equipment
Box terminal
Switch positions
I, +, 0
Rated current = rated uninterrupted current [In = Iu]
63 A
Rated current = rated uninterrupted current [In = Iu]
63 A
Switching capacity
SCCR 480Y/277 V 60 Hz [Icu]
35 kA
Short-circuit releases [Irm ]
Non-delayed [Ii = In x …]
1250 A fixed

Technical data

Switch-disconnectors
Rated surge voltage invariability [Uimp ]Main contacts
6000 V
Rated surge voltage invariability [Uimp ]Auxiliary contacts
6000 V
Rated operational voltage [Ue]
690 V AC
Rated current = rated uninterrupted current [In = Iu]
63 A
Rated current = rated uninterrupted current [In = Iu]
63 A
Rated uninterrupted current [Iu ]IEC/EN 61131-3 [Iu ]
125 A
Rated uninterrupted current [Iu ]UL 489, CSA 22.2 No. 5.1 [Iu ]
125 A
Overvoltage category/pollution degree
III/3
Rated insulation voltage [Ui ]
690 V
Other technical data (sheet catalogue)
Ambient temperatureAmbient temperature, storage
- 40 - + 70 °C
Ambient temperatureOperation
-25 - +70 °C
Mounting position
Vertical and 90° in all directions
  With residual-current release XFI:
- NZM1, N1, NZM2, N2: vertical and 90° in all directions
with plug-in adapter elements
- NZM1, N1, NZM2, N2: vertical, 90° right/left
with withdrawable unit:
- NZM3, N3: vertical, 90 ° left
- NZM4, N4: vertical
with remote operator:
- NZM2, N(S)2, NZM3, N(S)3, NZM4, N(S)4: vertical and 90° in all directions

Direction of incoming supply
as required
Degree of protectionDevice
In the area of the HMI devices: IP20 (basic protection type)
Degree of protectionEnclosures
With insulating surround: IP40
With door coupling rotary handle: IP66
Degree of protectionTerminations
Tunnel terminal: IP10
Phase isolator and band terminal: IP00
Switching capacity (UL489, CSA 22.2 No. 5.1)
SCCR 240 V 60 Hz [Icu]
85 kA
SCCR 480Y/277 V 60 Hz [Icu]
35 kA
Rated short-circuit making capacity [Icm ]
240 V 50/60 Hz [Icm ]
187 kA
400/415 V 50/60 Hz [Icm ]
105 kA
440 V 50/60 Hz [Icm ]
74 kA
525 V 50/60 Hz [Icm ]
53 kA
690 V 50/60 H [Ic]
17 kA
Rated short-circuit breaking capacity Icn [Icn ]
Icu to IEC/EN 60947 test cycle O-t-CO [Icu]240 V 50/60 Hz [Icu ]
85 kA
Icu to IEC/EN 60947 test cycle O-t-CO [Icu]400/415 V 50 Hz [Icu ]
50 kA
Icu to IEC/EN 60947 test cycle O-t-CO [Icu]440 V 50/60 Hz [Icu ]
35 kA
Icu to IEC/EN 60947 test cycle O-t-CO [Icu]525 V 50/60 Hz [Icu ]
20 kA
Icu to IEC/EN 60947 test cycle O-t-CO [Icu]690 V 50/60 Hz [Icu ]
10 kA
Ics to IEC/EN 60947 test cycle O-t-CO-t-CO [Ics]230 V 50/60 Hz [Ics ]
85 kA
Ics to IEC/EN 60947 test cycle O-t-CO-t-CO [Ics]400/415 V 50/60 Hz [Ics ]
50 kA
Ics to IEC/EN 60947 test cycle O-t-CO-t-CO [Ics]440 V 50/60 Hz [Ics ]
35 kA
Ics to IEC/EN 60947 test cycle O-t-CO-t-CO [Ics]525 V 50/60 Hz [Ics ]
10 kA
Ics to IEC/EN 60947 test cycle O-t-CO-t-CO [Ics]690 V 50/60 Hz [Ics]
7.5 kA
Lifespan, mechanical [Operations]
20000
Max. operating frequency
120 Ops/h
Lifespan, electrical
400 V 50/60 Hz [Operations]
10000
415 V 50/60 Hz [Operations]
10000
690 V 50/60 Hz [Operations]
7500
< 10 ms
Terminal capacity IEC
Standard equipment
Box terminal
Optional accessories
Screw connection
Tunnel terminal
connection on rear
Copper conductors and cablesBox terminalSolid
1 x (10 - 16)
2 x (6 - 16) mm2
Copper conductors and cablesBox terminalStranded
1 x (10 - 70) 3)
2 x (6 - 25) mm2
Copper conductors and cablesBox terminal
3) Up to 95 mm² can be connected depending on the cable manufacturer.
Copper conductors and cablesTunnel terminalSolid
1 x 16 mm2
Copper conductors and cablesTunnel terminalStranded1-hole
1 x (25 - 95) mm2
Copper conductors and cablesBolt terminal and rear-side connectionDirect on the switchSolid
1 x (10 - 16)
2 x (6 - 16) mm2
Copper conductors and cablesBolt terminal and rear-side connectionDirect on the switchStranded
1 x (25 - 70) 3)
2 x 25 mm2
Copper conductors and cablesBolt terminal and rear-side connectionDirect on the switch
3) Up to 95 mm² can be connected depending on the cable manufacturer.
Al conductors, Al cableTunnel terminalSolid
1 x 16 mm2
Al conductors, Al cableTunnel terminalStranded1-hole
1 x (25 - 95) mm2
Al conductors, Al cableBolt terminal and rear-side connectionDirect on the switchSolid
1 x (10 - 16)
2 x (10 - 16) mm2
Al conductors, Al cableBolt terminal and rear-side connectionDirect on the switchStranded
1 x (25 - 35)
2 x (25 - 35) mm2
Cu strip (number of segments x width x segment thickness)Box terminal [min.]
2 x 9 x 0.8 mm
Cu strip (number of segments x width x segment thickness)Box terminal [max.]
9 x 9 x 0.8 mm
Copper busbar (width x thickness) [mm]Bolt terminal and rear-side connectionScrew connection
M6
Copper busbar (width x thickness) [mm]Bolt terminal and rear-side connectionDirect on the switch [min.]
12 x 5 mm
Copper busbar (width x thickness) [mm]Bolt terminal and rear-side connectionDirect on the switch [max.]
16 x 5 mm
NA terminal capacity
Copper conductors and cablesBox terminalsolid
1 x (12 - 6) AWG
Copper conductors and cablesBox terminalStranded
1 x (4 - 2/0) AWG/kcmil
Copper conductors and cablesTunnel terminalsolid
1 x 6 AWG
Copper conductors and cablesTunnel terminalStranded1-hole
1 x (4 - 3/0) AWG/kcmil
Copper conductors and cablesBolt terminal and rear-side connectionDirect on the switchsolid
1 x (12 - 6)
2 x (9 - 6) AWG
Cu strip (number of segments x width x segment thickness)Box terminal [min.]
2 x 9 x 0.8 mm
Cu strip (number of segments x width x segment thickness)Box terminal [max.]
9 x 9 x 0.8 mm
Copper busbar (width x thickness) [mm]Bolt terminal and rear-side connectionScrew connection
M6
Copper busbar (width x thickness) [mm]Bolt terminal and rear-side connectionDirect on the switch [min.]
12 x 5 mm
Copper busbar (width x thickness) [mm]Bolt terminal and rear-side connectionDirect on the switch [max.]
16 x 5 mm

Design verification as per IEC/EN 61439

Datos técnicos para la verificación del diseño
Intensidad asignada de empleo para disipación térmica específica [In]
63 A
Disipación térmica del equipo, en función de la intensidad [Pvid]
6.69 W
Temperatura ambiente mínima de funcionamiento
-25 °C
Temperatura ambiente máxima de funcionamiento
+70 °C
Verificación de diseño IEC / EN 61439
10.2 Resistencia de materiales y piezas10.2.2 Resistencia a la corrosión
Cumple con los requisitos de la norma del producto.
10.2 Resistencia de materiales y piezas10.2.3.1 Verificación de la estabilidad térmica de los armarios
Cumple con los requisitos de la norma del producto.
10.2 Resistencia de materiales y piezas10.2.3.2 Verificación de la resistencia de los materiales aislantes en condiciones de calor normales
Cumple con los requisitos de la norma del producto.
10.2 Resistencia de materiales y piezas10.2.3.3. Verificación de la resistencia de los materiales aislantes al calor excesivo y al fuego debido a los efectos eléctricos internos
Cumple con los requisitos de la norma del producto.
10.2 Resistencia de materiales y piezas10.2.4 Resistencia a radiación ultravioleta (UV)
Cumple con los requisitos de la norma del producto.
10.2 Resistencia de materiales y piezas10.2.5 Elevación
No se aplica, ya que todo el equipo de conmutación debe ser evaluado.
10.2 Resistencia de materiales y piezas10.2.6 Impacto mecánico
No se aplica, ya que todo el equipo de conmutación debe ser evaluado.
10.2 Resistencia de materiales y piezas10.2.7 Inscripciones
Cumple con los requisitos de la norma del producto.
10.3 Grado de protección de montajes
No se aplica, ya que todo el equipo de conmutación debe ser evaluado.
10.4 Distancias de separación y fuga
Cumple con los requisitos de la norma del producto.
10.5 Protección contra descargas eléctricas
No se aplica, ya que todo el equipo de conmutación debe ser evaluado.
10.6 Incorporación de dispositivos y componentes de conmutación
No se aplica, ya que todo el equipo de conmutación debe ser evaluado.
10.7 Conexiones y circuitos eléctricos internos
Es responsabilidad del cuadrista.
10.8 Conexiones de conductores externos
Es responsabilidad del cuadrista.
10.9 Propiedades de aislamiento10.9.2 Resistencia eléctrica de frecuencia de alimentación
Es responsabilidad del cuadrista.
10.9 Propiedades de aislamiento10.9.3 Tensión de impulso soportada
Es responsabilidad del cuadrista.
10.9 Propiedades de aislamiento10.9.4 Pruebas de armarios hechos de material aislante
Es responsabilidad del cuadrista.
10.10 Aumento de la temperatura
El cuadrista es responsable del cálculo del aumento de la temperatura. Eaton proporcionará datos de disipación de calor para los dispositivos.
10.11 Resistencia a los cortocircuitos
Es responsabilidad del cuadrista. Deben tenerse en cuenta las especificaciones de la aparamenta.
10.12 Compatibilidad electromagnética
Es responsabilidad del cuadrista. Deben tenerse en cuenta las especificaciones de la aparamenta.
10.13 Función mecánica
El dispositivo cumple los requisitos, siempre que se observe la información del folleto de instrucciones (IL).

Technical data ETIM 7.0

Conmutadores en baja tensión (EG000017) / Disyuntor para protección de transformador/generador/instalación (EC000228)
Tecnología electrónica, de automatización y de mando de procesos / Tecnología de conmutación de baja tensión / Interruptor de potencia, interruptor de potencia (baja tensión) / Interruptor de potencia de transformador, generador y protección de instal. (ecl@ss10.0.1-27-37-04-09 [AJZ716013])
Intensidad permanente nominal Iu
63 Ampere
Intervalo de tensión nominal
690 - 690 Volt
Capacidad de desconexión de cortocircuito nominal lcu a 400 V, 50 Hz
50 kiloampere
Ajuste intervalo protector sobrecarga
0 - 0 Ampere
Liberación del corto circuito con retado a corto plazo del intervalo de ajuste
0 - 0 Ampere
Liberación del corto circuito sin retardo del intervalo de ajuste
1250 - 1250 Ampere
Protección de fuga a tierra integrada
No
Tipo de conexión del circuito de corriente principal
Abrazadera de bastidor
Construcción de dispositivo
Técnica integrada fija para dispositivo integrado
Compatible para montaje en rieles DIN (rieles simétricos)
No
Número de contactos auxiliares como contacto normalmente cerrado
0
Número de contactos auxiliares como contacto normalmente abierto
0
Número de contactos auxiliares como contacto de intercambio
0
Indicador de desconexión disponible
No
Con liberación de bajo voltaje integrada
No
Número de polos
3
Posición de la conexión para el circuito principal de tensión
Parte frontal
Tipo de elemento de control
Palanca de balancín
Accionamiento por motor integrado
No
Accionamiento por motor opcional
No
Grado de protección (IP)
IP20

Approvals

Product Standards
UL 489; IEC 60947-2; CE marking
UL File No.
E148671
UL Category Control No.
WJAZ
North America Certification
UL listed
Specially designed for North America
Yes
Suitable for
Feeder circuits, branch circuits
Current Limiting Circuit-Breaker
No
Max. Voltage Rating
480Y/277 V
Degree of Protection
IEC: IP20; UL/CSA Type: -

Characteristics

Characteristic curve
1230DIA-3
Characteristic curve
1230DIA-13

Dimensions

123X039
① Blow out area, minimum clearance to adjacent parts
123X506