101457 BBA4-63
Busbar adapter, 54 mm, 63 A, DIN rail: 1
EL Number (Norway)
2465052
55mm busbar adapter for 60mm busbar system, one mounting rail, three prefabricated cables (AWG8/10 square millimeter) for connection of switching device, can be used for motor-protective circuit-breaker PKZM4, PKE65, rated operational current: 63A
General specifications
Product name
Eaton Moeller® series BBA Accessory Busbar adapter
Part no.
BBA4-63
EAN
4015081013777
Product Length/Depth
200 millimetre
Product height
63 millimetre
Product width
55 millimetre
Product weight
0.347 kilogram
Certifications
UL File No.: E300273
CE
IEC60439-1
CSA-C22.2 No. 14
Certified by UL for use in Canada
UL 508
UL Category Control No.: NMTR; NMTR7
UL
UL 508A
CE
IEC60439-1
CSA-C22.2 No. 14
Certified by UL for use in Canada
UL 508
UL Category Control No.: NMTR; NMTR7
UL
UL 508A
Product Tradename
BBA
Product Type
Accessory
Product Sub Type
Busbar adapter
Delivery program
Type
SASY Busbar system 60 mm
Busbar adapter
Busbar adapter
Nominal current
63 A
Technical Data - Electrical
Voltage rating (UL CSA 13)
600 V AC, UL/CSA
Voltage rating at AC
690 V
Rated operation current (Ie)
63 A
Electric connection type
Round conductor
Technical Data - Mechanical
Rail width
35 mm
Number of DIN rails
1
Busbar distance
60 mm
Busbar thickness - min
5 mm
Busbar thickness - max
10 mm
Adapter width
55 mm
Design verification as per IEC/EN 61439 - technical data
Equipment heat dissipation, current-dependent Pvid
6.9 W
Static heat dissipation, non-current-dependent Pvs
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
55 °C
Design verification as per IEC/EN 61439
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Additional information
Special features
Terminal capacity: 10 mm² (AWG 8)
Technical data ETIM 9.0
Low-voltage industrial components (EG000017) / Busbar adapter (EC001531)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Busbar trunking system (LV circuitry) / Busbar adapter (low-voltage switching technology) (ecl@ss13-27-37-03-04 [ACN951016])
Mounting rail armament
1 mounting rail
Type of electric connection
Round conductor
Rated current In
63 A
Min. busbar thickness
5 mm
Max. busbar thickness
10 mm
Width of the adapter
55 mm
Rail width
35 mm
Busbar distance
60 mm
-
(Web)
-