General specifications
Product name
Eaton xEnergy Safety Ci meter enclosure rail
Part no.
ZG/I45E-200
EAN
4015080984795
Product Length/Depth
225 millimetre
Product height
500 millimetre
Product width
375 millimetre
Product weight
8.2 kilogram
Compliances
RoHS conform
Product Tradename
xEnergy Safety Ci
Product Type
Meter enclosure
Product Sub Type
Rail
Delivery program
Type
Ci insulated enclosure Meter enclosures Prepared enclosures
Accessory/spare part type
Meter rail
Meter enclosures
Color
Gray
Nominal current
1600 A
Technical Data - Electrical
Circuit integrity
Other
Technical Data - Mechanical
Unit type
Complete housing
Surface protection
Other
Enclosure material
Plastic
Width in number of modular spacings
17
Mounting depth
186 mm
Mounting method
Surface mounted (plaster)
Degree of protection
IP65
Other
IK10
Number of conduit inlets
104
Number of modules
1
Number of openings (flange plates)
6
Number of rows
0
Built-in depth
200 mm
Internal depth
200 mm
Cover/door color
Transparent
Cover/door model
Closed
Cover/door type
Transparent
Optional
None
Plate thickness (cabinet)
6 mm
Plate thickness (cover/door)
6 mm
Temperature-rise verification as per IEC 60890
Heat diss. ambient 35°C delta T: 20°C free stand middle encl. top (IEC 60890)
35 W
Heat diss. ambient 35°C delta T: 20°C wall mount middle encl. top (IEC 60890)
31 W
Heat diss. ambient 35°C delta T: 35°C free stand middle encl. top (IEC 60890)
71 W
Heat diss. ambient 35°C delta T: 35°C wall mount middle encl. top (IEC 60890)
62 W
Heat diss. ambient 35°C delta T:20°C free stand individ. encl. top (IEC 60890)
40 W
Heat diss. ambient 35°C delta T:20°C free stand starting encl. top (IEC 60890)
38 W
Heat diss. ambient 35°C delta T:20°C wall mount individ. encl. top (IEC 60890)
36 W
Heat diss. ambient 35°C delta T:20°C wall mount starting encl. top (IEC 60890)
33 W
Heat diss. ambient 35°C delta T:35°C free stand individ. encl. top (IEC 60890)
81 W
Heat diss. ambient 35°C delta T:35°C free stand starting encl. top (IEC 60890)
76 W
Heat diss. ambient 35°C delta T:35°C wall mount individ. encl. top (IEC 60890)
72 W
Heat diss. ambient 35°C delta T:35°C wall mount starting encl. top (IEC 60890)
67 W
Design verification as per IEC/EN 61439
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Lower part: 960 °C / cover: 850 °C
10.2.4 Resistance to ultra-violet (UV) radiation
Not relevant to indoor installations.
10.2.5 Lifting
30 kg per enclosure with support frame and lifting aid met; assembled and secured as per the latest applicable instruction leaflet.
10.2.6 Mechanical impact
IK10
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
IP65
10.4 Clearances and creepage distances
Is the panel builder's responsibility.
10.5 Protection against electric shock
Protection class 2, therefore not applicable.
10.6 Incorporation of switching devices and components
Is the panel builder's responsibility.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Ui = 1000 V AC
10.9.3 Impulse withstand voltage
8 kV
10.9.4 Testing of enclosures made of insulating material
Meets the product standard's requirements.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
Meets the product standard's requirements.
Additional information
Features
Cover with overpressure release
Fitted with:
Mounting plate
Functions
Extension possible
Protection class
II
RAL-number
7035
Special features
Meter rail to DIN 43853 including meter fixing screws and nuts Metric cable entry knockouts in all sides Fixing straps for wall fixing Sealable cover fasteners
Suitable for
Outdoor use
Lightning protection

Technical data ETIM 9.0

Distribution boards (EG000023) / Empty cabinet (EC000058)
Electric engineering, automation, process control engineering / Electrical installation, device / Electrical distribution system (including small distribution board) / Empty cabinet (small distribution board) (ecl@ss13-27-14-24-08 [ACN385016])
Mounting method
Surface mounted
Type of covering
Optional
Cover model
Closed
Type of door
None
Transparent cover/door
Yes
With lock
No
Nominal current (In)
1600 A
Height
500 mm
Width
375 mm
Depth
225 mm
Built-in depth
200 mm
Inner depth
200 mm
Material plate thickness cabinet
6 mm
Material plate thickness door/cover
6 mm
Colour
Grey
RAL-number
7035
Number of modules
1
Number of rows
0
Width in number of modular spacings
17
Number of openings for flange plates
6
Extension possible
Yes
Number of conduit inlets
104
Housing material
Plastic
Surface protection
Other
With mounting plate
Yes
Suitable for outdoor use
Yes
Suitable for lightning protection
Yes
Degree of protection (IP)
IP65
Degree of protection (NEMA)
Other
Protection class
II
Impact strength
Other
Circuit integrity
Other
Cover with overpressure release
Yes