General specifications
Product name
Eaton xEnergy Safety Ci empty enclosure insulated
Part no.
CI48-250
EAN
4015080836421
Product Length/Depth
275 millimetre
Product height
750 millimetre
Product width
375 millimetre
Product weight
6.13 kilogram
Compliances
RoHS conform
Certifications
EN 61439-2
EN 62208
Product Tradename
xEnergy Safety Ci
Product Type
Empty enclosure
Product Sub Type
Insulated
Delivery program
Type
Basic enclosure Panel enclosures xEnergy Safety Ci
Color
Gray
Nominal current
1600 A
Technical Data - Electrical
Circuit integrity
Other
Technical Data - Mechanical
Unit type
Single unit
Surface finishing
Resistant to corrosion
Surface protection
Other
Surface treatment
Resistant to corrosion
Enclosure material
Plastic
Width in number of modular spacings
17
Mounting depth with mounting plate
250 mm
Mounting method
Surface mounted (plaster)
Material
Halogen free
Glass-fibre reinforced polycarbonate (base)
Non-reinforced polycarbonate (cover)
Degree of protection
Other
IP65
IK10
Number of conduit inlets
0
Number of modules
1
Number of openings (flange plates)
6
Number of rows
0
Built-in depth
250 mm
Internal depth
250 mm
Cover/door color
Transparent
Cover/door model
Closed
Cover/door type
Optional
Transparent
None
Plate thickness (cabinet)
6 mm
Plate thickness (cover/door)
6 mm
Saline spray resistance
IEC 60068-2-11
Temperature-rise verification as per IEC 60890
Heat diss. ambient 35°C delta T: 20°C wall mount middle encl. top (IEC 60890)
44 W
Heat diss. ambient 35°C delta T: 35°C wall mount middle encl. top (IEC 60890)
88 W
Heat diss. ambient 35°C delta T:20°C wall mount individ. encl. top (IEC 60890)
52 W
Heat diss. ambient 35°C delta T:20°C wall mount starting encl. top (IEC 60890)
48 W
Heat diss. ambient 35°C delta T:35°C wall mount individ. encl. top (IEC 60890)
105 W
Heat diss. ambient 35°C delta T:35°C wall mount starting encl. top (IEC 60890)
96 W
Design verification as per IEC/EN 61439 - technical data
Temperature resistance
Temperature resistant: 80 °C (gasket)
Temperature resistant: -40 °C - 120 °C (enclosure)
Temperature resistant: 85 °C (enclosure bolt)
Ambient operating temperature details
-40 °C - 80 °C
Design verification as per IEC/EN 61439
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Lower part: 960 °C / cover: 850 °C
10.2.4 Resistance to ultra-violet (UV) radiation
Not relevant to indoor installations.
10.2.5 Lifting
40 kg per enclosure with support frame and lifting aid met, assembled and secured as per the latest applicable instruction leaflet.
10.2.6 Mechanical impact
IK10
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
IP65
10.4 Clearances and creepage distances
Is the panel builder's responsibility.
10.5 Protection against electric shock
Protection class 2, therefore not applicable.
10.6 Incorporation of switching devices and components
Is the panel builder's responsibility.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Ui = 1000 V AC
10.9.3 Impulse withstand voltage
8 kV
10.9.4 Testing of enclosures made of insulating material
Meets the product standard's requirements.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
Meets the product standard's requirements.
Additional information
Features
UV resistance beneath protective shield
Cover with overpressure release
Flammability characteristics (UL)
V1 (base) (UL94)
V2 (cover) (UL94)
Functions
Extension possible
Protection class
II
RAL-number
7035
Special features
Housing prepared for distribution board Two sides closed, can be folded out two sides open Sealable cover fasteners Integrated pressure-relief mechanism for short-circuits
Suitable for
Lightning protection
Outdoor use

Technical data ETIM 9.0

Distribution boards (EG000023) / Empty cabinet (EC000058)
Electric engineering, automation, process control engineering / Electrical installation, device / Electrical distribution system (including small distribution board) / Empty cabinet (small distribution board) (ecl@ss13-27-14-24-08 [ACN385016])
Mounting method
Surface mounted
Type of covering
Optional
Cover model
Closed
Type of door
None
Transparent cover/door
Yes
With lock
No
Nominal current (In)
1600 A
Height
750 mm
Width
375 mm
Depth
275 mm
Built-in depth
250 mm
Inner depth
250 mm
Material plate thickness cabinet
6 mm
Material plate thickness door/cover
6 mm
Colour
Grey
RAL-number
7035
Number of modules
1
Number of rows
0
Width in number of modular spacings
17
Number of openings for flange plates
6
Extension possible
Yes
Number of conduit inlets
0
Housing material
Plastic
Surface protection
Other
With mounting plate
No
Suitable for outdoor use
Yes
Suitable for lightning protection
Yes
Degree of protection (IP)
Other
Degree of protection (NEMA)
Other
Protection class
II
Impact strength
Other
Circuit integrity
Other
Cover with overpressure release
Yes