063961 B3.0/2-PKZ0
Three-phase busbar link, Circuit-breaker: 2, 90 mm, For PKZM0-... or PKE12, PKE32 without side mounted auxiliary contacts or voltage releases
EL Number (Norway)
4357208
Three-phase busbar link 3 poles for feeder unit of 2 PKZM0-... without auxiliary contact or voltage release built on laterally, can be extended by rotating installation, length 90mm protective against direct contact., Ue = 690 V, Iu = 63 A
General specifications
Product name
Eaton Moeller® series B3 Accessory Three-phase busbar link
Part no.
B3.0/2-PKZ0
EAN
4015080639619
Product Length/Depth
90 millimetre
Product height
34 millimetre
Product width
11 millimetre
Product weight
0.035 kilogram
Certifications
UL Category Control No.: NLRV
UL File No.: E36332
CE
UL
CSA File No.: 98494
CSA-C22.2 No. 14
UL 508
IEC/EN 60947-4-1
CSA
CSA Class No.: 3211-06
UL File No.: E36332
CE
UL
CSA File No.: 98494
CSA-C22.2 No. 14
UL 508
IEC/EN 60947-4-1
CSA
CSA Class No.: 3211-06
Product Tradename
B3
Product Type
Accessory
Product Sub Type
Three-phase busbar link
Catalog Notes
For parallel power feed to several motor-protective circuit-breakers on terminals 1, 3, 5
Features & Functions
Color
Black
Features
Insulated
Functions
Can be extended by rotating installation
Number of phases
3
Number of poles
Three-pole
General information
Electric connection type
Fork
Mounting width
45 mm
Overvoltage category
III
Pollution degree
3
Product category
Accessories
Rated impulse withstand voltage (Uimp)
6000 V AC
Suitable for
2 Circuit-breakers
Used with
PKE32
PKE12
PKZ0
PKE12
PKZ0
Climatic environmental conditions
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
55 °C
Electrical rating
Rated operational voltage (Ue) - max
690 V
Rated operational voltage (Ue) at AC - max
690 V
Rated uninterrupted current (Iu)
63 A
Short-circuit rating
Rated conditional short-circuit current (Iq)
0 kA
Rated short-time withstand current (Icw)
0 kA
Design verification
Equipment heat dissipation, current-dependent Pvid
3 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
1 W
Rated operational current for specified heat dissipation (In)
63 A
Static heat dissipation, non-current-dependent Pvs
0 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Technical data ETIM 9.0
Low-voltage industrial components (EG000017) / Phase busbar (EC000215)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Component for low-voltage switching technology / Phase busbar (ecl@ss13-27-37-13-06 [ACN992016])
Number of phases
3
Number of poles
3
Suitable for number of devices
2
Module width
45 mm
Cross section
0 mm²
Length
90 mm
Can be cut to size
No
Width in number of modular spacings
5
Rated permanent current Iu
63 A
Type of electric connection
Fork
Insulated
Yes
Rated surge voltage
6 kV
Conditioned rated short-circuit current Iq
0 kA
Max. rated operation voltage Ue
690 V
Rated short-time withstand current lcw
0 kA
Suitable for devices with N-conductor
No
Suitable for devices with auxiliary switch
No
Colour
Black
-
(Web)
-
Asset
-
Asset
-
Asset
-
Eaton EMEA Download-Center - download data for this item
-
Eaton EMEA Download-Center