Delivery program

Product range
Accessories
Basic function
Auxiliary contact
Part group reference
P1
P3
Late-break switching-on behavior, early-make switching-off behavior
The N/O is always connected as a load-shedding contact.
For left and/or right side mounting
Contacts
N/O = Normally open
1 N/O
N/C = Normally closed
1 NC
For use with
P1-…/Z, …/V, …/I2, …/IVS
P3-63/Z, …/V, …/I4, …/IVS
P3-100/Z, …/V, …/I5, …/IVS
For use with
P1, P3, intermediate
Rated uninterrupted current [Iu]
10 A

Technical data

Auxiliary contacts
Standards
Control circuit isolator to IEC/EN 60947-5
Rated insulation voltage [Ui]Rated insulation voltage [Ui ]
500 V AC
Rated uninterrupted current [Iu ]Rated uninterrupted current [Iu]
10 A
Rated operational current [Ie ]AC-15230 V [Ie]AC-15 with 230 V [Ie]
6 A
Rated operational current [Ie ]DC-13 [Ie ]125 V [Ie ]
1.1 A
Rated operational current [Ie ]DC-13 [Ie ]250 V [Ie ]
0.55 A
Short-circuit ratingMaximum fuse
10 A gG/gL
Terminal capacitiesSolid
1 x 0.75 - 2.5
2 x 0.75 - 1.5 mm2
Terminal capacitiesFlexible with ferrules to DIN 46228
1 x 0.5 - 1.5
2 x 0.5 - 1.5 mm2
Terminal capacitiesStripping length
7.5 mm
Tightening torque
1 Nm
Control circuit reliability at 24 V DC, 10 mA [Fault probability]
< 10-5, < 1 failure in 100000 operations HF

Design verification as per IEC/EN 61439

Technical data for design verification
Rated operational current for specified heat dissipation [In]
6 A
Heat dissipation per pole, current-dependent [Pvid]
0.11 W
Equipment heat dissipation, current-dependent [Pvid]
0 W
Static heat dissipation, non-current-dependent [Pvs]
0 W
Heat dissipation capacity [Pdiss]
0 W
Operating ambient temperature min.
-25 °C
Operating ambient temperature max.
+50 °C
IEC/EN 61439 design verification
10.2 Strength of materials and parts10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9 Insulation properties10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9 Insulation properties10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9 Insulation properties10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 7.0

Low-voltage industrial components (EG000017) / Auxiliary contact block (EC000041)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Component for low-voltage switching technology / Auxiliary switch block (ecl@ss10.0.1-27-37-13-02 [AKN342013])
Number of contacts as change-over contact
0
Number of contacts as normally open contact
1
Number of contacts as normally closed contact
1
Number of fault-signal switches
0
Rated operation current Ie at AC-15, 230 V
6 A
Type of electric connection
Screw connection
Model
Top mounting
Mounting method
Side mounting
Lamp holder
Other

Approvals

Product Standards
UL 508; CSA-C22.2 No. 14-05; IEC/EN 60947-5; CE marking
UL File No.
E36332
UL Category Control No.
NLRV
CSA File No.
12528
CSA Class No.
3211-05
North America Certification
UL listed, CSA certified

Dimensions

115X408
P1
115X409
P3