051776 DILER-22(220V50HZ,240V60HZ)
Contactor relay, 220 V 50 Hz, 240 V 60 Hz, N/O = Normally open: 2 N/O, N/C = Normally closed: 2 NC, Screw terminals, AC operation
Alternate Catalog No.
XTRM10A22B
Contactor relay, Product range: DILER Mini-contactors, Application: Contactor relays, Description: with interlocked opposing contacts, Connection technique: Screw terminals, Rated operational current Conventional free air thermal current, 1 pole Open at 50 °C: Ith =Ie= 10 A, Rated operational current AC-15 220 V 230 V 240 V: Ie= 6 A, 380 V 400 V 415 V: Ie= 3 A, Contacts N/O = Normally open: 2 N/O, Contacts N/C = Normally closed: 2 NC, Code number and version of combination Distinctive number: 22E, For use with: …DILE, Actuating voltage: 220 V 50 Hz, 240 V 60 Hz, Voltage AC/DC: AC operation, Degree of Protection: IP20, Instructions: Contact numbers to EN 50011, Coil terminal markings to EN 50005, Standards: IEC/EN 60947, EN 60947-5-1, VDE 0660, UL, CSA
Delivery program
Product range
DILER Mini-contactors
Application
Contactor relays
Description
with interlocked opposing contacts
Connection technique
Screw terminals
Rated operational current
Conventional free air thermal current, 1 poleOpenat 50 °C [Ith =Ie]
10 A
AC-15220 V 230 V 240 V [Ie]
6 A
AC-15380 V 400 V 415 V [Ie]
3 A
Contacts
N/O = Normally open
2 N/O
N/C = Normally closed
2 NC
Code number and version of combination
Distinctive number
22E
For use with
…DILE
Actuating voltage
220 V 50 Hz, 240 V 60 Hz
Voltage AC/DC
AC operation
Instructions
Contact numbers to EN 50011
Coil terminal markings to EN 50005
Coil terminal markings to EN 50005
Technical data
General
Standards
IEC/EN 60947, EN 60947-5-1, VDE 0660, UL, CSA
Lifespan, mechanicalAC operated [Operations]
10 x 106
Maximum operating frequency [Operations/h]
9000
Climatic proofing
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperatureOpen
-25 - +50 °C
Ambient temperatureEnclosed
- 25 - 40 °C
Mounting positionMounting position
As required, except vertical with terminals A1/A2 at the bottom
Mechanical shock resistance (IEC/EN 60068-2-27)Half-sinusoidal shock, 10 msBasic unit with auxiliary contact moduleN/O contact
10 g
Mechanical shock resistance (IEC/EN 60068-2-27)Half-sinusoidal shock, 10 msBasic unit with auxiliary contact moduleN/C contact
8 g
Degree of Protection
IP20
Protection against direct contact when actuated from front (EN 50274)
Finger and back-of-hand proof
Altitude
Max. 2000 m
WeightAC operated
0.17 kg
Terminal capacitiesScrew terminalsSolid
1 x (0.75 - 2.5)
2 x (0.75 - 2.5) mm2
2 x (0.75 - 2.5) mm2
Terminal capacitiesScrew terminalsFlexible with ferrule
1 x (0.75 - 1.5)
2 x (0.75 - 1.5) mm2
2 x (0.75 - 1.5) mm2
Terminal capacitiesScrew terminalsSolid or stranded
18 - 14
1 x (18 - 14)
2 x (18 - 14) AWG
1 x (18 - 14)
2 x (18 - 14) AWG
Terminal capacitiesScrew terminalsStripping length
8 mm
Terminal capacitiesScrew terminalsTerminal screw
M3.5
Terminal capacitiesScrew terminalsPozidriv screwdriver
2 Size
Terminal capacitiesScrew terminalsStandard screwdriver
0.8 x 5.5
1 x 6 mm
1 x 6 mm
Terminal capacitiesScrew terminalsMax. tightening torque
1.2 Nm
Contacts
Interlocked opposing contacts to ZH 1/457, including auxiliary contact module
Yes
Rated impulse withstand voltage [Uimp]
6000 V AC
Overvoltage category/pollution degree
III/3
Rated insulation voltage [Ui]
690 V AC
Rated operational voltage [Ue]
600 V AC
Safe isolation to EN 61140between coil and auxiliary contacts
300 V AC
Safe isolation to EN 61140between the auxiliary contacts
300 V AC
Rated operational currentConventional free air thermal current, 1 poleOpenat 50 °C [Ith =Ie]
10 A
Rated operational currentAC-15220 V 230 V 240 V [Ie]
6 A
Rated operational currentAC-15380 V 400 V 415 V [Ie]
3 A
Rated operational currentAC-15500 V [Ie]
1.5 A
Rated operational currentDC currentNotes
Switch-on and switch-off conditions based on DC-13, time constant as specified.
Rated operational currentDC currentDC L/R ≦ 15 msContacts in series:1 [24 V]
2.5 A
Rated operational currentDC currentDC L/R ≦ 15 msContacts in series:2 [60 V]
2.5 A
Rated operational currentDC currentDC L/R ≦ 15 msContacts in series:3 [110 V]
1.5 A
Rated operational currentDC currentDC L/R ≦ 15 msContacts in series:3 [220 V]
0.5 A
Rated operational currentControl circuit reliability [Failure rate]
<10-8, < one failure at 100 million operations
(at Ue = 24 V DC, Umin = 17 V, Imin = 5.4 mA) λ
(at Ue = 24 V DC, Umin = 17 V, Imin = 5.4 mA) λ
Short-circuit rating without weldingMaximum overcurrent protective device220 V 230 V 240 V
4 PKZM0
Short-circuit rating without weldingMaximum overcurrent protective device380 V 400 V 415 V
4 PKZM0
Short-circuit rating without weldingShort-circuit protection maximum fuse500 V
6 A gG/gL
Short-circuit rating without weldingShort-circuit protection maximum fuse500 V
10 A fast
Current heat loss at IthAC operated
1.1 W
Magnet systems
Voltage toleranceAC operatedSingle-voltage coil 50 Hz and dual-voltage coil 50 Hz, 60 Hz [Pick-up]
0.8 - 1.1 x Uc
Voltage toleranceAC operatedDual-frequency coil 50/60 Hz [Pick-up]
0.85 - 1.1 x Uc
Power consumptionAC operationSingle-voltage coil 50 Hz and dual-voltage coil 50 Hz, 60 Hz [Pick-up]
25 VA
Power consumptionAC operationSingle-voltage coil 50 Hz and dual-voltage coil 50 Hz, 60 Hz [Sealing]
4.6 VA
Power consumptionAC operationSingle-voltage coil 50 Hz and dual-voltage coil 50 Hz, 60 Hz [Sealing]
1.3 W
duty factor
100 % DF
Changeover time at 100 % US (recommended value)AC operated closing delay
14 - 21 ms
Changeover time at 100 % US (recommended value)AC operated N/O contact opening delay
8 - 18 ms
Changeover time at 100 % US (recommended value)AC operated With auxiliary contact module Max. closing delay
45 ms
Rating data for approved types
Auxiliary contactsPilot DutyAC operated
A600
Auxiliary contactsPilot DutyDC operated
P300
Auxiliary contactsGeneral UseAC
600 V
Auxiliary contactsGeneral UseAC
10 A
Auxiliary contactsGeneral UseDC
250 V
Auxiliary contactsGeneral UseDC
0.5 A
Design verification as per IEC/EN 61439
Datos técnicos para la verificación del diseño
Intensidad asignada de empleo para disipación térmica específica [In]
6 A
Disipación térmica por polo, en función de la intensidad [Pvid]
0.4 W
Disipación térmica del equipo, en función de la intensidad [Pvid]
0 W
Disipación térmica estática, en función de la intensidad [Pvs]
1.8 W
Capacidad de disipación térmica [Pdiss]
0 W
Temperatura ambiente mínima de funcionamiento
-25 °C
Temperatura ambiente máxima de funcionamiento
+50 °C
Verificación de diseño IEC / EN 61439
10.2 Resistencia de materiales y piezas10.2.2 Resistencia a la corrosión
Cumple con los requisitos de la norma del producto.
10.2 Resistencia de materiales y piezas10.2.3.1 Verificación de la estabilidad térmica de los armarios
Cumple con los requisitos de la norma del producto.
10.2 Resistencia de materiales y piezas10.2.3.2 Verificación de la resistencia de los materiales aislantes en condiciones de calor normales
Cumple con los requisitos de la norma del producto.
10.2 Resistencia de materiales y piezas10.2.3.3. Verificación de la resistencia de los materiales aislantes al calor excesivo y al fuego debido a los efectos eléctricos internos
Cumple con los requisitos de la norma del producto.
10.2 Resistencia de materiales y piezas10.2.4 Resistencia a radiación ultravioleta (UV)
Cumple con los requisitos de la norma del producto.
10.2 Resistencia de materiales y piezas10.2.5 Elevación
No se aplica, ya que todo el equipo de conmutación debe ser evaluado.
10.2 Resistencia de materiales y piezas10.2.6 Impacto mecánico
No se aplica, ya que todo el equipo de conmutación debe ser evaluado.
10.2 Resistencia de materiales y piezas10.2.7 Inscripciones
Cumple con los requisitos de la norma del producto.
10.3 Grado de protección de montajes
No se aplica, ya que todo el equipo de conmutación debe ser evaluado.
10.4 Distancias de separación y fuga
Cumple con los requisitos de la norma del producto.
10.5 Protección contra descargas eléctricas
No se aplica, ya que todo el equipo de conmutación debe ser evaluado.
10.6 Incorporación de dispositivos y componentes de conmutación
No se aplica, ya que todo el equipo de conmutación debe ser evaluado.
10.7 Conexiones y circuitos eléctricos internos
Es responsabilidad del cuadrista.
10.8 Conexiones de conductores externos
Es responsabilidad del cuadrista.
10.9 Propiedades de aislamiento10.9.2 Resistencia eléctrica de frecuencia de alimentación
Es responsabilidad del cuadrista.
10.9 Propiedades de aislamiento10.9.3 Tensión de impulso soportada
Es responsabilidad del cuadrista.
10.9 Propiedades de aislamiento10.9.4 Pruebas de armarios hechos de material aislante
Es responsabilidad del cuadrista.
10.10 Aumento de la temperatura
El cuadrista es responsable del cálculo del aumento de la temperatura. Eaton proporcionará datos de disipación de calor para los dispositivos.
10.11 Resistencia a los cortocircuitos
Es responsabilidad del cuadrista. Deben tenerse en cuenta las especificaciones de la aparamenta.
10.12 Compatibilidad electromagnética
Es responsabilidad del cuadrista. Deben tenerse en cuenta las especificaciones de la aparamenta.
10.13 Función mecánica
El dispositivo cumple los requisitos, siempre que se observe la información del folleto de instrucciones (IL).
Technical data ETIM 7.0
Conmutadores en baja tensión (EG000017) / Relé auxiliar (EC000196)
Tecnología electrónica, de automatización y de mando de procesos / Tecnología de conmutación de baja tensión / Contacto (baja tensión) / Contacto auxiliar, relé (ecl@ss10.0.1-27-37-10-01 [AAB716014])
Tensión de alimentación de nominal de control Us a CA 50HZ
220 - 220 Volt
Tensión de alimentación de nominal de control Us a CA 60HZ
240 - 240 Volt
Tensión de alimentación nominal Us en CC
0 - 0 Volt
Tipo de tensión para la activación
CA
Intensidad de funcionamiento nominal Ie, 400 V
3 Ampere
Circuito auxiliar del tipo de conexión
Conexión enroscada
Método de montaje
DIN-raíl/tornillo
Interfaz
No
Número de contactos auxiliares como contacto normalmente cerrado
2
Número de contactos auxiliares como contacto normalmente abierto
2
Número de contactos auxiliares como contacto normalmente cerrado, conmutación co
0
Número de contactos auxiliares como contacto normalmente abierto, entrada
0
Número de contactos auxiliares como contacto de intercambio
0
Con indicación LED
No
Funcionamiento manual
No
-
(Web)
-
Asset
-
Asset
-
Eaton EMEA Download-Center - download data for this item
-
Eaton EMEA Download-Center