Delivery program

Dimensions
461N180
Product range
xEnergy Safety Ci
Basic function
Prepared enclosures
Product function
Enclosures for miniature circuit-breakers
Accessories
Enclosures for miniature circuit-breakers
Single unit/Complete unit
Stand-alone device
Standards
EN 62208
EN 61439-2
Description
Housing prepared for distribution board
Two sides closed, can be folded out; two sides open
Housings for e.g. built-in devices MCB, RCD, RCBO, AFDD
Transparent cover with quick-release fasteners
Mounting rails for snap-fitting the devices
Blanking strip for unused mounting locations
Protective shroud with inscription label
Sealable cover fasteners
W/o PE/N terminals, please order separately
Degree of Protection
IP65
Type cover
Transparent
Model base
Partially closed, foldable
Width
187.5 mm
Height
250 mm
Depth
150 mm
Modular spacing (space units)
9 Number

Design verification as per IEC/EN 61439

Technical data for design verification
Heat dissipation, at an ambient temperature of 35°C, delta T: 20 degrees in top of the enclosure, calculated as per IEC 60890Individual enclosure for wall mounting [PV]
12 W
Heat dissipation, at an ambient temperature of 35°C, delta T: 20 degrees in top of the enclosure, calculated as per IEC 60890Starting enclosure for wall mounting [PV]
11 W
Heat dissipation, at an ambient temperature of 35°C, delta T: 20 degrees in top of the enclosure, calculated as per IEC 60890Middle enclosure for wall mounting [PV]
10 W
Heat dissipation, at an ambient temperature of 35°C, delta T: 35 degrees in top of the enclosure, calculated as per IEC 60890Individual enclosure for wall mounting [PV]
24 W
Heat dissipation, at an ambient temperature of 35°C, delta T: 35 degrees in top of the enclosure, calculated as per IEC 60890Starting enclosure for wall mounting [PV]
22 W
Heat dissipation, at an ambient temperature of 35°C, delta T: 35 degrees in top of the enclosure, calculated as per IEC 60890Middle enclosure for wall mounting [PV]
20 W
IEC/EN 61439 design verification
10.2 Strength of materials and parts10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Lower part: 960 °C / cover: 850 °C; meets the product standard's requirements.
10.2 Strength of materials and parts10.2.4 Resistance to ultra-violet (UV) radiation
Not relevant to indoor installations.
10.2 Strength of materials and parts10.2.5 Lifting
5 kg per enclosure with support frame and lifting aid met; assembled and secured as per the latest applicable instruction leaflet.
10.2 Strength of materials and parts10.2.6 Mechanical impact
IK10
10.2 Strength of materials and parts10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
IP65
10.4 Clearances and creepage distances
Is the panel builder's responsibility.
10.5 Protection against electric shock
Protection class 2, therefore not applicable.
10.6 Incorporation of switching devices and components
Is the panel builder's responsibility.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9 Insulation properties10.9.2 Power-frequency electric strength
Ui = 1000 V AC
10.9 Insulation properties10.9.3 Impulse withstand voltage
8 kV
10.9 Insulation properties10.9.4 Testing of enclosures made of insulating material
Meets the product standard's requirements.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
Meets the product standard's requirements.

Technical data ETIM 8.0

Distribution boards (EG000023) / Empty cabinet (EC000058)
Electric engineering, automation, process control engineering / Electrical installation, device / Electrical distribution system (incl. small distribution board) / Empty cabinet (small distribution board) (ecl@ss10.0.1-27-14-24-08 [ACN385011])
Mounting method
Surface mounted (plaster)
Type of cover
Optional
Cover model
Closed
Type of door
None
Transparent cover/door
Yes
With lock
No
Nominal current (In)
1600 A
Height
250 mm
Width
188 mm
Depth
150 mm
Built-in depth
100 mm
Internal depth
125 mm
Material plate thickness cabinet
6 mm
Material plate thickness door/cover
6 mm
Colour
Grey
RAL-number
7035
Number of modules
1
Number of rows
1
Width in number of modular spacings
9
Number of openings for flange plates
4
Extension possible
No
Number of conduit inlets
30
Material housing
Plastic
Surface protection
Other
With mounting plate
No
Suitable for outdoor use
Yes
Suitable for lightning protection
Yes
Degree of protection (IP)
IP65
Degree of protection (NEMA)
Other
Protection class
II
Impact strength
IK10
Circuit integrity
Other
Cover with overpressure release
Yes

Dimensions

450X004