Delivery program

Product range
ETR4 timing relays
Basic function
Timer relays
Function
On-delayed
Fixed timing function
Number of changeover contacts
1
Time range
0.05 s - 100 h
Time range
0.05 - 1 s
0.15 - 3 s
0.5 - 10 s
1.5 - 30 s
5 - 100 s
15 - 300 s
1.5 - 30 min
15 - 300 min
1.5 - 30 h
5 - 100 h
Rated operational current [Ie]
AC-14 [Ie]300 V [Ie ]
3 A
AC-14 [Ie]380 V 400 V 415 V [Ie ]
3 A
AC-14 [Ie]
Value applies starting with release 001.
AC-15220 V 230 V 240 V [Ie]
3 A
AC-15300 V [Ie]
3 A
AC-15380 V 400 V 415 V [Ie]
3 A
AC-15
Value applies starting with release 001.
Voltage range [ULN]
24 - 240 V AC, 50/60 Hz
24 – 240 V DC V
Width
22.5 mm
Terminal marking according to EN 50042
250S001

Technical data

General
Standards
Standard IEC/EN 61812
VDE 0435
Lifespan, mechanicalAC operated [Operations]
30 x 106
Lifespan, mechanicalDC operated [Operations]
30 x 106
Climatic proofing
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperatureAmbient temperature, storage
- 45 - + 85 °C
Ambient temperatureOpen
-25 - +60 °C
Ambient temperatureEnclosed
- 25 - + 45 °C
Mounting position
As required
Mechanical shock resistance (IEC/EN 60068-2-27)Half-sinusoidal shock, 20 msMake contact
4 g
Degree of protectionTerminals
IP20
Weight
0.1 kg
Terminal capacitiesSolid
1 x (0.5 - 2.5)
2 x (0.5 - 1.5) mm2
Terminal capacitiesFlexible with ferrule
1 x (0.5 - 2.5)
2 x (0.5 - 1.5) mm2
Terminal capacitiesSolid or stranded
1 x (20 - 14) AWG
Contacts
Rated impulse withstand voltage [Uimp]
4000 V AC
Rated impulse withstand voltage [Uimp]
6000 V AC
Value applies starting with release 001.
Overvoltage category/pollution degree
III/2
Rated insulation voltage [Ui]
400 V AC
Rated insulation voltage [Ui]
600 V AC
Value applies starting with release 001.
Rated operational voltage [Ue]
300 V AC
Rated operational voltage [Ue]
440 V AC
Value applies starting with release 001.
Safe isolation to EN 61140between coil and auxiliary contacts
250 V AC
Safe isolation to EN 61140between the auxiliary contacts
250 V AC
Making capacityAC-14 cos ϕ = 0.3 400 V
48 A
Making capacityAC-15 cos ϕ = 0.3 220 V
50 A
Making capacityDC-11 L/R - 40 ms
1.1 x Ie
Breaking capacity AC-14 cos ϕ = 0.3 440 V
3 A
Breaking capacity AC-15 cos ϕ = 0.3 220 V
3 A
Breaking capacity DC-11 L/R - 40 ms
1.1 x Ie
Rated operational current [Ie ]AC-14 [Ie]380 V 400 V 415 V [Ie ]
3 A
Rated operational current [Ie ]AC-14 [Ie]
Value applies starting with release 001.
Rated operational current [Ie ]AC--14440 V [Ie ]
3 A
Rated operational current [Ie ]AC-15220 V 230 V 240 V [Ie]
3 A
Rated operational current [Ie ]DC-11Note
Making and breaking conditions to DC13, time constant as stated
Rated operational current [Ie ]DC-11L/R max. 15 ms24 V [Ie ]
1.5 A
Rated operational current [Ie ]DC-11L/R max. 50 ms
1.2 A
Conv. thermal current [Ith]
6 A
Short-circuit rating without weldingNote
When supplied directly from mains or transformer > 1000 VA
Short-circuit rating without weldingMax. fuse, make contacts
6 A gG/gL
Short-circuit rating without weldingMax. fuse, break contacts
6 A gG/gL
Short-circuit rating without weldingMax. overcurrent protective device, 220/230 V
FAZ-B4/1-HI Type
Magnet systems
Rated operational voltage [Ue]AC
24 - 240
Rated operational voltage [Ue]DC
24 - 240
Rated operational voltage [Ue]Rated frequency AC
47 - 63 Hz
Rated operational voltage [Ue]Tolerance AC operated min.
0.85 x Uc
Rated operational voltage [Ue]Tolerance AC operated max.
1.1 x Uc
Rated operational voltage [Ue]Tolerance DC operated min.
0.7 x Uc
Rated operational voltage [Ue]Tolerance DC operated max.
1.1 x Uc
Power consumptionPick-up AC
2 VA
Power consumptionSealing AC
2 VA
Power consumptionPick-up DC
1.8 W
Power consumptionSealing DC
1.8 W
Duty factor
100 % DF
Maximum operating frequency
4000 Ops/h
Minimum command timeAC
50 ms
Minimum command timeDC
30 ms
Repetition accuracy (deviation)
≦ 0.5 %
Recovery time (after 100% time delay)
70 ms
Contact changeover time [tu ]
4 ms
Electromagnetic compatibility (EMC)
Electrostatic discharge (ESD)applied standard
IEC/EN 61000-4-2
Electrostatic discharge (ESD)Air discharge
8 kV
Electrostatic discharge (ESD)Contact discharge
6 kV
Electromagnetic fields (RFI)applied standard
IEC/EN 61000-4-3
Electromagnetic fields (RFI)
80 - 1000 MHz: 10
1.4 - 2 GHz: 3
2.0 - 2.7 GHz: 1 V/m
Radio interference suppression
EN 55011, Class B (conducted)
EN 55011, Class B (radiated)
Burst
Supply cables: 2
Signal cables: 1
according to IEC/EN 61000-4-4 kV
power pulses (Surge)
2 kV (symmetrical)
4 kV (asymmetrical)
according to IEC/EN 61000-4-5
Immunity to line-conducted interference to (IEC/EN 61000-4-6)
10 V

Design verification as per IEC/EN 61439

Technical data for design verification
Rated operational current for specified heat dissipation [In]
6 A
Heat dissipation per pole, current-dependent [Pvid]
1.4 W
Equipment heat dissipation, current-dependent [Pvid]
0 W
Static heat dissipation, non-current-dependent [Pvs]
1.8 W
Heat dissipation capacity [Pdiss]
0 W
Operating ambient temperature min.
-25 °C
Operating ambient temperature max.
+60 °C
IEC/EN 61439 design verification
10.2 Strength of materials and parts10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9 Insulation properties10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9 Insulation properties10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9 Insulation properties10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 7.0

Relays (EG000019) / Timer relay (EC001439)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Relay and socket / Timed relay (ecl@ss10.0.1-27-37-16-05 [AKF092013])
Type of electric connection
Screw connection
Function delay-on energization
Yes
Function delay on de-energization
No
Function floating contact on energization
No
Function floating contact on de-energization
No
Function star-delta
No
Function pulse shaping
No
Function flashing, starting with pause, fixed time
No
Function flashing, starting with pulse, fixed time
No
Clock function, starting with pause, variable
No
Clock function, starting with pulse, variable
No
With plug-in socket
No
Remote operation possible
No
Suitable for remote control
No
Pluggable on auxiliary contact block
No
Rated control supply voltage Us at AC 50HZ
24 - 240 V
Rated control supply voltage Us at AC 60HZ
24 - 240 V
Rated control supply voltage Us at DC
24 - 240 V
Voltage type for actuating
AC/DC
Nominal current
3 A
Time range
0.05 - 360000 s
Number of outputs, undelayed, normally closed contact
0
Number of outputs, undelayed, normally open contact
0
Number of outputs, undelayed, change-over contact
0
Number of outputs, delayed, normally closed contact
0
Number of outputs, delayed, normally open contact
0
Number of outputs, delayed, change-over contact
1
Outputs, reversible delayed/undelayed
No
With semiconductor output
No
Suitable for DIN rail (top hat rail) mounting
Yes
Suitable for front mounting
No
Width
23 mm
Height
82 mm
Depth
103 mm

Approvals

Product Standards
IEC/EN 61812-1; IEC/EN 60947-5-1; UL 508; CSA-22.2 No. 14; CE marking
UL File No.
E29184
UL Category Control No.
NKCR
CSA File No.
12528
CSA Class No.
3211-03
North America Certification
UL listed, CSA certified
Degree of Protection
IEC: IP20, UL/CSA Type: -

Characteristics

Flow diagram for timing functions

LED legend

 

Time not running, contact 15 – 18 closed

 

Time running, contact 15 – 18 closed

 

Time running, contact 15 – 18 not closed

 

① A2/A1 linked

② A2/A1 not linked

11 On-delayed
250U012

Dimensions

250X003
2527DIM-3
Applies to release 001 and higher