002253 CI48-200-NA
Insulated enclosure, top+bottom open, +door, HxWxD=796x421x225mm, NA type
EL-Nummer (Norway)
2502061
Distribution board basic enclosure, UL approved, material characteristic polycarbonate, impact-resistant, degree of protection IP65, patented cover fasteners with integrated overpressure compensation, on all 4 side walls with smooth, removable flanges equipped with sealable cover fasteners, RAL 7035, grey (base), transparent smoky, (cover), mounting depth with mounting plate=200mm, cover type: transparent smoky, base type: all-round UL flanges
Delivery program
Product range
xEnergy Safety Ci
Basic function
Basic enclosures
Product function
Distribution board enclosures for North America
Panel enclosures with cover and flanges
Panel enclosures with cover and flanges
Single unit/Complete unit
Single unit
Standards
UL508A
Degree of Protection
IP65
Description
Fitted with removable smooth flanges on all 4 sides
Fixing straps for wall fixing
Sealable cover fasteners
Fixing straps for wall fixing
Sealable cover fasteners
Type cover
Transparent
Surface finish
RAL 7035 (base)
Transparent, smoky gray (cover)
Transparent, smoky gray (cover)
Dimensions
Width
421 mm
Height
796 mm
Depth
225 mm
Mounting depth:
200 mm
Model base
Enclosure side plates with flanges
Model base
Enclosure side plates with removable smooth flanges
Technical data
General
Standards
UL508A
Climatic proofing
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperature
-40 - +80 °C
Degree of Protection
IP65
Operating and ambient conditions to VDE 0660 Part 500Surface finish
RAL 7035 (base)
Transparent, smoky gray (cover)
Transparent, smoky gray (cover)
Material characteristics
Surface finish
RAL 7035 (base)
Transparent, smoky gray (cover)
Transparent, smoky gray (cover)
Material properties
ElectricalTrack resistance
KB160, KC175 (base, to IEC 60112)
KB100, KC200 (cover, to IEC 60112)
KB100, KC200 (cover, to IEC 60112)
ElectricalSurface resistance to IEC 60093
1 Ω x 1013
ElectricalDielectric strength to IEC 60243-1
30 kV/mm
MechanicalImpact resistance
please require
AtmosphericSaline spray
IEC 60068-2-11
AtmosphericUV resistance
Beneath protective shield
AtmosphericWater consumption to DIN EN ISO 62
0.29 %
Design verification as per IEC/EN 61439
Technical data for design verification
Heat dissipation, at an ambient temperature of 35°C, delta T: 20 degrees in top of the enclosure, calculated as per IEC 60890Individual enclosure for wall mounting [PV]
47 W
Heat dissipation, at an ambient temperature of 35°C, delta T: 20 degrees in top of the enclosure, calculated as per IEC 60890Starting enclosure for wall mounting [PV]
44 W
Heat dissipation, at an ambient temperature of 35°C, delta T: 20 degrees in top of the enclosure, calculated as per IEC 60890Middle enclosure for wall mounting [PV]
40 W
Heat dissipation, at an ambient temperature of 35°C, delta T: 35 degrees in top of the enclosure, calculated as per IEC 60890Individual enclosure for wall mounting [PV]
95 W
Heat dissipation, at an ambient temperature of 35°C, delta T: 35 degrees in top of the enclosure, calculated as per IEC 60890Starting enclosure for wall mounting [PV]
88 W
Heat dissipation, at an ambient temperature of 35°C, delta T: 35 degrees in top of the enclosure, calculated as per IEC 60890Middle enclosure for wall mounting [PV]
81 W
IEC/EN 61439 design verification
10.2 Strength of materials and parts10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Lower part: 960 °C / cover: 850 °C; meets the product standard's requirements.
10.2 Strength of materials and parts10.2.4 Resistance to ultra-violet (UV) radiation
Not relevant to indoor installations.
10.2 Strength of materials and parts10.2.5 Lifting
40 kg per enclosure with support frame and lifting aid met, assembled and secured as per the latest applicable instruction leaflet.
10.2 Strength of materials and parts10.2.6 Mechanical impact
IK10
10.2 Strength of materials and parts10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
IP65
10.4 Clearances and creepage distances
Is the panel builder's responsibility.
10.5 Protection against electric shock
Protection class 2, therefore not applicable.
10.6 Incorporation of switching devices and components
Is the panel builder's responsibility.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9 Insulation properties10.9.2 Power-frequency electric strength
Ui = 1000 V AC
10.9 Insulation properties10.9.3 Impulse withstand voltage
8 kV
10.9 Insulation properties10.9.4 Testing of enclosures made of insulating material
Meets the product standard's requirements.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
Meets the product standard's requirements.
Technical data ETIM 8.0
Distribution boards (EG000023) / Empty cabinet (EC000058)
Electric engineering, automation, process control engineering / Electrical installation, device / Electrical distribution system (incl. small distribution board) / Empty cabinet (small distribution board) (ecl@ss10.0.1-27-14-24-08 [ACN385011])
Mounting method
Surface mounted (plaster)
Type of cover
Optional
Cover model
Closed
Type of door
None
Transparent cover/door
Yes
With lock
No
Nominal current (In)
1600 A
Height
750 mm
Width
375 mm
Depth
225 mm
Built-in depth
200 mm
Internal depth
200 mm
Material plate thickness cabinet
6 mm
Material plate thickness door/cover
6 mm
Colour
Grey
RAL-number
7035
Number of modules
1
Number of rows
0
Width in number of modular spacings
17
Number of openings for flange plates
0
Extension possible
Yes
Number of conduit inlets
0
Material housing
Plastic
Surface protection
Other
With mounting plate
No
Suitable for outdoor use
Yes
Suitable for lightning protection
Yes
Degree of protection (IP)
IP65
Degree of protection (NEMA)
13
Protection class
II
Impact strength
IK10
Circuit integrity
Other
Cover with overpressure release
Yes
-
Asset
-
Asset
-
Eaton EMEA Download-Center - download data for this item
-
Eaton EMEA Download-Center