General specifications
Product name
Eaton xEffect Ci Enclosures Switch- & Controlgear Enclosure
Part no.
CI48-200-NA
EAN
4015080022534
Product Length/Depth
225 millimetre
Product height
796 millimetre
Product width
421 millimetre
Product weight
6.658 kilogram
Compliances
UL 508A CSA-C22.2 No.94
CE marking
IEC/EN62208
RoHS conform
Certifications
UL (File No. E499317)
UL listed
UL508A
UL (Category Control Number NITW)
Specially designed for North America
Product Tradename
xEffect Ci
Product Type
Enclosures
Product Sub Type
Switch- & Controlgear Enclosure
Delivery program
Type
Basic enclosure Distribution board enclosures for North America Panel enclosures with cover and flanges xEnergy Safety Ci
Color
Gray
Nominal current
1600 A
Technical Data - Electrical
Dielectric strength
30 kV/mm
Creepage resistance
KB160, KC175 (base, to IEC 60112)
KB100, KC200 (cover, to IEC 60112)
Circuit integrity
Other
Technical Data - Mechanical
Unit type
Single unit
Base type
Enclosure side plates with removable smooth flanges
Surface finishing
Transparent, smoky gray (cover)
RAL 7035, light gray (base)
Surface protection
Other
Enclosure material
Plastic
Width in number of modular spacings
17
Mounting depth
200 mm
Mounting method
Surface mounted (plaster)
Degree of protection
UL/CSA Types 1, 12, 13, indoor only
IP65
IK10
IP65 (IEC)
13 (NEMA)
Number of conduit inlets
0
Number of modules
1
Number of openings (flange plates)
0
Number of rows
0
Built-in depth
200 mm
Internal depth
200 mm
Cover/door color
Transparent
Cover/door model
Closed
Cover/door type
Optional
Transparent
None
Plate thickness (cabinet)
6 mm
Plate thickness (cover/door)
6 mm
Saline spray resistance
IEC 60068-2-11
Climatic proofing
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Temperature-rise verification as per IEC 60890
Heat diss. ambient 35°C delta T: 20°C wall mount middle encl. top (IEC 60890)
40 W
Heat diss. ambient 35°C delta T: 35°C wall mount middle encl. top (IEC 60890)
81 W
Heat diss. ambient 35°C delta T:20°C wall mount individ. encl. top (IEC 60890)
47 W
Heat diss. ambient 35°C delta T:20°C wall mount starting encl. top (IEC 60890)
44 W
Heat diss. ambient 35°C delta T:35°C wall mount individ. encl. top (IEC 60890)
95 W
Heat diss. ambient 35°C delta T:35°C wall mount starting encl. top (IEC 60890)
88 W
Design verification as per IEC/EN 61439 - technical data
Ambient operating temperature details
-40 °C - 80 °C
Design verification as per IEC/EN 61439
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Lower part: 960 °C / cover: 850 °C
10.2.4 Resistance to ultra-violet (UV) radiation
Not relevant to indoor installations.
10.2.5 Lifting
40 kg per enclosure with support frame and lifting aid met, assembled and secured as per the latest applicable instruction leaflet.
10.2.6 Mechanical impact
IK10
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
IP65
10.4 Clearances and creepage distances
Is the panel builder's responsibility.
10.5 Protection against electric shock
Protection class 2, therefore not applicable.
10.6 Incorporation of switching devices and components
Is the panel builder's responsibility.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Ui = 1000 V AC
10.9.3 Impulse withstand voltage
8 kV
10.9.4 Testing of enclosures made of insulating material
Meets the product standard's requirements.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
Meets the product standard's requirements.
Additional information
Features
UV resistance beneath protective shield
Cover with overpressure release
Functions
Extension possible
Protection class
II
RAL-number
7035
Special features
Fitted with removable smooth flanges on all 4 sides Fixing straps for wall fixing Sealable cover fasteners
Suitable for
Outdoor use
Lightning protection
Surface resistance (IEC 60093)
10
Used with
Industrial control panels

Technical data ETIM 9.0

Distribution boards (EG000023) / Empty cabinet (EC000058)
Electric engineering, automation, process control engineering / Electrical installation, device / Electrical distribution system (including small distribution board) / Empty cabinet (small distribution board) (ecl@ss13-27-14-24-08 [ACN385016])
Mounting method
Surface mounted
Type of covering
Optional
Cover model
Closed
Type of door
None
Transparent cover/door
Yes
With lock
No
Nominal current (In)
1600 A
Height
796 mm
Width
421 mm
Depth
225 mm
Built-in depth
200 mm
Inner depth
200 mm
Material plate thickness cabinet
6 mm
Material plate thickness door/cover
6 mm
Colour
Grey
RAL-number
7035
Number of modules
1
Number of rows
0
Width in number of modular spacings
17
Number of openings for flange plates
0
Extension possible
Yes
Number of conduit inlets
0
Housing material
Plastic
Surface protection
Other
With mounting plate
No
Suitable for outdoor use
Yes
Suitable for lightning protection
Yes
Degree of protection (IP)
IP65
Degree of protection (NEMA)
13
Protection class
II
Impact strength
IK10
Circuit integrity
Other
Cover with overpressure release
Yes